Plan Review Details - Permit 08090558
Plan Review Stops For Permit 08090558
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-10-14 Cont ID  
Sent By mperson Date 2008-10-14 Time 14:24 Rev Time 0.00
Received By mperson Date 2008-10-14 Time 14:24 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-10-06 Cont ID  
Sent By mperson Date 2008-10-06 Time 14:10 Rev Time 0.00
Received By mperson Date 2008-10-06 Time 14:10 Sent To  
Notes
2008-10-06 14:11:39GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE AND THE CITY OF
 WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED GAS ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTION OF PROPOSED
 PIPE. PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT
 SECTIONS WITH NO CORRESPONDING LENGTHS AND COMPLY WITH
 THE REQUIRED INFORMATION ON THE RESUBMITTAL.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL
 GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED GAS ISOMETRIC IS ONLY INDICATING
 3/4" PE UNDERGROUND PIPING FOR THE PROPOSED GENERATOR.
 WHAT IS THE ABOVEGROUND PIPING MATERIAIL AND SIZE FOR
 THE PROPOSED GENERATOR AND AT THE METER LOCATION?
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 *NOTE: THE BTU LOAD FOR THE PROPOSED GENERATOR IS BEING
 INDICATED AS BEING 698,000, HOWEVER THE GENERATOR
 MANUFACTURER'S SPECIFICATION SHEETS ARE INDICATING THE
 BTU'S FOR THE PROPOSED GENERATOR AS BEING 485,000.
 PLEASE CORRELATE THE PLANS WITH THE GENERATOR
 SUBMITTAL. ALSO CLEARLY INDICATE THE TOTAL BTU"S FOR
 THE SYSTEM ON THE RESUBMITTED ISOMETRIC. PLANS ARE
 INDICATING SEE PERMIT #08040470, HOWEVER THAT GAS
 PERMIT IS CLOSED AND THAT INFORMATION IS NO LONGER
 AVAILABLE.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: CLEARLY INDICTAE THE LONGEST LENGTH OF THE
 SYSTEM ON THE RESUBMITTED GAS ISOMETRIC. PLEASE KNOW
 THAT THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION
 *106.3.4.3.
 *NOTE: THE PRINTED AND ORIGINAL SIGNATURE OF THE PERSON
 TAKING RESPONSIBILITY FOR THE GAS ISOMETRIC IS REQUIRED
 ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-09-30 Cont ID  
Sent By mcruz Date 2008-09-30 Time 11:22 Rev Time 0.00
Received By mcruz Date 2008-09-30 Time 11:22 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved