Plan Review Details - Permit 08090562
Plan Review Stops For Permit 08090562
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-10-06 Cont ID  
Sent By jwitmer Date 2009-10-06 Time 16:49 Rev Time 0.77
Received By jwitmer Date 2009-10-06 Time 16:49 Sent To  
Notes
2009-10-06 16:50:35ARCHITECTURAL REVISION# 4 DATED 9-21-09
 AD1.1
 A1.1
 A2.1
 A3.1
 A4.2
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). AD1.1 PROVIDE
 STOREFRONT SYSTEM PRODUCT APPROVALS BEFORE BUCK
 INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-07-28 Cont ID  
Sent By jwitmer Date 2009-07-28 Time 13:00 Rev Time 1.00
Received By jwitmer Date 2009-07-28 Time 12:30 Sent To  
Notes
2009-07-28 12:57:50REV:
 A1.1 REV# 2 6-30-09
 A2.1 REV# 2 6-30-09
 A3.1 REV# 2 6-30-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-05-28 Cont ID  
Sent By kconrad Date 2009-05-28 Time 09:23 Rev Time 0.00
Received By kconrad Date 2009-05-27 Time 09:23 Sent To FIRE
Notes
2009-05-28 09:25:33REVISED PLAN FOR PHASED CONSTRUCTION. ADDED SHEET
 PH1.1. REQUIRE FIRE REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-02-04 Cont ID  
Sent By mjacobs Date 2009-02-04 Time 15:30 Rev Time 0.00
Received By mjacobs Date 2009-02-04 Time 15:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-12-04 Cont ID  
Sent By mjacobs Date 2008-12-02 Time 16:55 Rev Time 0.00
Received By mjacobs Date 2008-12-02 Time 16:55 Sent To  
Notes
2008-12-02 16:55:04 
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-10 Cont ID  
Sent By mjacobs Date 2008-10-10 Time 14:37 Rev Time 0.00
Received By mjacobs Date 2008-10-10 Time 14:37 Sent To  
Notes
2008-10-10 14:37:36BUILDING PLAN REVIEW
 PERMIT: 08090562
 ADD: 4847 FRED GLADSTONE DR.
 CONT: PRETI CONSTRUCTION INC.
 TEL: (561)840-9949
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 10-9-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. INDICATE THIS
 INFORMATION ON THE PLANS.
  
 4) SHEET LS1.0 INDICATES THE OCCUPANT LOAD OF THE
 BUILDING PER TABLE 1004.1.2.
  
 5) SHEET A1.1 DOORS #14 AND #16 SHALL MEET THE
 REQUIREMENTS OF FBC 11-4.13.6 AND FIGURE 25. SHOW
 COMPLIANCE. 11-4.2.3 THE SPACE REQUIRED FOR A
 WHEELCHAIR TO MAKE A 180-DEGREE TURN IS A CLEAR SPACE
 OF 60 INCHES DIAMETER. SHOW THE WHEELCHAIR TURNING
 SPACE IN THE AREAS OF THE DOORS MENTIONED ABOVE.
 INDICATE THE WIDTH OF THE CORRIDOR AFTER THE NEW WALLS
 ARE CONSTRUCTED IN THIS AREA.
  
 6) THE FLOOR PLAN ON SHEET A1.1 AND SHEET FP1.02 DO NOT
 CORRESPOND WITH EACH OTHER. THE NEW WALLS CONSTRUCTED
 AROUND DOORS #10 #11 AND #14 ARE NOT SHOWN ON SHEET
 FP1.02. THIS IS CRITICAL FOR THE LAYOUT OF THE NEW FIRE
 SPRINKLER HEADS. THE DOOR SCHEDULE INDICATES THE DOOR
 AS TEMPORARY BUT THE PLANS DO NOT STATE THE WALLS AS
 TEMPORARY WALLS. IF BOTH THE WALLS AND DOORS IN THESE
 AREAS ARE TEMPORARY STRUCTURES BUILT TO CONTROL THE
 DUST FROM TRAVELING INTO OTHER AREAS BEING OCCUPIED
 PLEASE INDICATE THIS INFORMATION ON THE PLANS.
  
