Plan Review Details - Permit 08090442
Plan Review Stops For Permit 08090442
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-31 Cont ID  
Sent By rmcdouga Date 2008-10-31 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2008-10-31 Time 13:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-02 Cont ID  
Sent By rmcdouga Date 2008-10-01 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2008-09-30 Time 16:38 Sent To  
Notes
2008-10-02 07:10:412004 FBC W/2007 REVISIONS
 NSFD
  
 DENIED BY BUILDING
  
 1) SHOW COMPLIANCE WITH R302.1 AND R302.2. R302.1
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL. R302.2 OPENINGS SHALL
 NOT BE PERMITTED IN THE EXTERIOR WALL OF A DWELLING OR
 ACCESSORY BUILDING THAT IS SEPARATED FROM AN ADJACENT
 BUILDING BY A DISTANCE OF LESS THAN 6 FEET (1828 MM).
 THIS DISTANCE SHALL BE MEASURED PERPENDICULAR TO THE
 LINE USED TO DETERMINE THE SEPARATION DISTANCE THE
 STRUCTURE IS LESS THAN 6' FROM THE PROPERTY LINE IN ONE
 SIDE. SPECIFY THE DISTANCE TO STRUCTURES ON THE
 ADJACENT PROPERTY AT THIS LOCATION.
  
 2) SPECIFY THE MINIMUM SIZE OF THE ATTIC ACCESS
 OPENINGS ON THE PLANS. R807.1 ATTIC ACCESS.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS
 THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND
 SHALL BE LOCATED IN A HALLWAY OR OTHER READILY
 ACCESSIBLE LOCATION. A 30-INCH (762 MM) MINIMUM
 UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT SOME POINT ABOVE THE ACCESS OPENING. SEE
 SECTION M1305.1.3 FOR ACCESS REQUIREMENTS WHERE
 MECHANICAL EQUIPMENT IS LOCATED IN ATTICS.
  
 3) ON SHEET A2.3 THE WRONG CODE AND SECTION ARE
 SPECIFIED FOR THE ROOF VENTILATION REQUIREMENTS. THE
 CODE IS 2004 FBC AND THE SECTION IS R806.2 FROM THE FBC
 RESIDENTIAL. PLEASE CORRECT.
  
 4) SPECIFY THE HEIGHT OF THE GUARDS ON THE STAIR
 DETAILS. R312.1 GUARDS REQUIRED. PORCHES, BALCONIES OR
 RAISED FLOOR SURFACES LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR OR GRADE BELOW SHALL HAVE GUARDS
 NOT LESS THAN 36 INCHES (914 MM) IN HEIGHT. OPEN SIDES
 OF STAIRS WITH A TOTAL RISE OF MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR OR GRADE BELOW SHALL HAVE GUARDS
 NOT LESS THAN 34 INCHES (864 MM) IN HEIGHT MEASURED
 VERTICALLY FROM THE NOSING OF THE TREADS.
  
 5) SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING
 REQUIRED. WHEN THERE IS USABLE SPACE BOTH ABOVE AND
 BELOW THE CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY,
 DRAFTSTOPS SHALL BE INSTALLED SO THAT THE AREA OF THE
 CONCEALED SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9
 M 2 ). DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE
 INTO APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS
 ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING
 MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN
 FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING
 CIRCUMSTANCES:
 1. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING.
 2. FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB
 OR PERFORATED MEMBERS.
 SPECIFY THE LOCATION AND MATERIAL (502.1.2.1) THAT WILL
 BE USED ON THE PLANS.
  
 6) ON SHEET S1.1, THE DETAIL MARKERS MISTAKENLY REFER
 TO SHEET S2.2, HOWEVER THE DETAILS ARE LOCATED ON SHEET
 S2.4. PLEASE CORRECT.
  
 7) THE WINDOW AND DOOR BUCK DETAILS ON SHEET S2.4
 CONFLICT WITH THOSE ON SHEET A6.2 FOR SPACING AND EMBED
 REQUIREMENTS. PLEASE COORDINATE.
  
