| Plan Review Stops For Permit 08090562 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2009-10-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-10-06 |
Time |
16:49 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-10-06 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2009-10-06 16:50:35 | ARCHITECTURAL REVISION# 4 DATED 9-21-09 | | | AD1.1 | | | A1.1 | | | A2.1 | | | A3.1 | | | A4.2 | | | | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). AD1.1 PROVIDE | | | STOREFRONT SYSTEM PRODUCT APPROVALS BEFORE BUCK | | | INSPECTION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2009-07-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-07-28 |
Time |
13:00 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2009-07-28 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2009-07-28 12:57:50 | REV: | | | A1.1 REV# 2 6-30-09 | | | A2.1 REV# 2 6-30-09 | | | A3.1 REV# 2 6-30-09 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-05-28 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2009-05-28 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2009-05-27 |
Time |
09:23 |
Sent To |
FIRE |
|
| Notes |
| 2009-05-28 09:25:33 | REVISED PLAN FOR PHASED CONSTRUCTION. ADDED SHEET | | | PH1.1. REQUIRE FIRE REVIEW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-02-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-02-04 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-02-04 |
Time |
15:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-12-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-12-02 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-12-02 |
Time |
16:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-10-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-10-10 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-10-10 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2008-10-10 14:37:36 | BUILDING PLAN REVIEW | | | PERMIT: 08090562 | | | ADD: 4847 FRED GLADSTONE DR. | | | CONT: PRETI CONSTRUCTION INC. | | | TEL: (561)840-9949 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 10-9-08 | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS. INDICATE THIS | | | INFORMATION ON THE PLANS. | | | | | | 4) SHEET LS1.0 INDICATES THE OCCUPANT LOAD OF THE | | | BUILDING PER TABLE 1004.1.2. | | | | | | 5) SHEET A1.1 DOORS #14 AND #16 SHALL MEET THE | | | REQUIREMENTS OF FBC 11-4.13.6 AND FIGURE 25. SHOW | | | COMPLIANCE. 11-4.2.3 THE SPACE REQUIRED FOR A | | | WHEELCHAIR TO MAKE A 180-DEGREE TURN IS A CLEAR SPACE | | | OF 60 INCHES DIAMETER. SHOW THE WHEELCHAIR TURNING | | | SPACE IN THE AREAS OF THE DOORS MENTIONED ABOVE. | | | INDICATE THE WIDTH OF THE CORRIDOR AFTER THE NEW WALLS | | | ARE CONSTRUCTED IN THIS AREA. | | | | | | 6) THE FLOOR PLAN ON SHEET A1.1 AND SHEET FP1.02 DO NOT | | | CORRESPOND WITH EACH OTHER. THE NEW WALLS CONSTRUCTED | | | AROUND DOORS #10 #11 AND #14 ARE NOT SHOWN ON SHEET | | | FP1.02. THIS IS CRITICAL FOR THE LAYOUT OF THE NEW FIRE | | | SPRINKLER HEADS. THE DOOR SCHEDULE INDICATES THE DOOR | | | AS TEMPORARY BUT THE PLANS DO NOT STATE THE WALLS AS | | | TEMPORARY WALLS. IF BOTH THE WALLS AND DOORS IN THESE | | | AREAS ARE TEMPORARY STRUCTURES BUILT TO CONTROL THE | | | DUST FROM TRAVELING INTO OTHER AREAS BEING OCCUPIED | | | PLEASE INDICATE THIS INFORMATION ON THE PLANS. | | | | | | 7) SHEET LS1.1 INDICATES DOOR #10 AS AN EGRESS DOOR | | | HOWEVER, SHEET A1.1 SHOWS A NEW WALL CLOSING OFF THIS | | | DOOR. PLEASE MAKE SURE THE FLOOR PLAN ON THE | | | ARCHITECTURAL SHEETS CORRESPOND WITH THE ?MEP AND FS | | | SHEETS. CLARIFY. | | | | | | 8) THE OCCUPANT LOAD FOR ROOM #111-#113 IS A TOTAL OF | | | 61 OCCUPANTS, THEREFORE, TWO EXITS SHALL BE PROVIDED | | | FOR THAT ROOM. FBC 1014 AND TABLE 1014.1 AND 1018 AND | | | TABLE 108.1 IF ANY EQUIPMENT WILL BE PLACED IN THIS | | | ROOM PLEASE SHOW THE LOCATIONS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2009-10-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-10-11 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-10-11 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2009-10-11 08:19:35 | MINOR REVISIONS ON E1.02,1.03,1.04, | | | | | | LOW VOLTAGE, FIRE ALARM ARE UNDER SEPARATE PERMITS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-07-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-28 |
Time |
18:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-28 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2009-07-28 18:20:08 | | | | | | | ** REDLINED REVIEW ** | | | | | | 1) NOTE: LOW VOLTAGE, FIRE ALARM, OR LIGHTNING | | | PROTECTION SYSTEMS SHOWN ON PLANS ARE REQUIRED TO BE | | | UNDER SEPARATE PERMITS. TO DATE OF THIS REVIEW NO LOW | | | VOLTAGE, FIRE ALARM OR LIGHTNING PROTECTION SYSTEM | | | PERMITS HAVE BEEN APPLIED FOR. THESE PLANS MAY BE | | | REFERENCED FOR LOW VOLTAGE AND LIGHTNING PROTECTION. | | | FIRE ALARM PERMITS ARE UNDER SEPARATE PLANS AND PERMIT. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-06 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-06 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2009-02-06 15:17:09 | ** REDLINED PLANS | | | | | | 1) NOTE: FP SHEETS SEEM TO INDICATE NEW FIRE PUMP AND | | | JOCKEY PUMP HOWEVER ELECTRICAL RISER INDICATES BOTH AS | | | EXISTING. CALLED AND LEFT MESSAGE FOR THE ENGINEER TO | | | CONFIRM. FP SHEET WAS REDLINED TO STATE THESE ARE NOT | | | NEW AT THIS TIME AND ARE NOT INCLUDED IN THE SCOPE OF | | | WORK. | | | | | | 2) NOTE: TABLE FOR LPD CALCS SHOULD HAVE READ | | | 13-415.2.B | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-12-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-23 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-23 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2008-12-23 15:21:01 | ** DENIED REVIEW** | | | | | | | | | 1) NOTE: PLEASE SEE THAT THE ORIGINAL PERMIT | | | APPLICATION WAS NOT BROUGHT BACK IN WHEN PLANS WERE | | | RESUBMITTED. IN FACT THE APPLICATION IN PACKAGE IS A | | | PHOTO-COPY OF THE ORIGINAL. | | | PLEASE BRING BACK THE ORIGINAL SIGNED PERMIT | | | APPLICATION WHEN RE-SUBMITTING. | | | NO SUB CONTRACTORS ARE SIGNED ON. | | | | | | 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1, .1.1, .1.2, | | | .1.3. LIGHTING CONTROLS AS SHOWN DO NOT COMPLY FOR | | | AUTOMATED LIGHTING CONTROLS. THIS IS LIGHTING CONTROLS | | | IN A BUILDING GREATER THAN 5000 SQ FT. ALL NEW LIGHTING | | | CONTROLS BEING INSTALLED SHALL BE AUTOMATED OF SOME | | | SORT. A MANUAL SWITCH DOES NOT MEET THE CODE. | | | A MANUAL OVER RIDE OF A SYSTEM, IF A SYSTEM IS PROPOSED | | | IS PERMITTED HOWEVER THERE IS DOZENS OF WAYS TO COMPLY | | | WITH THE MINIMUM PRESCRIPTIVE REQUIREMENTS. | | | 13- | | | | | | | | | 3) NOTE: PLEASE SUBMIT AND SHOW MINIMUM CODE COMPLIANCE | | | FOR LIGHTING PERFORMANCE CALCULATIONS AS PART OF THE | | | RECORD PLANS. THE SEPARATE SUBMITTED SHEET DOES NOT | | | CONTAIN ANY INFORMATION FROM THE ELECTRICAL DESIGNER OF | | | RECORD. NO TITLE BLOCKS, NOT SIGNED AND SEALED ETC. | | | PLEASE SEE THE ALLOWANCES ON THIS SHEET ALSO NEED TO BE | | | ADJUSTED FOR CODE COMPLIANCE. ONE EXAMPLE WOULD BE | | | STORAGE ROOM WHICH INDICATES AN ALLOWANCE FROM FBC OF | | | 1.1. HOWEVER NO STORAGE ROOMS LISTED IN TABLE FBC | | | 13-415.2.B ALLOWS A 1.1 FOR STORAGE. IN FACT HOSPITAL | | | STORAGE AREAS IS ACTUALLY THE HIGHEST WHICH IS .09. | | | PLEASE COMPLETE FIXTURE LEGEND FOR ALL FIXTURES. | | | EXAMPLE OF ONE IS *G* WHICH IS BLANK. | | | PLEASE ADJUST FBC ALLOWANCES, PLEASE PLACE ON PLANS, | | | PLEASE COMPLETE TITLE BLOCKS, SIGNED, DATED SEALED ETC. | | | 13-415.2, 13-415.2.ABC.1.1, .1.2, FS 471.025, FAC | | | 61G15-23.002. | | | | | | | | | 4) NOTE: PLEASE SEE 410.5 AND 410.6 FOR LIGHT FIXTURE | | | IN CLOSET AREA #104. AS SHOWN THIS APPEARS TO BE OVER | | | SHELVING AREAS WHICH IS A FIRE HAZARD. | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-10-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-14 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-14 