 7) SHEET LS1.1 INDICATES DOOR #10 AS AN EGRESS DOOR
 HOWEVER, SHEET A1.1 SHOWS A NEW WALL CLOSING OFF THIS
 DOOR. PLEASE MAKE SURE THE FLOOR PLAN ON THE
 ARCHITECTURAL SHEETS CORRESPOND WITH THE ?MEP AND FS
 SHEETS. CLARIFY.
  
 8) THE OCCUPANT LOAD FOR ROOM #111-#113 IS A TOTAL OF
 61 OCCUPANTS, THEREFORE, TWO EXITS SHALL BE PROVIDED
 FOR THAT ROOM. FBC 1014 AND TABLE 1014.1 AND 1018 AND
 TABLE 108.1 IF ANY EQUIPMENT WILL BE PLACED IN THIS
 ROOM PLEASE SHOW THE LOCATIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-10-11 Cont ID  
Sent By dpalmer Date 2009-10-11 Time 08:18 Rev Time 0.00
Received By dpalmer Date 2009-10-11 Time 08:18 Sent To  
Notes
2009-10-11 08:19:35MINOR REVISIONS ON E1.02,1.03,1.04,
  
 LOW VOLTAGE, FIRE ALARM ARE UNDER SEPARATE PERMITS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-07-28 Cont ID  
Sent By dpalmer Date 2009-07-28 Time 18:19 Rev Time 0.00
Received By dpalmer Date 2009-07-28 Time 18:19 Sent To  
Notes
2009-07-28 18:20:08 
  
 ** REDLINED REVIEW **
  
 1) NOTE: LOW VOLTAGE, FIRE ALARM, OR LIGHTNING
 PROTECTION SYSTEMS SHOWN ON PLANS ARE REQUIRED TO BE
 UNDER SEPARATE PERMITS. TO DATE OF THIS REVIEW NO LOW
 VOLTAGE, FIRE ALARM OR LIGHTNING PROTECTION SYSTEM
 PERMITS HAVE BEEN APPLIED FOR. THESE PLANS MAY BE
 REFERENCED FOR LOW VOLTAGE AND LIGHTNING PROTECTION.
 FIRE ALARM PERMITS ARE UNDER SEPARATE PLANS AND PERMIT.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-06 Cont ID  
Sent By dpalmer Date 2009-02-06 Time 15:17 Rev Time 0.00
Received By dpalmer Date 2009-02-06 Time 15:16 Sent To  
Notes
2009-02-06 15:17:09** REDLINED PLANS
  
 1) NOTE: FP SHEETS SEEM TO INDICATE NEW FIRE PUMP AND
 JOCKEY PUMP HOWEVER ELECTRICAL RISER INDICATES BOTH AS
 EXISTING. CALLED AND LEFT MESSAGE FOR THE ENGINEER TO
 CONFIRM. FP SHEET WAS REDLINED TO STATE THESE ARE NOT
 NEW AT THIS TIME AND ARE NOT INCLUDED IN THE SCOPE OF
 WORK.
  
 2) NOTE: TABLE FOR LPD CALCS SHOULD HAVE READ
 13-415.2.B
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-12-23 Cont ID  
Sent By dpalmer Date 2008-12-23 Time 15:20 Rev Time 0.00
Received By dpalmer Date 2008-12-23 Time 15:20 Sent To  
Notes
2008-12-23 15:21:01** DENIED REVIEW**
  
  
 1) NOTE: PLEASE SEE THAT THE ORIGINAL PERMIT
 APPLICATION WAS NOT BROUGHT BACK IN WHEN PLANS WERE
 RESUBMITTED. IN FACT THE APPLICATION IN PACKAGE IS A
 PHOTO-COPY OF THE ORIGINAL.
 PLEASE BRING BACK THE ORIGINAL SIGNED PERMIT
 APPLICATION WHEN RE-SUBMITTING.
 NO SUB CONTRACTORS ARE SIGNED ON.
  