 8) ON SHEET S2.1 THE NUMBERING OF THE FOUNDATION
 DETAILS IS INCORRECT. THE FOOTING SCHEDULE SPECIFIES
 DETAIL 3 FOR THE ISOLATED PADS AND DETAIL 4 IS THE
 CORRECT ONE. PLEASE CORRECT.
  
 9) SHOW COMPLIANCE WITH R309.2 AT GARAGE AND STORAGE
 LOFT. R309.2 SEPARATION REQUIRED. THE GARAGE SHALL BE
 SEPARATED FROM THE RESIDENCE AND ITS ATTIC AREA BY NOT
 LESS THAN 1/2 -INCH (12.7 MM) GYPSUM BOARD APPLIED TO
 THE GARAGE SIDE. GARAGES BENEATH HABITABLE ROOMS SHALL
 BE SEPARATED FROM ALL HABITABLE ROOMS ABOVE BY NOT LESS
 THAN 5 / 8 -INCH (15.9 MM) TYPE X GYPSUM BOARD OR
 EQUIVALENT. WHERE THE SEPARATION IS A FLOOR-CEILING
 ASSEMBLY, THE STRUCTURE SUPPORTING THE SEPARATION SHALL
 ALSO BE PROTECTED BY NOT LESS THAN 1/2 -INCH (12.7 MM)
 GYPSUM BOARD OR EQUIVALENT.
  
 10) ON SHEET S1.3, THE ROOF FRAMING PLAN HAS AN ID TAG
 IN ONE CORNER WITH AN "X", THIS SHOULD BE AN "A".
 PLEASE CORRECT.
  
 11) IN THE ANCHOR SCHEDULE ON S1.3, THE H7Z SIMPSON
 CONNECTOR IS SPECIFIED WITH 2-8D NAILS AT THE TRUSS AND
 THE SIMPSON CATALOG REQUIRES 4. PLEASE CORRECT.
  
 12) ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH
 SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL
 BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT
 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS
 SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130
 MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH
 FIGURE R803.2.3.1. PLEASE REVISE SHEATHING FASTENING
 SCHEDULE ON S2.4
  
 13) THE SURVEY THAT WAS SUBMITTED SHOWS A ONE STORY
 STRUCTURE, WHICH DOES NOT AGREE WITH THE PLANS. PLEASE
 CORRECT.
  
 14) ON SHEET A6.1 ALL OF THE WINDOWS ARE SPECIFIED ON
 THE PLANS WITH DESIGN PRESSURES OF +70 AND -90 PSF.
 THIS DOES NOT CONCUR WITH THE PRODUCT APPROVALS. THE
 DESIGN PRESSURES FOR THE 5/16" LAMI SINGLE HUNG WINDOWS
 IN THE NOA DEPEND ON GLASS TYPES USED. SEE TABLES 1,2
 AND 3 OF THE NOA. THE FIXED GLASS DESIGN PRESSURES ARE
 BASED ON AREA. SEE NOA TABLES.
  
 15) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE 1
 X HEAVY MULLIONS DO NOT APPEAR TO WORK FOR DOORS E107
 AND E108, THE TWO 6' X 8' DOORS WITH THE 3' X6'
 TRANSOMS AT THE FAMILY ROOM. PLEASE PROVIDE AN
 ELEVATION AT THIS LOCATION AND SPECIFY HOW THEY WILL BE
 INSTALLED. FBC R301.2.1
  
 NOTE: THE ENERGY CALCULATIONS HAVE THE WRONG
 JURISDICTION SPECIFIED. THIS HAS BEEN CORRECTED.
  
 IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER WITH THE RESUBMITTAL THAT INDICATES HOW
 THE ABOVE ITEMS HAVE BEEN ADDRESSED. THANK YOU.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-23 Cont ID  
Sent By btrobaug Date 2008-10-23 Time 13:47 Rev Time 0.00
Received By btrobaug Date 2008-10-23 Time 13:20 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-29 Cont ID  
Sent By btrobaug Date 2008-09-29 Time 09:29 Rev Time 0.00
Received By btrobaug Date 2008-09-26 Time 13:40 Sent To P
Notes
2008-09-26 16:27:02 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. FOR RECORD RETENTION PER
 106.5 FBC, AND CLARITY IN THE FIELD WHEN WORKING FROM
 THIS DOCUMENT, PLEASE INDICATE THE CODE CYCLES UNDER
 WHICH THIS PLAN WAS DESIGNED. ***SEE NOTE #1 SHEET
 E2.1.
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). CIRCUITS 1,4,8 AND 10 PANEL
 "B" AND CIRCUITS 9 AND 10 IN PANEL "A" HAVE THESE
 CIRCUITS ON 15 AMP OCP AND #14 CONDUCTORS.
  
 3} THE DINING ROOM CIRCUIT #6 IN PANEL "A" IS REQUIRED
 TO BE ON A SMALL APPLIANCE CIRCUIT PER 210.52(B)(1).
  
 4} THE CIRCUIT BREAKER, OCP, FOR CIRCUIT #24 GARAGE
 DOOR OPENER, PANEL "A" IS INCORRECTLY LABELED 10 AMP.
 SEE 240.6(A) FOR STANDARD RATINGS.
  
 NOTE: IN THE CALCULATION SUB TOTALS THE DIVIDER IS
 SHOWN AS 24 VOLTS, BUT CORRECTLY CALCULATED USING 240
 VOLTS.
  
 5} 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.
 NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE.***
 REVISE SHEET E1.2 FOR COMPLIANCE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2008-11-24 Cont ID  
Sent By lmartine Date 2008-11-24 Time 09:36 Rev Time 0.00
Received By lmartine Date 2008-11-24 Time 09:36 Sent To  
Notes
2008-11-24 09:41:29COMPLIANCE WITH ALL COMMENTS FROM PREVIOUS REVIEW UNDER
 SEPARATE PERMIT WILL BE REQUIRED. LM

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-10-27 Cont ID  
Sent By mperson Date 2008-10-27 Time 10:39 Rev Time 0.45
Received By mperson Date 2008-10-27 Time 10:39 Sent To B
Notes
2008-10-27 10:47:41GAS PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS. (RESUBMITTED GAS PLANS LOCATED IN THE
 SUPPLEMENTAL INFORMATION BOOK)
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 OF PIPE WITH NO CORRESPONDING LENGTHS.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC
 STILL HAS CUT SECTIONS OF PIPE WITH NO CORRESPONDING
 LENGTHS. PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT
 SECTION OF PIPE WITH NO CORRESPONDING LENGTHS AND
 COMPLY ON THE NEXT RESUBMITTAL.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE ANY OF
 THE ABOVEGROUND PIPING MATERIAL AS WELL AS SOME CUT
 SECTIONS OF UNDERGROUND PIPING. THE ISOMETRIC ALSO DOES
 NOT INDICATE PIPE SIZES TO ALL CUT SECTIONS OF PIPE.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC
 ONLY INDICATION OF ABOVE GROUND PIPING MATERIAL IS ONE
 CUT SECTION OF 3/4" GALV. PIPE TO ONE TANKLESS WATER
 HEATER. WHAT IS THE PIPING MATERIAL TO THE OTHER ABOVE
 GROUND CUT SECTIONS OF PIPE? THE RESUBMITTED GAS
 ISOMETRIC ALSO STILL DOES NOT INDICATE THE PIPING
 MATERIAL ABOVE/UNDERGROUND OR PIPE SIZES TO THE TWO GAS
 LAMPS ON THE OUTLET SIDE OF THE MP REGULATORS. THE
 UNDERGROUND PIPING MATERIAL TO THE TANKLESS WATER
 HEATERS IS NOT INDICATED.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THE ISOMETRIC INDICATES 97' D.L. (LONGEST
 LENGTH), HOWEVER NOT ALL CUT SECTIONS OF GAS PIPE HAVE
 CORRESPONDING LENGTHS. PLEASE REFERENCE COMMENT #1 AND
 COMPLY.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC
 NOW INDICATES 108' D.L. (LONGEST LENGTH) AND STILL NOT
 ALL CUT SECTIONS OF GAS PIPE HAVE CORRESPONDING
 LENGTHS. AGAIN PLEASE REFERENCE COMMENT #1 AND COMPLY.
 UNTIL COMMENT #1 IS FULLY ADDRESSED AND THIS COMMENT IS
 CORRELATED WITH COMMENT #1, THE COMMENT SHALL REMAIN.
  
