Plan Review Details - Permit 08090577
Plan Review Stops For Permit 08090577
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-10 Cont ID  
Sent By jwitmer Date 2008-12-10 Time 08:01 Rev Time 0.33
Received By jwitmer Date 2008-12-10 Time 08:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-04 Cont ID  
Sent By jwitmer Date 2008-11-04 Time 13:40 Rev Time 0.77
Received By jwitmer Date 2008-11-04 Time 13:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-09 Cont ID  
Sent By jwitmer Date 2008-10-09 Time 13:35 Rev Time 1.55
Received By jwitmer Date 2008-10-09 Time 13:28 Sent To  
Notes
2008-10-09 13:52:49BUILDING PLAN REVIEW
 PERMIT: 08090577
 ADD: 5500 VILLAGE BLVD
 CONT: PRESIDENTIAL CONSTRUCTION
 TEL: (561)723-3370
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
 3) SHEET A-2 DOOR B IS MISSING THE REQUIRED 18" ON THE
 PULL SIDE OF THE PULL SIDE OF DOOR. 11-4.13.6
 MANEUVERING CLEARENCES, AT DOORS. MINIMUM MANEUVERING
 CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 4) SHEET A-4 DETAIL BREAK ROOM ELEVATION INDICATES
 DOORS ON THE SINK BASE UNIT. SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH
 THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH
 SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK
 TO ALLOW FORWARD APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM)
 UNDERNEATH THE SINK.
  
 5) THE COVERSHEET LIST THIS AS A TYPE III-B FULLY
 SPRINKLERED BUILDING WHERE AS THE LS -1 INDICATES THE
 BUILDING TO BE A V-B FULLY SPRINKLERED BUILDING. PLEASE
 COORDINATE PLANS TO A MINIMUM
 BUILDING TYPE. TABLE 503 & TABLE 601.
  
 6) GONZALEZ & GONZALEZ ENGINEERING, INC IS MISSING
 THEIR CERTIFICATE OF AUTHORIZATION.
 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-12-13 Cont ID  
Sent By rregueir Date 2008-12-13 Time 10:13 Rev Time 0.00
Received By rregueir Date 2008-12-13 Time 10:11 Sent To M
Notes
2008-12-13 10:12:55METHOD B ENERGY CALCULATIONS REMOVED FROM PERMIT
 APPLICATION. COMPLIANCE WITH 400C PRESCRIPTIVE
 REQUIREMENTS DEMONSTRATED ON PLANS. OK PER DVP.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-05 Cont ID  
Sent By dpalmer Date 2008-12-05 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2008-12-05 Time 13:06 Sent To  
Notes
2008-12-05 13:06:38 
 ** FAILED/TEMPORARY**
  
  
  
 1) NOTE: PLEASE SEE FBC 13-415.2.ABC.1. THE FOLLOWING
 IS EXTRACTED DIRECTLY FROM THE FLORIDA BUILDING CODE.
 **
 **TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE AMONG
 PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT METHOD
 OF CALCULATION HAS BEEN USED ARE NOT PERMITTED.**
 AS THE PLANS SUBMITTED INDICATE METHOD *C* AND THE
 FLA-COM BEING SUBMITTED IS METHOD*B* THIS A CLEAR
 CONFLICT WITH THE CODE SECTION AS NOTED ABOVE.
 THE MINIMUM PRESCRIPTIVE REQUIREMENTS FOR LIGHTING
 PERFORMANCE IS SHOWN ON ELECTRICAL PLANS ARE IS OK.
 HOWEVER THE FLA-COM B MAY NOT BE USED IN CONJUNCTION.
 PLEASE SEE SECTION 202 FOR DEFINITIONS OF A RENOVATION
 AND SECTION 13-400.0.C.4. THE FOLLOWING IS EXTRACTED
 DIRECTLY FROM THE LATEST REVISIONS WHICH ARE ADOPTED IN
 THE 2004 FBC.
  