 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1, .1.1, .1.2,
 .1.3. LIGHTING CONTROLS AS SHOWN DO NOT COMPLY FOR
 AUTOMATED LIGHTING CONTROLS. THIS IS LIGHTING CONTROLS
 IN A BUILDING GREATER THAN 5000 SQ FT. ALL NEW LIGHTING
 CONTROLS BEING INSTALLED SHALL BE AUTOMATED OF SOME
 SORT. A MANUAL SWITCH DOES NOT MEET THE CODE.
 A MANUAL OVER RIDE OF A SYSTEM, IF A SYSTEM IS PROPOSED
 IS PERMITTED HOWEVER THERE IS DOZENS OF WAYS TO COMPLY
 WITH THE MINIMUM PRESCRIPTIVE REQUIREMENTS.
 13-
  
  
 3) NOTE: PLEASE SUBMIT AND SHOW MINIMUM CODE COMPLIANCE
 FOR LIGHTING PERFORMANCE CALCULATIONS AS PART OF THE
 RECORD PLANS. THE SEPARATE SUBMITTED SHEET DOES NOT
 CONTAIN ANY INFORMATION FROM THE ELECTRICAL DESIGNER OF
 RECORD. NO TITLE BLOCKS, NOT SIGNED AND SEALED ETC.
 PLEASE SEE THE ALLOWANCES ON THIS SHEET ALSO NEED TO BE
 ADJUSTED FOR CODE COMPLIANCE. ONE EXAMPLE WOULD BE
 STORAGE ROOM WHICH INDICATES AN ALLOWANCE FROM FBC OF
 1.1. HOWEVER NO STORAGE ROOMS LISTED IN TABLE FBC
 13-415.2.B ALLOWS A 1.1 FOR STORAGE. IN FACT HOSPITAL
 STORAGE AREAS IS ACTUALLY THE HIGHEST WHICH IS .09.
 PLEASE COMPLETE FIXTURE LEGEND FOR ALL FIXTURES.
 EXAMPLE OF ONE IS *G* WHICH IS BLANK.
 PLEASE ADJUST FBC ALLOWANCES, PLEASE PLACE ON PLANS,
 PLEASE COMPLETE TITLE BLOCKS, SIGNED, DATED SEALED ETC.
 13-415.2, 13-415.2.ABC.1.1, .1.2, FS 471.025, FAC
 61G15-23.002.
  
  
 4) NOTE: PLEASE SEE 410.5 AND 410.6 FOR LIGHT FIXTURE
 IN CLOSET AREA #104. AS SHOWN THIS APPEARS TO BE OVER
 SHELVING AREAS WHICH IS A FIRE HAZARD.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-14 Cont ID  
Sent By dpalmer Date 2008-10-14 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2008-10-14 Time 14:39 Sent To  
Notes
2008-10-14 14:39:32 
 ** DENIED REVIEW**
  
  
 1) NOTE: THE SCOPE OF WORK FOR WHAT APPEARS TO BE A
 RESIDENTIAL UNIT HAS CREATED SEVERAL COMMENTS FROM
 MULTIPLE TRADES INCLUDING ZONING. IF THIS IS A SEPARATE
 RESIDENTIAL DWELLING/APARTMENT THE WIRING METHODS
 REQUIRED IN NEC 210.52, 2108 NEED TO BE MET.
 AN EXAMPLE OF THIS WOULD BE 210.52(D)3 FOR CIRCUITING
 OF THE BATH GFI WHICH IS SHOWN ON OTHER THAN THE
 BATHROOM WHICH IS NOT PERMITTED PER SECTION GIVEN.
 ANOTHER WOULD BE THE REQUIRED CIRCUITING FOR ARC FAULT
 PER 210.12. SPACING PER 210.52, SPACING ALONG KITCHEN
 COUNTER SPACE AREAS PER 210.52(C) 1-5 ETC
 AS THE SCOPE OF THIS UNCLEAR AT THIS TIME FOR THIS
 RESIDENTIAL UNIT, WIRING ETC CAN NOT BE CONFIRMED AS
 COMPLIANT. IF RESIDENTIAL THE WIRING AS SHOWN DOES NOT
 MEET THE NEC.
  
 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE FOR NEW
 AREAS WHERE LIGHTING IS BEING INSTALLED. 13-415.2,
 13-415.2.ABC.1.1, .1.2, TABLES 13-415.2.B, 13-415.2.C
  
 3) NOTE: PLEASE INDICATE LIGHTING CONTROL DEVICES PER
 13-415.1.ABC.1.1, .1.2, .1.3 FOR NEW BEING INSTALLED.
  
 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR ADA
 COMPLIANCE PER FBC 11-4.28.1, .2 AND .3.
  