 4. "OK" COMMENT WAS ADDRESSED>
  
 5. CLEARLY INDICATE THE LOCATION OF THE MP REGULATORS
 (2 PSI TO 0.5 PSI REGULATORS) ON THE RESUBMITTED
 ISOMETRIC OR PROVIDE A LEGEND OF HOW THEY APPEAR ON THE
 PLANS. ALSO PROVIDE A DETAIL OF THE GAS LAMP VALVE BOX
 CLEARLY INDICATING THE LOCATION OF THE SHUT OFF VALVE
 AND MP REGULATOR. PLEASE CLARIFY THE LOCATION OF THE
 GAS LAMP VALVE BOXES. IT APPEARS TO BE LOCATED AT
 FINNISH GRADE LEVEL. PLEASE CLARIFY HOW THE MP
 REGULATORS WILL WORK IF VALVE BOX FILLS WITH WATER
 DURING A STORM. PER FBC-2004 FUEL GAS CODE SECTION
 401.1 SCOPE.
  
 **RESPONSE NOTED, AND COMMENT WAS PARTIALLY ADDRESSED.
 THE RESUBMITTED GAS ISOMETRIC STILL DOES NOT CLEARLY
 INDICATE THE REQUIRED MP REGULATORS (2 PSI TO 0.5 PSI
 REGULATORS) ON THE PLANS OR PROVIDE A LEGEND OF HOW
 THEY APPEAR ON THE PLANS.
  
 6. THE COOK TOP NEEDS A SHUT OFF VALVE BEFORE THE MP
 REGULATOR IF THE CIRCLE IS A MP REGULATOR (REFERENCE
 COMMENT #5). PER FBC-2004 FUEL GAS, SECTION 409.4 MP
 REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 **RESPONSE NOTED, HOWEVER UNTIL THE MP REGULATORS ARE
 CLEARLY IDENTIFIED ON THE PLANS AS ASKED FOR IN COMMENT
 #5 THIS COMMENT SHALL REMAIN.
  
 7. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATORS
 (2/PSI TO 0.5/PSI REGULATORS) TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS
 CODE SEC 402.2. THE MANUFACTURER SHEETS SHOULD CLEARLY
 INDICATE THE MP REGULATOR MAKE, MODEL NUMBER, BTU LOAD
 CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY SUCH AS CSA, AGA, OR UL.
  
 **RESPONSE NOTED, HOWEVER THIS COMMENT WAS NOT
 ADDRESSED. THE REQUIRED MANUFACTURE SHEETS FOR THE MP
 REGULATORS WAS NOT IN THE RESUBMITTAL PACKAGE.
  
 8. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS
 ISOMETRICS DO NOT HAVE ORIGINAL SIGNATURES ON THEM OF
 THE PERSON TAKING THE RESPONSIBILITY FOR THEM. THE
 SIGNATURES ARE COPIED FROM A FAX.
  