 13-400.0.C.4 RENOVATED BUILDINGS.
 RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION
 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR
 COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE
 ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR
 THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT
 MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE
 MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE
 SYSTEM(S) BEING CHANGED.
 13-400.1 PRESCRIPTIVE REQUIREMENTS.
 BASIC PRESCRIPTIVE REQUIREMENTS SHALL BE MET FOR ALL
 BUILDINGS. THE SECTION NUMBER FOLLOWED BY THE COMBINED
 NUMBER AND LETTERS ?.1.ABC? INDICATES THESE BASIC
 PRESCRIPTIVE REQUIREMENTS (I.E., PRESCRIPTIVE
 REQUIREMENTS THAT SHALL BE MET BY BUILDINGS COMPLYING
 BY EITHER METHOD A, B, OR C) IN SECTIONS 401 THROUGH
 415. PRESCRIPTIVE REQUIREMENTS SPECIFIC TO METHOD A, B,
 OR C (I.E. ?.1.B? IS SPECIFIC TO METHOD B) SHALL BE MET
 WHEN COMPLYING WITH THE CODE BY THAT METHOD. WHERE A
 PRESCRIPTIVE REQUIREMENT SPECIFIC TO A METHOD IS MORE
 STRINGENT THAN THE BASIC PRESCRIPTIVE REQUIREMENT, THE
 MORE STRINGENT REQUIREMENT SHALL BE MET.
  
  
 ** UPON READING SECTION 202 OF THE FBC CHAPTER 13
 DEFINITIONS YOU WILL BE ABLE TO UNDERSTAND HOW THIS IS
 NOT A RENOVATED BUILDING BY THE DEFINITION.
  
 A CALL WAS PLACED TO THE ARCHITECT OF RECORD AND A
 MESSAGE WAS LEFT ON VOICE-MAIL. A CALL WAS ALSO PLACED
 TO MR. TIM CROWLEY OF PRESIDENTIAL CONSTRUCTION TO
 INFORM OF THE DISCREPANCIES.
  
  
 PLEASE CALL AS SOON AS POSSIBLE TO GO OVER FOR
 ACCEPTABLE FORM FOR OTHER TRADES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-06 Cont ID  
Sent By dpalmer Date 2008-11-06 Time 11:49 Rev Time 0.00
Received By dpalmer Date 2008-11-06 Time 11:49 Sent To  
Notes
2008-11-06 11:49:29 
  
  
 ** DENIED 2ND REVIEW **
  
 1) NOTE: ELECTRICAL PLANS NEED TO SHOW THE CIRCUITING
 OF EMERGENCY AND EXIT LIGHTS PER 700.12F. RESPONSE
 MENTIONS TO SEE NOTES ON THE LIFE SAFETY PLANS HOWEVER
 AS THE PLANS NEED TO SHOW THE CIRCUITING YOU MAY NOT
 QUOTE THE CODE IN LIEU OF SPECIFIC DETAIL.
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW WITH RESPECT TO
 THE LIGHTING PERFORMANCE CALCULATIONS. IN THE REVIEW
 COMMENTS IT STATED TO PLEASE CALL TO GO OVER HOW TO
 SHOW. THE PLANS SHOW CALCULATIONS BASED ON TABLE
 13-415.2.C WHICH ARE OK HOWEVER THERE ARE ADDITIONAL
 FIXTURES ON PLANS NOT FIGURED INTO THE CALCULATIONS.
 (RECESSED FIXTURES).
 PLEASE SEE THE PACKAGE ALSO SUBMITTED A FORM B, WHICH
 BY DEFINITION THIS IS NOT A RENOVATION MEETING SECTION
 202. THE COMPLIANCE METHOD SHOWN ON PLANS IS OK BUT
 PLEASE ADJUST THE NUMBER OF FIXTURES.
  
 3) NOTE: PLEASE SEE SOME AREAS ARE STILL MISSING
 REQUIRED LIGHTING CONTROLS PER
 13-415.1.ABC.1.1,.1.2,.1.3. SEE ROOM 117 FOR EXAMPLE
 WHICH STILL INDICATES STAND SWITCHES.
 PLEASE ALSO EXPLAIN THE NUMEROUS SWITCHES IN ROOM 100.
 AN OCCUPANT MUST BE ABLE TO SEE ALL LIGHTING WHICH IS
 BEING CONTROLLED OR MEET THE EXCEPTIONS IN THE SECTIONS
 GIVEN.
 PLEASE CALL TO GO OVER.
  