 5) NOTE: THE LIGHTNING PROTECTION SYSTEM AS NOTED SHALL
 BE UNDER SEPARATE PERMIT AS WELL AS LOW VOLTAGE
 SYSTEMS. THE LOW VOLTAGE SYSTEM MAY REMAIN ON PLANS AND
 THESE PLANS MAY BE REFERENCED FOR A TURNAROUND PERMIT
 ONCE MAIN PERMIT IS ISSUED.
 SEPARATE FEES ETC WILL BE APPLIED FOR VALUE OF SCOPE.
  
 6) NOTE: THE PERMIT PACKAGE CONTAINS A RESPONSE LETTER
 FROM THE ENGINEER TO ELECTRICAL COMMENTS AS WELL AS
 RESPONSES TO OTHER TRADES. THIS IS THE FIRST TIME THIS
 IS IN FOR PERMITTING AND IT IS UNCLEAR WHERE THESE
 RESPONSES COME FROM. THE ELECTRICAL NOTES WHICH WERE
 RESPONDED TO WERE NOT FROM THIS OFFICE.
 A CALL WAS PLACED TO THE ELECTRICAL ENGINEER OF RECORD
 TO CLARIFY WHERE THESE NOTES CAME FROM HOWEVER WAS OUT
 OF THE OFFICE AT THE TIME OF THE REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-10-21 Cont ID  
Sent By mawillia Date 2009-10-21 Time 16:44 Rev Time 0.00
Received By mawillia Date 2009-10-21 Time 16:22 Sent To  
Notes
2009-10-21 16:35:40*****REVISION, DATED 9/21/2009, APPROVED*****
  
  
 REVISED PLAN SHEETS A1.1, A2.1, E1.02, E1.04, AND
 FP1.02 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-08-03 Cont ID  
Sent By mawillia Date 2009-08-03 Time 15:29 Rev Time 0.00
Received By mawillia Date 2009-08-03 Time 15:01 Sent To  
Notes
2009-08-03 15:27:14*****REVISION, DATED 6/30/2009, APPROVED*****
  
  
 REVISED PLAN SHEETS A1.1, A2.1, E1.02, AND E1.04 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-05-28 Cont ID  
Sent By mawillia Date 2009-05-28 Time 15:36 Rev Time 0.00
Received By mawillia Date 2009-05-28 Time 15:16 Sent To  
Notes
2009-05-28 15:21:54*****REVISION #2, DATED 4/20/2009, APPROVED*****
  
  
 SINGLE REVISED SHEET PH1.1 STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-12-24 Cont ID  
Sent By mwennerg Date 2008-12-24 Time 10:07 Rev Time 0.00
Received By mwennerg Date 2008-12-24 Time 10:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By mwennerg Date 2008-10-23 Time 10:35 Rev Time 0.00
Received By mwennerg Date 2008-10-23 Time 10:35 Sent To  
Notes
2008-10-23 10:39:39***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 3) DAMPERS TO BE TESTED FOR CLOSURE PER REQUIREMENTS OF
 UL 555 PRIOR TO FINAL INSPECTION.
  
 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 5) ONLY ONE EXIT SHOWN IN AREAS WITH OCCUPANT LOAD OF
 (61) PERSONS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-09-29 Cont ID  
Sent By shill Date 2009-09-29 Time 14:43 Rev Time 0.00
Received By shill Date 2009-09-29 Time 14:43 Sent To  
Notes
2009-09-29 14:48:46C22

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-08-11 Cont ID  
Sent By lmartine Date 2009-08-11 Time 09:15 Rev Time 0.00
Received By lmartine Date 2009-08-11 Time 09:15 Sent To  
Notes
2009-08-11 09:17:13GAVE TO RON
2009-08-11 09:16:00IN MECHANICAL BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 14:31 Rev Time 0.00
Received By shill Date 2009-07-15 Time 14:31 Sent To  
Notes
2009-07-15 14:34:45C34
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 14:35 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 14:35 Sent To  
Notes
2009-04-29 14:35:55TO C15

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-27 Cont ID  
Sent By adarroug Date 2009-01-27 Time 10:26 Rev Time 0.00
Received By adarroug Date 2009-01-27 Time 10:26 Sent To  
Notes
2009-01-27 10:30:07TO "COMM" BD#49