 **THE FOLLOWING IS A NEW COMMENT DUE TO THE RESUMITTED
 GAS ISOMETRIC.
  
 9. A MP REGULATOR (2 PSI TO 0.5 PSI REGULATOR) IS
 REQUIRED FOR THE FUTURE B.B.Q. AND SHALL BE INSTALLED
 BEFORE FINAL GAS INSPECTION. PER FBC-2004 FUEL GAS CODE
 SECTION 410.1 PRESSURE REGULATOR.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 **PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-09-30 Cont ID  
Sent By mperson Date 2008-09-30 Time 08:39 Rev Time 1.30
Received By mperson Date 2008-09-30 Time 08:39 Sent To B
Notes
2008-09-30 09:48:47GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.(GAS PLANS
 LOCATED IN SUPPLEMENTAL INFORMATION BOOK)
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 OF PIPE WITH NO CORRESPONDING LENGTHS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE ANY OF
 THE ABOVEGROUND PIPING MATERIAL AS WELL AS SOME CUT
 SECTIONS OF UNDERGROUND PIPING. THE ISOMETRIC ALSO DOES
 NOT INDICATE PIPE SIZES TO ALL CUT SECTIONS OF PIPE.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THE ISOMETRIC INDICATES 97' D.L. (LONGEST
 LENGTH), HOWEVER NOT ALL CUT SECTIONS OF GAS PIPE HAVE
 CORRESPONDING LENGTHS. PLEASE REFERENCE COMMENT #1 AND
 COMPLY.
  
 4. THE FUTURE B.B.Q. NEEDS TO BE CAPPED GAS TIGHT. PER
 FBC-2004 FUEL GAS SEC. 404.12 OUTLET CLOSURES: GAS
 OUTLETS THAT DO NOT CONNECT TO APPLIANCES SHALL BE
 CAPPED GAS TIGHT.
  
 5. CLEARLY INDICATE THE LOCATION OF THE MP REGULATORS
 (2/PSI TO 0.5/PSI REGULATORS) ON THE RESUBMITTED
 ISOMETRIC OR PROVIDE A LEGEND OF HOW THEY APPEAR ON THE
 PLANS. ALSO PROVIDE A DETAIL OF THE GAS LAMP VALVE BOX
 CLEARLY INDICATING THE LOCATION OF THE SHUT OFF VALVE
 AND MP REGULATOR. PLEASE CLARIFY THE LOCATION OF THE
 GAS LAMP VALVE BOXES. IT APPEARS TO BE LOCATED AT
 FINNISH GRADE LEVEL. PLEASE CLARIFY HOW THE MP
 REGULATORS WILL WORK IF VALVE BOX FILLS WITH WATER
 DURING A STORM. PER FBC-2004 FUEL GAS CODE SECTION
 401.1 SCOPE.
  
 6. THE COOK TOP NEEDS A SHUT OFF VALVE BEFORE THE MP
 REGULATOR IF THE CIRCLE IS A MP REGULATOR (REFERENCE
 COMMENT #5). PER FBC-2004 FUEL GAS, SECTION 409.4 MP
 REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 7. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATORS
 (2/PSI TO 0.5/PSI REGULATORS) TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS
 CODE SEC 402.2. THE MANUFACTURER SHEETS SHOULD CLEARLY
 INDICATE THE MP REGULATOR MAKE, MODEL NUMBER, BTU LOAD
 CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY SUCH AS CSA, AGA, OR UL.
  