 4) NOTE: PLEASE SEE 230.2,230.2E ETC. PLEASE IDENTIFY
 ALL SERVICE EQUIPMENT. THE RISER AND LAYOUT IS NOT
 INFORMATIVE ENOUGH TO GRANT AN ADDITIONAL MAIN TO THE
 TENANT SPACE WHICH ALREADY CONTAINS ELECTRICAL SERVICE.
 WHAT IS THE VOLTAGE OF NEW?
 200,201 INDICATES 120/240V.
 FINAL DETERMINATION CAN NOT BE MADE AT THIS TIME.
 PLEASE SEE 220.87,215.5,215.3,230.42 ETC
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-09 Cont ID  
Sent By dpalmer Date 2008-10-09 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2008-10-09 Time 08:39 Sent To  
Notes
2008-10-09 08:39:41 
 ** DENIED **
  
 1) NOTE: PLEASE SEE THE SUBMITTED METHOD *A* ENERGY
 CALCULATIONS MAY NOT BE USED. THIS IS FOR A TENANT
 SPACE WITHIN A BUILDING. THE METHOD *A* BY DEFINITION
 IS FOR A *WHOLE BUILDING* WHICH THIS IS NOT.
 PLEASE SEE 13-101.1.
 PLEASE BE SURE TO SEE FBC 13-415.2,
 13-415.2.ABC.1.1,.1.2, TABLE 13-415.2.B., 13-415.2.C.
 PLEASE CALL TO GO OVER HOW PRESCRIPTIVE REQUIREMENTS
 CAN BE MET.
 THE SUBMITTED CALCULATIONS DO NOT CONTAIN ANY SEAL.
 THEY ALSO CONTAIN A PRINTED NAME OF THE PERSON
 PREPARING THE DOCUMENTS OTHER THAN THE LICENSED
 ARCHITECT OR ENGINEER.
  
 2) NOTE: PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR
 GONZALES AND GONZALES ENGINEERS INC. PLEASE SEE THESE
 ARE MISSING THE REQUIRED ENGINEERING BUSINESS LICENSE
 NUMBER WHICH IS ALSO KNOWN AS A CERTIFICATE OF
 AUTHORIZATION NUMBER PER FS 471.023, FAC 61G15-23.002.
  
 3) NOTE: NEW SERVICE AS SHOWN NOT GRANTED PER 230.2.
 PLEASE RE-WORK RISER AND UPGRADE EXISTING AS NEEDED.
 AS PROPOSED SERVICE IS NOT GRANTED NO REVIEW FOR NEW
 SHOWN WAS DONE.
 PLEASE ALSO SEE THE CODE AS THE RISER DOES SHOW
 ELECTRICAL FROM SEPARATE SERVICES INTO THE SAME
 JUNCTION BOXES WHICH IS NOT PERMITTED.
  
 4) NOTE: ACCESS CONTROLS AS NOTED ON PLANS WILL BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT APPLICATION
 ALONG WITH PLANS DETAILING ALL SYSTEM PER NFPA-101
 CHAPTER 7 FOR ACCESS CONTROLS, EGRESS ETC.
 EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS SHALL NOT
 BE IMPEDED.
  
 5) NOTE: PLEASE SEE FBC 11-4.27.4
 CONTROLS AND OPERATING MECHANISMS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 LBF
 (22.2 N).
  
 6) NOTE: PLEASE PROVIDE A BASE DESIGN DETAIL FOR
 OCCUPANCY SENSORS AND CONTROLS. WILL THIS BE A LOW
 VOLTAGE SYSTEM? LINE VOLTAGE SYSTEM? ETC
 PLEASE KNOW THE DEVICES USED IN AREAS SUCH AS THE
 MULTI-STALL RESTROOM SHALL BE ULTRASONIC/DUAL
 TECHNOLOGY.
 13-415.1.ABC.1.1,.1.2
  
 7) NOTE: PLEASE INDICATE ALL EMERGENCY AND EXIT
 LIGHTING TO THE LOCAL BRANCH CIRCUIT PER 700.12F.
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-12-11 Cont ID  
Sent By mwennerg Date 2008-12-11 Time 13:28 Rev Time 0.00
Received By mwennerg Date 2008-12-11 Time 13:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-10 Cont ID  
Sent By mwennerg Date 2008-11-10 Time 11:27 Rev Time 0.00
Received By mwennerg Date 2008-11-10 Time 11:27 Sent To  
Notes
2008-11-10 11:28:31PLANS STAMPED SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE ALARM REMODEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-21 Cont ID  
Sent By mwennerg Date 2008-10-21 Time 14:26 Rev Time 0.00
Received By mwennerg Date 2008-10-21 Time 14:26 Sent To  
Notes
2008-10-21 14:39:34***DENIED***
  
 1) CLASSIFICATION OF RATED DOORS SHALL BE EXPRESSED IN
 HOURS OR FRACTIONS PER NFPA 80, SEC. 4.1.1.
  