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-24 Cont ID  
Sent By adarroug Date 2008-11-24 Time 15:56 Rev Time 0.00
Received By adarroug Date 2008-11-24 Time 15:56 Sent To  
Notes
2008-11-24 15:59:04TO "COMM" BD#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-23 Cont ID  
Sent By mwennerg Date 2008-10-23 Time 10:42 Rev Time 0.00
Received By mwennerg Date 2008-09-24 Time 08:49 Sent To  
Notes
2008-09-24 08:49:42TO "COMM" BD#11

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2009-10-23 Cont ID  
Sent By rregueir Date 2009-10-23 Time 13:44 Rev Time 0.00
Received By rregueir Date 2009-10-23 Time 13:44 Sent To  
Notes
2009-10-23 13:45:08REVISED M1.02 DELTA 4

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-08-18 Cont ID  
Sent By rregueir Date 2009-08-18 Time 10:59 Rev Time 0.00
Received By rregueir Date 2009-08-18 Time 10:59 Sent To PC
Notes
2009-08-18 10:59:38REVISED M1.02 AND M1.03 DELTA 3

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2009-07-27 Cont ID  
Sent By rregueir Date 2009-07-27 Time 18:28 Rev Time 0.00
Received By rregueir Date 2009-07-27 Time 17:55 Sent To  
Notes
2009-07-27 18:01:36M1.03 DELTA 2 REVISION DENIED
  
 DETAIL #5 SHOWS AN INSTALLATION DETAIL FOR A SLEEVE TO
 BE USED WHERE DUCTS PENETRATE RATED WALL ASSEMBLIES
 WITHOUT FIRE DAMPERS. ALL DUCT PENETRATIONS OF RATED
 WALL ASSEMBLIES WHICH ARE ALLOWED WITHOUT FIRE DAMPERS
 SHALL BE PROTECTED WITH A LISTED THROUGH-PENETRATION
 FIRESTOP SYSTEM IN ACCORDANCE WITH RBC-M 607.1.1 AND
 FBC-B SECTION 712. INDICATE ON PLANS EACH LOCATION
 WHERE A FIRE DAMPER IS INSTALLED AND WHERE A
 THROUGH-PENETRATION FIRESTOP SYSTEM IS TO BE USED IN
 ACCORDANCE WITH FBC-M 607.8.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
 DENIED REVISION PAGES FILED IN SMALL PLAN CABINET UNDER
 "P"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-07-27 Cont ID  
Sent By rregueir Date 2009-07-27 Time 17:54 Rev Time 0.00
Received By rregueir Date 2009-07-27 Time 17:54 Sent To  
Notes
2009-07-27 17:54:53REVISED M1.01 AND M1.02, DELTA 2
 PAGE M1.04 NO CHANGES - RESTAMPED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-12-13 Cont ID  
Sent By rregueir Date 2008-12-13 Time 15:33 Rev Time 0.00
Received By rregueir Date 2008-12-13 Time 15:04 Sent To  
Notes
2008-12-13 15:33:42REVIEW #: 2ND
 ACTION: PASS W/ PROVISO
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 COMMENTS 1,3,4 AND NOTE HAVE BEEN ADEQUATELY ADDRESSED.
 PERMIT MAY BE ISSUED WITH THE FOLLOWING PROVISO:
  
 *******************PROVISO*********************
 EXHAUST FAN EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST WIND PRESSURES IN ACCORDANCE WITH
 FBCM 301.13 AND FBCB 1609.
 PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE OR A
 RATIONAL ANALYSIS FROM A FLORIDA LICENSED STRUCTURAL
 ENGINEER CERTIFYING THE PROPOSED FAN IS DESIGNED FOR
 WIND RESISTANCE BASED ON THE LOCATION INSTALLED
 (ELEVATION, EXPOSURE CATEGORY AND WIND IMPORTANCE
 FACTOR) AS DETERMINED BY FBCB SECTION 1609.
  