 8. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-10-19 Cont ID  
Sent By dpalmer Date 2009-10-19 Time 14:21 Rev Time 0.00
Received By dpalmer Date 2009-10-19 Time 14:21 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-03-31 Cont ID  
Sent By adarroug Date 2009-03-31 Time 14:16 Rev Time 0.00
Received By adarroug Date 2009-03-31 Time 14:15 Sent To Z
Notes
2009-03-31 14:16:23TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-19 Cont ID  
Sent By adarroug Date 2009-03-19 Time 10:55 Rev Time 0.00
Received By adarroug Date 2009-03-19 Time 10:55 Sent To M
Notes
2009-03-19 10:55:30TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 08:43 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 08:43 Sent To Z
Notes
2008-11-06 08:43:45TO "Z" BOX/RESUB--FOR "Z" AND "L" REVIEWS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 16:29 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 16:29 Sent To Z
Notes
2008-10-17 16:29:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-01 Cont ID  
Sent By rmcdouga Date 2008-10-01 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2008-09-19 Time 11:51 Sent To  
Notes
2008-09-19 11:51:37TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 5 Status P Date 2009-10-21 Cont ID  
Sent By rkussner Date 2009-10-21 Time 09:30 Rev Time 0.00
Received By rkussner Date 2009-10-21 Time 09:30 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 4 Status P Date 2009-04-01 Cont ID  
Sent By rkussner Date 2009-04-01 Time 09:21 Rev Time 0.00
Received By rkussner Date 2009-04-01 Time 09:21 Sent To PC
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2008-11-13 Cont ID  
Sent By rkussner Date 2008-11-13 Time 12:37 Rev Time 0.00
Received By rkussner Date 2008-11-13 Time 12:36 Sent To  
Notes
2008-11-13 12:39:01***LANDSCAPE APPROVED WITH PROVISO***
  
 MUST SUBMIT REVISED LANDSCAPE PLAN TO ADDRESS PREVIOUS
 COMMENTS AND HAVE PLAN APPROVED PRIOR TO C/O.---RAK
 11/13/08

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2008-11-10 Cont ID  
Sent By rkussner Date 2008-11-10 Time 10:23 Rev Time 0.00
Received By rkussner Date 2008-11-10 Time 10:23 Sent To PC
Notes
2008-11-10 10:28:51***LANDSCAPE REVIEW FAILED***
  
 1. PROPOSED TREES LOCATED AT REAR OF SITE SHALL COMPLY
 WITH FPL'S "PLANT THE RIGHT TREE IN THE RIGHT PLACE"
 PROGRAM. THE PROPOSED TABEBUIA TREES WILL BE TOO CLOSE
 TO THE OVERHEAD LINES. PLEASE SELECT ANOTHER SPECIES
 THAT COMPLIES WITH FPL.
  
 2. REPEAT COMMENT: PLEASE SHOW TREES ON NEIGHBORING
 PROPERTIES THAT ARE CLOSE TO THE COMMON PROPERTY LINES
 TO AVOID CONFLICTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @(561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-10-22 Cont ID  
Sent By rkussner Date 2008-10-22 Time 16:10 Rev Time 0.00
Received By rkussner Date 2008-10-22 Time 16:10 Sent To  
Notes
2008-10-22 17:06:03***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-442(D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND LANDSCAPED OPEN SPACE SHALL BE PLANTED
 WITH GRASS.
  
 2. PURSUANT TO SECTION 94-445(4)(G)(3), AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED
 LANDSCAPED AREAS FOR ALL PROPERTIES. THIS INCLUDES THE
 RIGHT-OF-WAY AREA MENTIONED IN ITEM #1.
  
 3. BASED UPON THE LANDSCAPE CALCULATIONS PROVIDED, FOUR
 SHADE OR FLOWERING TREES ARE REQUIRED AND ONLY THREE
 HAVE BEEN PROVIDED.
  
 4, PURSUANT TO SECTION 94-442(C), PALM TREES MAY BE
 SUBSTITUTED FOR NOT MORE THAN 35 PERCENT OF THE SHADE
 OR FLOWERING TREES REQUIRED BY THIS ARTICLE.
  
 5. PROVIDE A PLANT LIST IN TABULAR FORM THAT IDENTIFIES
 ALL EXISTING AND PROPOSED PLANT MATERIAL BY NAME,
 QUANTITIY, SIZE AND SPACING. THE QUANTITY OF PLANT
 MATERIAL SHALL BE SHOWN IN EACH PLANTING AREA, AS WELL.
  
 6. PURSUANT TO SECTION 94-442(B)(1), ALL OPEN SPACE,
 EXCLUDING VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES
 AND SURFACE PARKING, SHALL BE COVERED WITH GRASS,
 GROUND COVER, SHRUBBERY OR OTHER SUTIABLE PLANT
 MATERIAL. THE LOOSE STONE THAT WAS PROPOSED DOES NOT
 MEET THIS REQUIREMENT.
  
 7. PROVIDE SCREENING FOR ALL MECHANICAL EQUIPMENT SUCH
 AS THE AIR CONDITIONING UNITS AND POOL EQUIPMENT.
  
 8. PROVIDE THE LOCATION ON THE LANDSCAPE PLAN OF ALL
 UTILITIES, EASEMENTS, OVERHANGING TREE LIMBS FROM
 NEIGHBORING PROPERTY AND ANYTHING ELSE THAT MAY
 INTERFERE WITH THE PROPOSED LANDCAPING.
  
 9. CERTAIN NOTES MUST APPEAR ON THE LANDSCAPE PLAN SUCH
 AS DEPTH OF MULCH IN THE PLANT BEDS. REMOVAL OF ALL
 PROHIBITED PLANT SPECIES AND THE REQUIRED PLANT GRADE.
  
 10.PURSUANT TO SECTION 94-442(G), ALL NEW DEVELOPMENT
 SHALL BE REQUIRED TO APPLY CERTAIN XERISCAPE TECHNIQUES
 FOR LANDSCAPING PRIOR TO RECEIVING A CERTIFICATE OF
 COCCUPANCY. THE ADOPTED DESIGN OPTIONS AND THE
 ACCOMPANYING POINTS USED TO MEET THE XERISCAPE
 REQUIREMENTS SHALL BE CLEARLY TABULATED ON THE
 LANDSCAPE PLAN AS REQUIRED IN SUBSECTION
 94-448(D)(2)(G). SUCH A LANDSCAPE PLAN MUST SATISFY A
 MINIMUM TOTAL OF 15 POINTS FOR A SINGLE FAMILY HOME.
  
  
 IF YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS,
 PLEASE CONTACT ROBERT KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2009-04-03 Time 12:10 Sent To  
Notes
2009-04-03 12:12:34REVISED PLANS HAVE BEEN REVIEWED FOR COMPLIANCE.
 ORIGINAL PLANS WERE SIGNED AND SEALED BY THE ARCHITECT
 OF RECORD. THEREFORE, THESE PLANS MUST BE APPROVED BY
 THE ARCHITECT OF RECORD IN ORDER TO BE INCORPORATED
 INTO THE RECORD SET OF PLANS. PLEASE RESUBMIT PLANS
 APPROVED BY THE ARCHITECT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-10-23 Cont ID  
Sent By tgordon Date 2008-10-23 Time 15:32 Rev Time 0.30
Received By tgordon Date 2008-10-23 Time 15:32 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-19 Cont ID  
Sent By tgordon Date 2008-09-19 Time 15:37 Rev Time 1.00
Received By tgordon Date 2008-09-19 Time 15:37 Sent To Z
Notes
2008-09-19 15:43:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-607.1.ABC.1.
  
