Plan Review Details - Permit 08090447
Plan Review Stops For Permit 08090447
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-10 Cont ID  
Sent By rmcdouga Date 2008-10-10 Time 14:31 Rev Time 0.00
Received By rmcdouga Date 2008-10-10 Time 14:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-09-29 Cont ID  
Sent By rmcdouga Date 2008-09-29 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2008-09-29 Time 11:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-07 Cont ID  
Sent By btrobaug Date 2008-10-07 Time 08:37 Rev Time 0.00
Received By btrobaug Date 2008-10-07 Time 08:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By btrobaug Date 2008-09-26 Time 07:30 Rev Time 0.00
Received By btrobaug Date 2008-09-25 Time 16:36 Sent To P
Notes
2008-09-25 16:40:50 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE DESCRIPTION ON THE APPLICATION INDICATES
 BATHROOM WORK. THE PLANS SUBMITTED THAT ARE LABLED
 "ELECTRICAL" SHOW MOST OF THE WIRING IN THE RESIDENCE.
 INDICATE WHAT IS NEW FROM EXISTING
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-06 Cont ID  
Sent By shill Date 2008-10-06 Time 16:47 Rev Time 0.00
Received By shill Date 2008-10-06 Time 16:47 Sent To E
Notes
2008-10-06 16:48:15TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-29 Cont ID  
Sent By rmcdouga Date 2008-09-29 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2008-09-19 Time 09:43 Sent To  
Notes
2008-09-19 09:43:26TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-09-22 Cont ID  
Sent By tgordon Date 2008-09-22 Time 11:33 Rev Time 0.20
Received By tgordon Date 2008-09-22 Time 11:33 Sent To E
Notes
2008-09-22 11:36:20NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME. (REPLACING EXISTING BATHROOM EXHAUST FAN).

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-10 Cont ID  
Sent By mperson Date 2008-10-10 Time 09:30 Rev Time 0.30
Received By mperson Date 2008-10-10 Time 09:30 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-29 Cont ID  
Sent By mperson Date 2008-09-29 Time 08:47 Rev Time 0.45
Received By mperson Date 2008-09-29 Time 08:47 Sent To B
Notes
2008-09-29 09:18:16PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLUMBING SHEET: CLEARLY INDICATE IF THE NEW DROP IN
 TUB IS GOING TO BE A WHIRLPOOL BATHTUB (JACUZZI) AND IF
 IT IS CLEARLY INDICATE THAT ACCESS SHALL BE PROVIDED TO
 THE PUMP. PER FBC-2004 PLUMBING SECTION 421.2
 INSTALLATION.
  
 2. PLUMBING SHEET: CLEARLY INDICATE THAT THE NEW SHOWER
 VALVE SHALL BE A BALANCED PRESSURE, THERMOSTATIC OR
 COMBINATION BALANCED-PRESSURS/THERMOSTATIC VALVES THAT
 CONFORM TO THE REQUIREMENTS OF ASSE 1016. THE SHOWER
 VALVE SHALL BE EQUIPPEDWITH A MEANS TO LIMIT THE
 MAXIMUM SETTING OF THE VALVE TO 120 DEGREES (F), WHICH
 SHALL BE FIELD ADJUSTED IN ACCORDANCE TO MANUFACTURER'S
 INSTRUCTIONS. PER FBC-2004 PLUMBING SECTION 424.3
 SHOWER VALVES.
  
 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 (W.P.B. AS AMENDED) SECTION *106.3.4.3.
 *NOTE: CLEARLY PRINT THE NAME OF THE PERSON WHOSE
 SIGNATURE APPREARS ON THE PLAN SHEETS THAT IS TAKING
 RESPONSIBILITY FOR THE PLAN SHEETS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]