 NOTE: DESIGNER'S WRITTEN RESPONSE INDICATES NO FAN
 WHICH IS DESIGNED FOR WIND RESISTANCE COULD BE FOUND.
 THERE IS AT LEAST ONE AND POSSIBLY MORE EXHAUST FAN
 MANUFACTURERS WITH A LINE OF FANS DESIGNED FOR WIND
 RESISTANCE. THIS OFFICE IS PROHIBITED BY POLICY FROM
 RECOMMENDING SPECIFIC BRANDS OR MANUFACTURERS. A SEARCH
 OF MIAMI-DADE'S NOA DATABASE MAY PROVIDE ADDITIONAL
 GUIDANCE IN YOUR SEARCH FOR A CODE COMPLAINT OUTDOOR
 APPLIANCE. AN NOA IS NOT SPECIFICALLY REQUIRED FOR
 OUTDOOR APPLIANCES. HOWEVER, THE DATA PROVIDED IN A
 CURRENT NOA MAY BE USED AND WOULD BE ACCEPTED BY THIS
 AHJ AS A DEMONSTRATION OF CODE COMPLIANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-18 Cont ID  
Sent By rregueir Date 2008-10-18 Time 15:52 Rev Time 0.00
Received By rregueir Date 2008-10-18 Time 12:34 Sent To  
Notes
2008-10-18 15:52:42REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1.03 SHOWS NEW ROOF-MOUNTED EXHAUST FAN.
 PROVIDE STRUCTURAL DETAIL SHOWING HOW ROOF OPENING
 REINFORCEMENT IS TO BE INSTALLED AND HOW ROOF CURB IS
 TO BE ATTACHED TO STRUCTURE FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBCM 301.13.
  
 2. PAGE M1.03 SHOWS NEW ROOF-MOUNTED EXHAUST FAN. NO
 INFORMATION WAS PROVIDED SHOWING THE EXHAUST FAN IS
 DESIGNED TO RESIST WIND PRESSURES IN ACCORDANCE WITH
 FBCM 301.13. PROVIDE MANUFACTURER?S DATA SHOWING WIND
 RESISTANCE INFORMATION. THIS INFORMATION SHOULD INCLUDE
 INFORMATION ON ATTACHMENT OF APPLIANCE (EXHAUST FAN) TO
 ROOF CURB.
  
 3. WHAT IS THE PITCH OF THE ROOF WHERE NEW EF-7 IS TO
 BE INSTALLED? WHERE APPLIANCES ARE INSTALLED ON A ROOF
 HAVING A SLOPE OF THREE UNITS VERTICAL IN 12 UNITS
 HORIZONTAL OR GREATER AND HAVING AN EDGE MORE THAN 30
 INCHES ABOVE GRADE AT SUCH EDGE, A LEVEL PLATFORM SHALL
 BE PROVIDED ON EACH SIDE OF THE APPLIANCE TO WHICH
 ACCESS IS REQUIRED BY THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS FOR SERVICE, REPAIR OR MAINTENANCE IN
 ACCORDANCE WITH FBCM 306.6. THE PLATFORM SHALL NOT BE
 LESS THAN 30 INCHES IN ANY DIMENSION AND SHALL BE
 PROVIDED WITH GUARDS IN ACCORDANCE WITH SECTION 304.10.
  
 4. WHAT IS THE HEIGHT OF THE ROOF WHERE NEW EF-7 IS
 LOCATED? WHAT IS THE PITCH OF THE ROOF WALKING SURFACE
 WHICH WILL BE USED TO ACCESS THIS FAN? WHERE APPLIANCES
 REQUIRING ACCESS ARE INSTALLED ON ROOFS AT A HEIGHT
 EXCEEDING 16 FEET, SUCH ACCESS SHALL BE PROVIDED BY A
 PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH
 SHALL BE FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4
 UNITS VERTICAL IN 12 UNITS HORIZONTAL IN ACCORDANCE
 WITH FBCM 306.5.
  
 NOTE: NEW RANGE PROPOSED FOR OCCUPATIONAL THERAPY AREA
 IS SHOWN ON ELECTRICAL PLANS TO BE FED BY 120V FOR
 DEMONSTRATION PURPOSES ONLY AND NO COOKING. THIS RANGE
 SHALL REMAIN INOPERABLE FOR COOKING AT ALL TIMES. IF AT
 ANY THIME THIS RANGE BECOMES OPERATIONAL FOR COOKING, A
 TYPE I HOOD WITH FIRE SUPPRESSION SYSTEM WILL BE
 REQUIRED IN ACCORDANCE WITH FBCM 507.2.1 AND 509.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2009-01-07 Cont ID  
Sent By kstevens Date 2009-01-07 Time 15:09 Rev Time 0.00
Received By kstevens Date 2009-01-07 Time 15:09 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2008-09-26 Cont ID  
Sent By kstevens Date 2008-09-26 Time 15:06 Rev Time 0.00
Received By kstevens Date 2008-09-26 Time 15:06 Sent To  
Notes
2009-01-07 15:08:46 
  
 SEPARATE MED-GAS PERMIT IS REQUIRED. THE CERTIFICATIONS
 FOR THE QUALIFER, THE INSTALLER AND THE BRAZER SHALL BE
 SUBMITTED WITH THE MED-GAS PERMIT APPLICATION. FAC
 61G4-15.031.