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2008-10-14 14:39:32 | | | | ** DENIED REVIEW** | | | | | | | | | 1) NOTE: THE SCOPE OF WORK FOR WHAT APPEARS TO BE A | | | RESIDENTIAL UNIT HAS CREATED SEVERAL COMMENTS FROM | | | MULTIPLE TRADES INCLUDING ZONING. IF THIS IS A SEPARATE | | | RESIDENTIAL DWELLING/APARTMENT THE WIRING METHODS | | | REQUIRED IN NEC 210.52, 2108 NEED TO BE MET. | | | AN EXAMPLE OF THIS WOULD BE 210.52(D)3 FOR CIRCUITING | | | OF THE BATH GFI WHICH IS SHOWN ON OTHER THAN THE | | | BATHROOM WHICH IS NOT PERMITTED PER SECTION GIVEN. | | | ANOTHER WOULD BE THE REQUIRED CIRCUITING FOR ARC FAULT | | | PER 210.12. SPACING PER 210.52, SPACING ALONG KITCHEN | | | COUNTER SPACE AREAS PER 210.52(C) 1-5 ETC | | | AS THE SCOPE OF THIS UNCLEAR AT THIS TIME FOR THIS | | | RESIDENTIAL UNIT, WIRING ETC CAN NOT BE CONFIRMED AS | | | COMPLIANT. IF RESIDENTIAL THE WIRING AS SHOWN DOES NOT | | | MEET THE NEC. | | | | | | 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE FOR NEW | | | AREAS WHERE LIGHTING IS BEING INSTALLED. 13-415.2, | | | 13-415.2.ABC.1.1, .1.2, TABLES 13-415.2.B, 13-415.2.C | | | | | | 3) NOTE: PLEASE INDICATE LIGHTING CONTROL DEVICES PER | | | 13-415.1.ABC.1.1, .1.2, .1.3 FOR NEW BEING INSTALLED. | | | | | | 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR ADA | | | COMPLIANCE PER FBC 11-4.28.1, .2 AND .3. | | | | | | 5) NOTE: THE LIGHTNING PROTECTION SYSTEM AS NOTED SHALL | | | BE UNDER SEPARATE PERMIT AS WELL AS LOW VOLTAGE | | | SYSTEMS. THE LOW VOLTAGE SYSTEM MAY REMAIN ON PLANS AND | | | THESE PLANS MAY BE REFERENCED FOR A TURNAROUND PERMIT | | | ONCE MAIN PERMIT IS ISSUED. | | | SEPARATE FEES ETC WILL BE APPLIED FOR VALUE OF SCOPE. | | | | | | 6) NOTE: THE PERMIT PACKAGE CONTAINS A RESPONSE LETTER | | | FROM THE ENGINEER TO ELECTRICAL COMMENTS AS WELL AS | | | RESPONSES TO OTHER TRADES. THIS IS THE FIRST TIME THIS | | | IS IN FOR PERMITTING AND IT IS UNCLEAR WHERE THESE | | | RESPONSES COME FROM. THE ELECTRICAL NOTES WHICH WERE | | | RESPONDED TO WERE NOT FROM THIS OFFICE. | | | A CALL WAS PLACED TO THE ELECTRICAL ENGINEER OF RECORD | | | TO CLARIFY WHERE THESE NOTES CAME FROM HOWEVER WAS OUT | | | OF THE OFFICE AT THE TIME OF THE REVIEW. | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2009-10-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-10-21 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-10-21 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2009-10-21 16:35:40 | *****REVISION, DATED 9/21/2009, APPROVED***** | | | | | | | | | REVISED PLAN SHEETS A1.1, A2.1, E1.02, E1.04, AND | | | FP1.02 WERE STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-08-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-08-03 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-08-03 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2009-08-03 15:27:14 | *****REVISION, DATED 6/30/2009, APPROVED***** | | | | | | | | | REVISED PLAN SHEETS A1.1, A2.1, E1.02, AND E1.04 WERE | | | STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-05-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-28 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-28 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2009-05-28 15:21:54 | *****REVISION #2, DATED 4/20/2009, APPROVED***** | | | | | | | | | SINGLE REVISED SHEET PH1.1 STAMPED, INITIALED, AND | | | DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-12-24 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-24 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-24 |
Time |
10:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-10-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-23 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-10-23 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2008-10-23 10:39:39 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 3) DAMPERS TO BE TESTED FOR CLOSURE PER REQUIREMENTS OF | | | UL 555 PRIOR TO FINAL INSPECTION. | | | | | | 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING. | | | | | | 5) ONLY ONE EXIT SHOWN IN AREAS WITH OCCUPANT LOAD OF | | | (61) PERSONS. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2009-09-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-09-29 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-09-29 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-08-11 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-08-11 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-08-11 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2009-08-11 09:17:13 | GAVE TO RON | | 2009-08-11 09:16:00 | IN MECHANICAL BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-07-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-07-15 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-07-15 |
Time |
14:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-04-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-29 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-29 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2009-04-29 14:35:55 | TO C15 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-01-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-27 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-27 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2009-01-27 10:30:07 | TO "COMM" BD#49 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-24 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-24 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2008-11-24 15:59:04 | TO "COMM" BD#13 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-10-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-23 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-09-24 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2008-09-24 08:49:42 | TO "COMM" BD#11 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2009-10-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-10-23 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-10-23 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2009-10-23 13:45:08 | REVISED M1.02 DELTA 4 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2009-08-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-08-18 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-08-18 |
Time |
10:59 |
Sent To |
PC |
|
| Notes |
| 2009-08-18 10:59:38 | REVISED M1.02 AND M1.03 DELTA 3 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2009-07-27 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-27 |
Time |
18:28 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-27 |
Time |
17:55 |
Sent To |
|
|
| Notes |
| 2009-07-27 18:01:36 | M1.03 DELTA 2 REVISION DENIED | | | | | | DETAIL #5 SHOWS AN INSTALLATION DETAIL FOR A SLEEVE TO | | | BE USED WHERE DUCTS PENETRATE RATED WALL ASSEMBLIES | | | WITHOUT FIRE DAMPERS. ALL DUCT PENETRATIONS OF RATED | | | WALL ASSEMBLIES WHICH ARE ALLOWED WITHOUT FIRE DAMPERS | | | SHALL BE PROTECTED WITH A LISTED THROUGH-PENETRATION | | | FIRESTOP SYSTEM IN ACCORDANCE WITH RBC-M 607.1.1 AND | | | FBC-B SECTION 712. INDICATE ON PLANS EACH LOCATION | | | WHERE A FIRE DAMPER IS INSTALLED AND WHERE A | | | THROUGH-PENETRATION FIRESTOP SYSTEM IS TO BE USED IN | | | ACCORDANCE WITH FBC-M 607.8. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | | | | DENIED REVISION PAGES FILED IN SMALL PLAN CABINET UNDER | | | "P" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-07-27 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-27 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-27 |
Time |
17:54 |
Sent To |
|
|
| Notes |
| 2009-07-27 17:54:53 | REVISED M1.01 AND M1.02, DELTA 2 | | | PAGE M1.04 NO CHANGES - RESTAMPED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-12-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-12-13 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-12-13 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2008-12-13 15:33:42 | REVIEW #: 2ND | | | ACTION: PASS W/ PROVISO | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | COMMENTS 1,3,4 AND NOTE HAVE BEEN ADEQUATELY ADDRESSED. | | | PERMIT MAY BE ISSUED WITH THE FOLLOWING PROVISO: | | | | | | *******************PROVISO********************* | | | EXHAUST FAN EXPOSED TO WIND SHALL BE DESIGNED AND | | | INSTALLED TO RESIST WIND PRESSURES IN ACCORDANCE WITH | | | FBCM 301.13 AND FBCB 1609. | | | PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE OR A | | | RATIONAL ANALYSIS FROM A FLORIDA LICENSED STRUCTURAL | | | ENGINEER CERTIFYING THE PROPOSED FAN IS DESIGNED FOR | | | WIND RESISTANCE BASED ON THE LOCATION INSTALLED | | | (ELEVATION, EXPOSURE CATEGORY AND WIND IMPORTANCE | | | FACTOR) AS DETERMINED BY FBCB SECTION 1609. | | | | | | NOTE: DESIGNER'S WRITTEN RESPONSE INDICATES NO FAN | | | WHICH IS DESIGNED FOR WIND RESISTANCE COULD BE FOUND. | | | THERE IS AT LEAST ONE AND POSSIBLY MORE EXHAUST FAN | | | MANUFACTURERS WITH A LINE OF FANS DESIGNED FOR WIND | | | RESISTANCE. THIS OFFICE IS PROHIBITED BY POLICY FROM | | | RECOMMENDING SPECIFIC BRANDS OR MANUFACTURERS. A SEARCH | | | OF MIAMI-DADE'S NOA DATABASE MAY PROVIDE ADDITIONAL | | | GUIDANCE IN YOUR SEARCH FOR A CODE COMPLAINT OUTDOOR | | | APPLIANCE. AN NOA IS NOT SPECIFICALLY REQUIRED FOR | | | OUTDOOR APPLIANCES. HOWEVER, THE DATA PROVIDED IN A | | | CURRENT NOA MAY BE USED AND WOULD BE ACCEPTED BY THIS | | | AHJ AS A DEMONSTRATION OF CODE COMPLIANCE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-10-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-10-18 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-10-18 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2008-10-18 15:52:42 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M1.03 SHOWS NEW ROOF-MOUNTED EXHAUST FAN. | | | PROVIDE STRUCTURAL DETAIL SHOWING HOW ROOF OPENING | | | REINFORCEMENT IS TO BE INSTALLED AND HOW ROOF CURB IS | | | TO BE ATTACHED TO STRUCTURE FOR WIND RESISTANCE IN | | | ACCORDANCE WITH FBCM 301.13. | | | | | | 2. PAGE M1.03 SHOWS NEW ROOF-MOUNTED EXHAUST FAN. NO | | | INFORMATION WAS PROVIDED SHOWING THE EXHAUST FAN IS | | | DESIGNED TO RESIST WIND PRESSURES IN ACCORDANCE WITH | | | FBCM 301.13. PROVIDE MANUFACTURER?S DATA SHOWING WIND | | | RESISTANCE INFORMATION. THIS INFORMATION SHOULD INCLUDE | | | INFORMATION ON ATTACHMENT OF APPLIANCE (EXHAUST FAN) TO | | | ROOF CURB. | | | | | | 3. WHAT IS THE PITCH OF THE ROOF WHERE NEW EF-7 IS TO | | | BE INSTALLED? WHERE APPLIANCES ARE INSTALLED ON A ROOF | | | HAVING A SLOPE OF THREE UNITS VERTICAL IN 12 UNITS | | | HORIZONTAL OR GREATER AND HAVING AN EDGE MORE THAN 30 | | | INCHES ABOVE GRADE AT SUCH EDGE, A LEVEL PLATFORM SHALL | | | BE PROVIDED ON EACH SIDE OF THE APPLIANCE TO WHICH | | | ACCESS IS REQUIRED BY THE MANUFACTURER?S INSTALLATION | | | INSTRUCTIONS FOR SERVICE, REPAIR OR MAINTENANCE IN | | | ACCORDANCE WITH FBCM 306.6. THE PLATFORM SHALL NOT BE | | | LESS THAN 30 INCHES IN ANY DIMENSION AND SHALL BE | | | PROVIDED WITH GUARDS IN ACCORDANCE WITH SECTION 304.10. | | | | | | 4. WHAT IS THE HEIGHT OF THE ROOF WHERE NEW EF-7 IS | | | LOCATED? WHAT IS THE PITCH OF THE ROOF WALKING SURFACE | | | WHICH WILL BE USED TO ACCESS THIS FAN? WHERE APPLIANCES | | | REQUIRING ACCESS ARE INSTALLED ON ROOFS AT A HEIGHT | | | EXCEEDING 16 FEET, SUCH ACCESS SHALL BE PROVIDED BY A | | | PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH | | | SHALL BE FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND | | | APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT | | | REQUIRE WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 | | | UNITS VERTICAL IN 12 UNITS HORIZONTAL IN ACCORDANCE | | | WITH FBCM 306.5. | | | | | | NOTE: NEW RANGE PROPOSED FOR OCCUPATIONAL THERAPY AREA | | | IS SHOWN ON ELECTRICAL PLANS TO BE FED BY 120V FOR | | | DEMONSTRATION PURPOSES ONLY AND NO COOKING. THIS RANGE | | | SHALL REMAIN INOPERABLE FOR COOKING AT ALL TIMES. IF AT | | | ANY THIME THIS RANGE BECOMES OPERATIONAL FOR COOKING, A | | | TYPE I HOOD WITH FIRE SUPPRESSION SYSTEM WILL BE | | | REQUIRED IN ACCORDANCE WITH FBCM 507.2.1 AND 509.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
2 |
Status |
P |
Date |
2009-01-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-07 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-07 |
Time |
15:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
1 |
Status |
P |
Date |
2008-09-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-09-26 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-09-26 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2009-01-07 15:08:46 | | | | | | | SEPARATE MED-GAS PERMIT IS REQUIRED. THE CERTIFICATIONS | | | FOR THE QUALIFER, THE INSTALLER AND THE BRAZER SHALL BE | | | SUBMITTED WITH THE MED-GAS PERMIT APPLICATION. FAC | | | 61G4-15.031. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2009-10-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-10-05 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-10-05 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2009-10-05 14:38:26 | NO PLUMBING REVISIONS FOUND/SUBMITTED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-07-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-07-29 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-07-29 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2009-07-29 14:53:22 | REVISION OK -- SHT P-02 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-01-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-07 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-07 |
Time |
14:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-09-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-09-26 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-09-25 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2008-09-25 16:01:23 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | NAPA 99C-99 | | | FLORIDA ADMINISTRATIVE CODE | | | | | | 1. SHTS LS1.0 & LS1.1 CODE REFERENCE SHALL INCLUDE THE | | | 2007 REVISIONS. | | | | | | 2. SHTS LS1.0 & LS1.1 OCCUPANCY STATES "SEE PLAN" | | | PLEASE INDICATE WHERE ON THE PLANS THE OCCUPANCY OF THE | | | STRUCTURE CAN BE LOCATED. | | | | | | 3. SHT A3.1 DETAIL 15 SHOWS THE FLUSH CONTROL FOR THE | | | W/C TO THE WALL SIDE OF THE TANK. PER SECTION 11-4.16.5 | | | THE FLUSH CONTROL SHALL BE ON THE WIDE SIDE. PLEASE | | | SHOW THE FLUSH CONTROL WHERE REQUIRED. | | | | | | 4. SHT A3.1 DETAIL 15 CLEARANCE FOR THE LAV SHALL BE AT | | | LEAST 29 INCHES PER SECTION 11-4.19.2. IT IS SHOWN AS | | | 27 INCHES. | | | | | | 5. SHT A3.1 DETAIL 15 TUB CONTROLS SHALL BE LOCATED PER | | | SECTION 11-4.20.5 & FIGURE 34. | | | | | | 6. SHT A3.1 DETAIL 21 SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.24.3 KNEE CLEARANCE | | | B. 11-4.24.4 SINK DEPTH | | | C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH | | | REQUIRED. CABINET DOORS NOT APPROVED IN THE CLEAR FLOOR | | | SPACE. | | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | | | | | 7. SHT P1.02 PER SECTION 406.3, THE AUTOMATIC CLOTHES | | | WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH DRAIN A | | | MINIMUM OF 3 INCHES. 2 INCHES IS SHOWN. | | | | | | 8. A SEPARATE MED-GAS PERMIT IS REQUIRED. | | | CERTIFICATIONS FOR THE QUALIFIER, THE INSTALLERS AND | | | THE BRAZERS SHALL BE SUBMITTED WITH THE MED GAS PERMIT | | | APPLICATION. FAC 61G4-15.031. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-11-25 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2008-11-25 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-11-25 |
Time |
16:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-09-29 |
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-09-29 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2008-09-29 16:11:57 | FAILED | | | | | | THE PLANS CALL OUT THAT THE REMODEL IS FOR A BEDROOM | | | W/KITCHEN AND BATH. PLEASE CLARIFY THE USE OF THIS | | | SPACE. IS THIS AN ADDITIONAL LIVING UNIT? IF THIS IS TO | | | BE A RESIDENTIAL UNIT, WHETHER ACLF OR EMPLOYEE, THEN | | | AN AMENDMENT TO THE MORSE LIFE CSPD IS REQUIRED. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|