Plan Review Details - Permit 08090459
Plan Review Stops For Permit 08090459
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-12-31 Cont ID  
Sent By jwitmer Date 2008-12-31 Time 10:01 Rev Time 0.77
Received By jwitmer Date 2008-12-31 Time 10:01 Sent To PC
Notes
2008-12-31 10:05:28REVISION SHEET A-2, REVISION # 3, DATED 12/15/08 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-01 Cont ID  
Sent By jwitmer Date 2008-12-01 Time 14:03 Rev Time 0.77
Received By jwitmer Date 2008-12-01 Time 14:03 Sent To PC
Notes
2008-12-01 14:04:42RED LINED 2007 SUPPLEMENTS TO THE 2004 FBC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-20 Cont ID  
Sent By jwitmer Date 2008-11-20 Time 15:12 Rev Time 0.55
Received By jwitmer Date 2008-11-20 Time 15:12 Sent To  
Notes
2008-11-20 15:13:00RED LINED 2007 SUPPLEMENTS TO THE 2004 FBC

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-10-07 Cont ID  
Sent By jwitmer Date 2008-10-07 Time 15:56 Rev Time 1.33
Received By jwitmer Date 2008-10-07 Time 15:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-12-01 Cont ID  
Sent By dpalmer Date 2008-12-01 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2008-12-01 Time 08:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-06 Cont ID  
Sent By dpalmer Date 2008-11-06 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2008-11-06 Time 10:36 Sent To  
Notes
2008-11-06 10:39:58 
  
  
 ** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO LIGHTING PERFORMANCE CALCULATIONS. PLEASE
 SEE SECTIONS 13-415.2.ABC.1.1,.1.2. THE REQUIRED
 LIGHTING VA PER FIXTURE SHALL BE BASE DON THE MAXIMUM
 VA A FIXTURE IS RATED FOR NOT THE BULB WATTAGE. AN
 EXAMPLE IS THE FACT THE *C* FIXTURE AS LISTED IN
 ACTUALLY A FIXTURE WHICH IS RATED FOR TWICE THE WATTAGE
 THAN FIGURED IN THE CALCULATIONS SUBMITTED. MUST USE
 THE MAXIMUM VA OF FIXTURE OR BALLAST IF HID ETC. ( IF
 HID, FLUORESCENT ETC CHECK EFFICIENCY RATINGS OF
 BALLAST THIS MAY HELP).
  
 2) NOTE: PLEASE PROVIDE THE SELECTIVE COORDINATION OF
 NEW EQUIPMENT AND BREAKERS. 240.12,700.27, 701.18.
 PLEASE SEE 517.17 FOR REQUIRED GFI PROTECTION OF
 SYSTEMS.
 ** RESPONSE MENTIONS THIS ELECTRICAL IS ON THE NORMAL
 POWER. PLEASE INDICATE THIS INFORMATION ON THE SIGNED
 AND SEALED RECORD PLANS. THE RESPONSE LETTER HAS NO
 LEGEL RECORD PART OF THE PLANS.
  
 3) NOTE: PLEASE PROVIDE LOADS ON EXISTING SERVICE/MAIN
 IN WHICH THE NEW PANEL IS BEING FED FROM.
 NEC 220
 RESPONSE WRITES ABOUT LOADS REMOVED ETC HOWEVER THIS
 INFORMATION NEEDS TO BE ON THE PLANS.
 FBC 106.1.1 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE INDICATE THE LOCATIONS OF NEW
 HORNS/STROBES OR EXISTING WHICH MEET NFPA-72 AS WELL AS
 FBC 11-4.28.1, .2 AND .3 FOR ADA COMPLIANCE.
 THE PLANS NEED TO SHOWS THE LEVELS FOR MINIMUM
 COMPLIANCE. PLEASE KNOW THE FBC CAN BE MORE RESTRICTIVE
 IN SOME ASPECTS.
  
 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-07 Cont ID  
Sent By dpalmer Date 2008-10-07 Time 11:41 Rev Time 0.00
Received By dpalmer Date 2008-10-07 Time 11:41 Sent To  
Notes
2008-10-07 11:41:13 
 ** DENIED **
  
 1) NOTE: PLANS INDICATE SOME OF NOTES FOR A LIGHTING
 CONTROL PANEL HOWEVER SPACE CONTROLS PER FBC
 13-415.1.ABC.1.1 ARE NOT MET BASED ON THE SYMBOL LEGEND
 ONLY CALLING FOR A STANDARD SINGLE POLE SWITCH DEVICE.
  
  
 2) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2,13-415.2.ABC.1.1,.1.2. PLEASE
 CALL TO GO OVER HOW PRESCRIPTIVE REQUIREMENTS CAN BE
 MET.
  
 3) NOTE: PLEASE PROVIDE THE SELECTIVE COORDINATION OF
 NEW EQUIPMENT AND BREAKERS. 240.12,700.27, 701.18.
 PLEASE SEE 517.17 FOR REQUIRED GFI PROTECTION OF
 SYSTEMS.
  
 4) NOTE: PLEASE PROVIDE LOADS ON EXISTING SERVICE/MAIN
 IN WHICH THE NEW PANEL IS BEING FED FROM.
 NEC 220
 FBC 106.1.1 FOR ADDITIONAL INFORMATION.
  
 5) NOTE: PLEASE INDICATE THE LOCATIONS OF NEW
 HORNS/STROBES OR EXISTING WHICH MEET NFPA-72 AS WELL AS
 FBC 11-4.28.1, .2 AND .3 FOR ADA COMPLIANCE.
 THE PLANS NEED TO SHOWS THE LEVELS FOR MINIMUM
 COMPLIANCE. PLEASE KNOW THE FBC CAN BE MORE RESTRICTIVE
 IN SOME ASPECTS.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-21 Cont ID  
Sent By mwennerg Date 2008-11-21 Time 11:09 Rev Time 0.00
Received By mwennerg Date 2008-11-21 Time 11:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-22 Cont ID  
Sent By mawillia Date 2008-10-22 Time 18:00 Rev Time 0.00
Received By mawillia Date 2008-10-22 Time 17:44 Sent To  
Notes
2008-10-22 17:59:28*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE FIRE ALARM
 DEVICES (IF ANY) TO BE REMODELED.
  
 3. SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-17 Cont ID  
Sent By adarroug Date 2008-12-17 Time 11:19 Rev Time 0.00
Received By adarroug Date 2008-12-17 Time 11:19 Sent To B
Notes
2008-12-17 11:19:46TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-25 Cont ID  
Sent By adarroug Date 2008-11-25 Time 09:43 Rev Time 0.00
Received By adarroug Date 2008-11-25 Time 09:43 Sent To  
Notes
2008-11-25 09:45:49TO "COMM" BD#47

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-11-03 Time 09:06 Rev Time 0.00
Received By adarroug Date 2008-11-03 Time 09:06 Sent To  
Notes
2008-11-03 09:09:37TO "COMM" BD#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-22 Cont ID  
Sent By mawillia Date 2008-10-22 Time 17:45 Rev Time 0.00
Received By mawillia Date 2008-09-19 Time 13:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-10-01 Cont ID  
Sent By tgordon Date 2008-10-01 Time 13:43 Rev Time 1.15
Received By tgordon Date 2008-10-01 Time 13:43 Sent To  
Notes
***NONE***