 2) DUCT SMOKE DETECTORS SHALL INITATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 3) IN ADDITION TO SHOP DRAWINGS AND PERMIT, FIRE
 SPRINKLER HEAD LAYOUT FOR COMMERCIAL PROJECTS SHALL BE
 PROVIDED PER FBC 106. HEAD LAYOUT MAY BE SHOWN ON
 REFLECTED CEILING PLAN.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 ACCESS CONTROL SYSTEM THAT SHALL COMPLY WITH NFPA 101,
 SEC. 7.2.1.6.2.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 16:52 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 16:52 Sent To  
Notes
2008-11-18 16:54:59TO "COMM" BD#49

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-31 Cont ID  
Sent By adarroug Date 2008-10-31 Time 13:48 Rev Time 0.00
Received By adarroug Date 2008-10-31 Time 13:48 Sent To  
Notes
2008-10-31 13:48:20TO "COMM" BD#56

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-21 Cont ID  
Sent By mwennerg Date 2008-10-21 Time 14:51 Rev Time 0.00
Received By mwennerg Date 2008-09-24 Time 11:57 Sent To  
Notes
2008-09-24 12:00:28TO "COMM" BD#35

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-02-17 Cont ID  
Sent By rregueir Date 2009-02-17 Time 18:02 Rev Time 0.00
Received By rregueir Date 2009-02-17 Time 18:02 Sent To PC
Notes
2009-02-17 18:02:35REVISED M-3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-12-13 Cont ID  
Sent By rregueir Date 2008-12-13 Time 10:11 Rev Time 0.00
Received By rregueir Date 2008-12-13 Time 10:11 Sent To PC
Notes
2008-12-13 10:15:07FORM 400B CALCULATIONS REMOVED FROM APPPLICATION. FORM
 400C PRESCRIPTIVE REQUIREMENTS ARE DEMONSTRATED ON
 PLANS, WITH SEPARATE COOLING LOAD CALCS, MEETING THE
 REQUIREMENTS FOR FBC CHAPTER 13 COMPLIANCE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-11-03 Cont ID  
Sent By tgordon Date 2008-11-03 Time 10:05 Rev Time 2.00
Received By tgordon Date 2008-11-03 Time 09:35 Sent To  
Notes
2008-11-03 10:05:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) THE RESPONSE TO REVIEW NOTES FROM 10-1-08 SYSTEM
 SIZING, ADDRESSES SENSIBLE LOADS. THE 2004 FBC DOES NOT
 ADDRESS SENSIBLE LOAD ONLY TOTAL LOADS, AS THE COOLING
 LOAD CALCULATIONS SUBMITTED SHOWS TOTAL COOLING
 REQUIRED IS BASED ON TOTAL LOAD. IF YOU WISH TO
 ENGINEER THE A/C SYSTEMS TO YOUR REQUIREMENTS PLEASE
 COMPLY WITH 2004 FBC 13-407.1.ABC.1 " EXCEPTIONS" A
 SUMMARY SHEET MAY BE SUBMITTED WHEN SIGNED AND SEALED
 BY THE ENGINEER AND HAS THE MINIMUM INFORMATION ON IT.
 **PROJECT NAME/OWNER... **PROJECT ADDRESS... **SIZING
 METHOD USED... **AREA IN SQUARE FEET... **OUTDOOR DRY
 BULB USED... **OUTDOOR WET BULB USED... **RELATIVE
 HUMIDITY... **INDOOR DRY BULB.... **TOTAL HEATING
 REQUIRED WITH OUTSIDE AIR... **TOTAL SENSIBLE GAIN...
 **TOTAL LATENT GAIN... **GRAINS WATER (DIFFERENCE)...
 **TOTAL COOLING REQUIRED WITH OUTSIDE AIR. (PLEASE HAVE
 THE TOTAL COOLING OF THE SUMMARY ADDRESS THE TOTAL
 COOLING OF THE SYSTEMS ON THE PLANS).
  
 2) SYSTEMS 1, 2, 3, 4, 6, 7, 8, AND 9 ARE OVER SIZED
 PER COOLING LOAD CALCULATIONS SUBMITTED. PER 2004 FBC
 13-407.1.ABC.1.1 HVAC SYSTEMS AND EQUIPMENT SHALL BE
 SIZED TO PROVIDE NO MORE THAN THE SPACE AND SYSTEM
 LOADS CALCULATED IN ACCORDANCE WITH SECTION
 407.1.ABC.1. A SINGLE PIECE OF EQUIPMENT PROVIDING BOTH
 COOLING AND HEATING SHALL SATISFY THIS PROVISION WHEN
 THE COOLING FUNCTION MEETS THE PROVISIONS OF SECTION
 407.1.ABC.1, AND THE HEATING FUNCTION IS SIZED AS SMALL
 AS POSSIBLE TO MEET THE LOAD WITHIN AVAILABLE EQUIPMENT
 OPTIONS.
  
 3) REVISED ENERGY CALCULATIONS SUBMITTED ARE NOT
 LISTING SYSTEMS 1, 2, 3, 4, AND 9. ALSO THE INPUT DATA
 REPORT SUBMITTED IS MISSING SYSTEMS 1, 2, 8, AND 9.
 PLEASE CORRECT PER 2004 FBC 13-103.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-01 Cont ID  
Sent By tgordon Date 2008-10-01 Time 16:04 Rev Time 1.45
Received By tgordon Date 2008-10-01 Time 16:04 Sent To  
Notes
2008-10-01 16:28:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS SHOW ZONE #5 NEEDS 8,876
 TOTAL COOLING BTU'S, MECHANICAL PLAN M-1 IS SHOWING
 SYSTEM #5 AS 24,500 (2 TON) TOTAL COOLING BTU'S. A 1.5
 TON SYSTEM WOULD MEET THE COOLING LOAD REQUIREMENTS,
 SEE 2004 FBC 13-407.1.ABC.1.1. PLEASE COMPLY.
  
 2) COOLING LOAD CALCULATIONS SHOW ZONE #6 NEEDS 15,670
 TOTAL COOLING BTU'S, MECHANICAL PLAN M-1 IS SHOWING
 SYSTEM #6 AS 59,700 (5 TON) TOTAL COOLING BTU'S. A 1.5
 TON SYSTEM WOULD MEET THE COOLING LOAD REQUIREMENTS,
 SEE 2004 FBC 13-407.1.ABC.1.1. PLEASE COMPLY.
  
 3) ONLY ONE SET OF THE COOLING LOAD CALCULATIONS WERE
 SUBMITTED, PLEASE SUBMIT TWO SETS, PER 2004 WPB AMEND.
 106.1.
  
 4) PLAN M-3 RETURN AIR DUCTS (FLEX) NEEDS TO BE SIZED
 IN ROOMS 117, 116, 113.112 AND 102. A SUPPLY AIR DUCT
 IN FILE AREA 111 NEEDS TO BE SIZED ALSO (SEE YELLOW
 HIGH LIGHT ON PLAN). PLEASE CORRECT PER 2004 FBC/M
 603.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-11-14 Cont ID  
Sent By kstevens Date 2008-11-14 Time 08:52 Rev Time 0.00
Received By kstevens Date 2008-11-14 Time 08:52 Sent To  
Notes
2008-11-14 08:54:50 
  
 PASSED/PROVISO:
  
 SECTIONS
 11-4.24.4 SINK DEPTH
 11-4.24.5 CLEAR FLOOR SPACE (FIG. 32)
 11-4.16.5 FLUSH CONTROLS
 604.9 W.H.A AT ICE MAKER IN REF.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By kstevens Date 2008-09-26 Time 15:47 Rev Time 0.00
Received By kstevens Date 2008-09-26 Time 10:31 Sent To  
Notes
2008-09-26 15:47:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. THE TITLE BLOCK SHALL CONTAIN THE
 ADDRESS AND PHONE NUMBER OF THE ARCHITECT. FAC
 61B1-16.004(1) & FS 481.2055.
  
 2. SUBMIT DETAILS FOR THE ACCESSIBLE WATER CLOSETS,
 LAVS & BREAK ROOM SINK. PLEASE SHOW COMPLIANCE WITH THE
 FOLLOWING:
  
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS (SHT A-2 REFERENCE NOTES 1 & 2
 INDICATE THE WRONG LENGTHS FOR THE BARS FOR THE BACK
 WALL AND THE SIDE WALL).
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
  
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C.11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 ___FOR SINKS:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
 F. 11-4.2.3 TURNING AREA IN BREAK ROOM
  
 3. SHT P.1 SANITARY RISER INDICATES A DRY HORIZONTAL
 VENT. THIS IS NOT APPROVED PER SECTION 905.3.
  
 4. SHT P.1 WATER RISER DOES NOT INDICATE THE NEW BREAK
 ROOM SINK. PLEASE SUBMIT A RISER THAT REFLECT THE FLOOR
 PLAN. SECTIONS 106.1.1 & 604.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  