 2) SEE PLAN M1.2 THE FOLLOWING SUPPLY AIR DUCTS (FLEX)
 NEED TO BE SIZED, LAUNDRY ROOM, STAIRS, BATH 4, HALL,
 FOYER, AND BEDROOM 5 CLOSET (SEE YELLOW HIGH LIGHTED
 DUCTS ON PLAN) PER 2004 FBC/R M1601.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-27 Cont ID  
Sent By mperson Date 2008-10-27 Time 10:03 Rev Time 0.30
Received By mperson Date 2008-10-27 Time 10:03 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-29 Cont ID  
Sent By mperson Date 2008-09-29 Time 14:54 Rev Time 1.30
Received By mperson Date 2008-09-29 Time 14:54 Sent To G
Notes
2008-09-29 15:50:57PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P1.1, PLUMBING NOTES #2: PLUMBING NOTE #2
 STATES "ALL SANITARY LINES SHALL HAVE A MINIMUM SLOPE
 OF 1/8" RISE PER ONE HORIZONTAL FOOT OF PIPE, UNLESS
 SPECIFICALLY INDICATED OTHERWISE". THIS IS NOT
 COMPLIANT WITH THE FBC-2004 PLUMBING TABLE 704.1 SLOPE
 OF HORIZONTAL DRAINAGE PIPE. TABLE 704.1 SPECIFICALLY
 INDICATES THE FOLLOWING MINIMUM SLOPE FOR THE FOLLOWING
 PIPE SIZES (2-1/2" OR LESS= 1/4" MINIMUM SLOPE PER
 FOOT) (3" TO 6"= 1/8" MINIMUM SLOPE PER FOOT) (8" OR
 LARGER= 1/16" MINIMUM SLOPE PER FOOT). PLEASE REVISE
 NOTE #2 PER THE FBC-2004 PLUMBING TABLE 704.1.
  
 2. SHEET P1.1, SANITARY PLUMBING RISER DIAGRAM:
 CLEANOUTS ARE REQUIRED AT THE BASE OF THE FOLLOWING
 STACKS PER THE FBC-2004 PLUMBING SECTION 708.3.4 BASE
 OF STACK.
  
 A} HIS AND HER SANITARY STACK.
  
 B} BATH 2.
  
 C} BATH 3.
  
 D} BATH 4.
  
 3. SHEET P1.1, SANITARY PLUMBING RISER DIAGRAM: THE
 AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO
 A BRANCH DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES
 IN DIAMETER. PER FBC-2004 PLUMBING SECTION 406.3 WASTE
 CONNECTION.
  
 4. SHEET P1.1, SANITARY PLUMBING RISER DIAGRAM: CLEARLY
 INDICATE THE SIZES OF ALL FIXTURE DRAINS AND WATER-SEAL
 TRAPS OR PROVIDE A FIXTURE SCHEDULE INDICATING THE
 REQUESTED SIZES. PER FBC-2004 PLUMBING SECTION 401.1
 SCOPE AND (W.P.B. AS AMENDED) SECTION 106.3.5.4 (9)
 PLUMBING.
  
 5. SHEET P1.1 WATER HEATER SCHEDULE: THE SCHEDULE
 INDICATES A RECIRCULATING PUMP FOR THE WATER HEATER
 SUPPLING HOT WATER TO HIS AND HER BATH, KITCHEN, AND
 POWDER ROOM. PLEASE CLEARLY INDICATE THAT THE HOT WATER
 RECIRCULATING PIPE WILL BE INSULATED WITH INSULATION OF
 AT LEAST 1/2 INCH MINIMUM THICKNESS. PER FBC-2004
 CHAPTER 13, SECTION 13-612.ABC.5 PIPING INSULATION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-11-23 Cont ID  
Sent By mcruz Date 2008-11-23 Time 15:13 Rev Time 0.00
Received By mcruz Date 2008-11-23 Time 15:13 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-10-23 Cont ID  
Sent By mcruz Date 2008-10-23 Time 08:42 Rev Time 0.00
Received By mcruz Date 2008-10-23 Time 08:40 Sent To E
Notes
2008-10-23 08:41:56***ZONING FAILED***
  
 1. SEE ATTACHED LANDSCAPE COMMENTS FROM CITY LANDSCAPE
 PLANNER, ROBERT KUSSNER (561.822.1462).
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-25 Cont ID  
Sent By mcruz Date 2008-09-25 Time 15:53 Rev Time 0.00
Received By mcruz Date 2008-09-25 Time 15:48 Sent To I
Notes
2008-09-25 15:52:20***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2): AS THE VALUE OF THE PROPOSED WORK EXCEEDS
 50% OF THE STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT
 VALUE" WITH THE P.B.C. PROPERTY APPRAISER'S OFFICE),
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDRS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  