Review Stop P PLUMBING
Rev No 4 Status N Date 2009-10-05 Cont ID  
Sent By kstevens Date 2009-10-05 Time 14:38 Rev Time 0.00
Received By kstevens Date 2009-10-05 Time 14:38 Sent To  
Notes
2009-10-05 14:38:26NO PLUMBING REVISIONS FOUND/SUBMITTED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-07-29 Cont ID  
Sent By kstevens Date 2009-07-29 Time 14:52 Rev Time 0.00
Received By kstevens Date 2009-07-29 Time 14:52 Sent To  
Notes
2009-07-29 14:53:22REVISION OK -- SHT P-02

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-01-07 Cont ID  
Sent By kstevens Date 2009-01-07 Time 14:32 Rev Time 0.00
Received By kstevens Date 2009-01-07 Time 14:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By kstevens Date 2008-09-26 Time 08:43 Rev Time 0.00
Received By kstevens Date 2008-09-25 Time 08:45 Sent To  
Notes
2008-09-25 16:01:23DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 NAPA 99C-99
 FLORIDA ADMINISTRATIVE CODE
  
 1. SHTS LS1.0 & LS1.1 CODE REFERENCE SHALL INCLUDE THE
 2007 REVISIONS.
  
 2. SHTS LS1.0 & LS1.1 OCCUPANCY STATES "SEE PLAN"
 PLEASE INDICATE WHERE ON THE PLANS THE OCCUPANCY OF THE
 STRUCTURE CAN BE LOCATED.
  
 3. SHT A3.1 DETAIL 15 SHOWS THE FLUSH CONTROL FOR THE
 W/C TO THE WALL SIDE OF THE TANK. PER SECTION 11-4.16.5
 THE FLUSH CONTROL SHALL BE ON THE WIDE SIDE. PLEASE
 SHOW THE FLUSH CONTROL WHERE REQUIRED.
  
 4. SHT A3.1 DETAIL 15 CLEARANCE FOR THE LAV SHALL BE AT
 LEAST 29 INCHES PER SECTION 11-4.19.2. IT IS SHOWN AS
 27 INCHES.
  
 5. SHT A3.1 DETAIL 15 TUB CONTROLS SHALL BE LOCATED PER
 SECTION 11-4.20.5 & FIGURE 34.
  
 6. SHT A3.1 DETAIL 21 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT APPROVED IN THE CLEAR FLOOR
 SPACE.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
  
 7. SHT P1.02 PER SECTION 406.3, THE AUTOMATIC CLOTHES
 WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH DRAIN A
 MINIMUM OF 3 INCHES. 2 INCHES IS SHOWN.
  
 8. A SEPARATE MED-GAS PERMIT IS REQUIRED.
 CERTIFICATIONS FOR THE QUALIFIER, THE INSTALLERS AND
 THE BRAZERS SHALL BE SUBMITTED WITH THE MED GAS PERMIT
 APPLICATION. FAC 61G4-15.031.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2008-11-25 Cont ID  
Sent By eschneid Date 2008-11-25 Time 16:40 Rev Time 0.00
Received By eschneid Date 2008-11-25 Time 16:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-29 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By eschneid Date 2008-09-29 Time 16:08 Sent To  
Notes
2008-09-29 16:11:57FAILED
  
 THE PLANS CALL OUT THAT THE REMODEL IS FOR A BEDROOM
 W/KITCHEN AND BATH. PLEASE CLARIFY THE USE OF THIS
 SPACE. IS THIS AN ADDITIONAL LIVING UNIT? IF THIS IS TO
 BE A RESIDENTIAL UNIT, WHETHER ACLF OR EMPLOYEE, THEN
 AN AMENDMENT TO THE MORSE LIFE CSPD IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved