Plan Review Details - Permit 08090442
| Plan Review Stops For Permit 08090442 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-10-31 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-10-31 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-10-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-10-01 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-09-30 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2008-10-02 07:10:41 | 2004 FBC W/2007 REVISIONS | | | NSFD | | | | | | DENIED BY BUILDING | | | | | | 1) SHOW COMPLIANCE WITH R302.1 AND R302.2. R302.1 | | | EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) | | | SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE | | | RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL | | | NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM | | | AN ADJACENT PROJECTION OR WALL. R302.2 OPENINGS SHALL | | | NOT BE PERMITTED IN THE EXTERIOR WALL OF A DWELLING OR | | | ACCESSORY BUILDING THAT IS SEPARATED FROM AN ADJACENT | | | BUILDING BY A DISTANCE OF LESS THAN 6 FEET (1828 MM). | | | THIS DISTANCE SHALL BE MEASURED PERPENDICULAR TO THE | | | LINE USED TO DETERMINE THE SEPARATION DISTANCE THE | | | STRUCTURE IS LESS THAN 6' FROM THE PROPERTY LINE IN ONE | | | SIDE. SPECIFY THE DISTANCE TO STRUCTURES ON THE | | | ADJACENT PROPERTY AT THIS LOCATION. | | | | | | 2) SPECIFY THE MINIMUM SIZE OF THE ATTIC ACCESS | | | OPENINGS ON THE PLANS. R807.1 ATTIC ACCESS. | | | IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF | | | CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED | | | TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) | | | AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR | | | GREATER. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS | | | THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND | | | SHALL BE LOCATED IN A HALLWAY OR OTHER READILY | | | ACCESSIBLE LOCATION. A 30-INCH (762 MM) MINIMUM | | | UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE | | | PROVIDED AT SOME POINT ABOVE THE ACCESS OPENING. SEE | | | SECTION M1305.1.3 FOR ACCESS REQUIREMENTS WHERE | | | MECHANICAL EQUIPMENT IS LOCATED IN ATTICS. | | | | | | 3) ON SHEET A2.3 THE WRONG CODE AND SECTION ARE | | | SPECIFIED FOR THE ROOF VENTILATION REQUIREMENTS. THE | | | CODE IS 2004 FBC AND THE SECTION IS R806.2 FROM THE FBC | | | RESIDENTIAL. PLEASE CORRECT. | | | | | | 4) SPECIFY THE HEIGHT OF THE GUARDS ON THE STAIR | | | DETAILS. R312.1 GUARDS REQUIRED. PORCHES, BALCONIES OR | | | RAISED FLOOR SURFACES LOCATED MORE THAN 30 INCHES (762 | | | MM) ABOVE THE FLOOR OR GRADE BELOW SHALL HAVE GUARDS | | | NOT LESS THAN 36 INCHES (914 MM) IN HEIGHT. OPEN SIDES | | | OF STAIRS WITH A TOTAL RISE OF MORE THAN 30 INCHES (762 | | | MM) ABOVE THE FLOOR OR GRADE BELOW SHALL HAVE GUARDS | | | NOT LESS THAN 34 INCHES (864 MM) IN HEIGHT MEASURED | | | VERTICALLY FROM THE NOSING OF THE TREADS. | | | | | | 5) SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING | | | REQUIRED. WHEN THERE IS USABLE SPACE BOTH ABOVE AND | | | BELOW THE CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, | | | DRAFTSTOPS SHALL BE INSTALLED SO THAT THE AREA OF THE | | | CONCEALED SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 | | | M 2 ). DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE | | | INTO APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS | | | ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING | | | MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN | | | FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING | | | CIRCUMSTANCES: | | | 1. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. | | | 2. FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB | | | OR PERFORATED MEMBERS. | | | SPECIFY THE LOCATION AND MATERIAL (502.1.2.1) THAT WILL | | | BE USED ON THE PLANS. | | | | | | 6) ON SHEET S1.1, THE DETAIL MARKERS MISTAKENLY REFER | | | TO SHEET S2.2, HOWEVER THE DETAILS ARE LOCATED ON SHEET | | | S2.4. PLEASE CORRECT. | | | | | | 7) THE WINDOW AND DOOR BUCK DETAILS ON SHEET S2.4 | | | CONFLICT WITH THOSE ON SHEET A6.2 FOR SPACING AND EMBED | | | REQUIREMENTS. PLEASE COORDINATE. | | | | | | 8) ON SHEET S2.1 THE NUMBERING OF THE FOUNDATION | | | DETAILS IS INCORRECT. THE FOOTING SCHEDULE SPECIFIES | | | DETAIL 3 FOR THE ISOLATED PADS AND DETAIL 4 IS THE | | | CORRECT ONE. PLEASE CORRECT. | | | | | | 9) SHOW COMPLIANCE WITH R309.2 AT GARAGE AND STORAGE | | | LOFT. R309.2 SEPARATION REQUIRED. THE GARAGE SHALL BE | | | SEPARATED FROM THE RESIDENCE AND ITS ATTIC AREA BY NOT | | | LESS THAN 1/2 -INCH (12.7 MM) GYPSUM BOARD APPLIED TO | | | THE GARAGE SIDE. GARAGES BENEATH HABITABLE ROOMS SHALL | | | BE SEPARATED FROM ALL HABITABLE ROOMS ABOVE BY NOT LESS | | | THAN 5 / 8 -INCH (15.9 MM) TYPE X GYPSUM BOARD OR | | | EQUIVALENT. WHERE THE SEPARATION IS A FLOOR-CEILING | | | ASSEMBLY, THE STRUCTURE SUPPORTING THE SEPARATION SHALL | | | ALSO BE PROTECTED BY NOT LESS THAN 1/2 -INCH (12.7 MM) | | | GYPSUM BOARD OR EQUIVALENT. | | | | | | 10) ON SHEET S1.3, THE ROOF FRAMING PLAN HAS AN ID TAG | | | IN ONE CORNER WITH AN "X", THIS SHOULD BE AN "A". | | | PLEASE CORRECT. | | | | | | 11) IN THE ANCHOR SCHEDULE ON S1.3, THE H7Z SIMPSON | | | CONNECTOR IS SPECIFIED WITH 2-8D NAILS AT THE TRUSS AND | | | THE SIMPSON CATALOG REQUIRES 4. PLEASE CORRECT. | | | | | | 12) ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH | | | SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC | | | RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL | | | BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT | | | 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT | | | INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS | | | SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 | | | MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH | | | FIGURE R803.2.3.1. PLEASE REVISE SHEATHING FASTENING | | | SCHEDULE ON S2.4 | | | | | | 13) THE SURVEY THAT WAS SUBMITTED SHOWS A ONE STORY | | | STRUCTURE, WHICH DOES NOT AGREE WITH THE PLANS. PLEASE | | | CORRECT. | | | | | | 14) ON SHEET A6.1 ALL OF THE WINDOWS ARE SPECIFIED ON | | | THE PLANS WITH DESIGN PRESSURES OF +70 AND -90 PSF. | | | THIS DOES NOT CONCUR WITH THE PRODUCT APPROVALS. THE | | | DESIGN PRESSURES FOR THE 5/16" LAMI SINGLE HUNG WINDOWS | | | IN THE NOA DEPEND ON GLASS TYPES USED. SEE TABLES 1,2 | | | AND 3 OF THE NOA. THE FIXED GLASS DESIGN PRESSURES ARE | | | BASED ON AREA. SEE NOA TABLES. | | | | | | 15) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE 1 | | | X HEAVY MULLIONS DO NOT APPEAR TO WORK FOR DOORS E107 | | | AND E108, THE TWO 6' X 8' DOORS WITH THE 3' X6' | | | TRANSOMS AT THE FAMILY ROOM. PLEASE PROVIDE AN | | | ELEVATION AT THIS LOCATION AND SPECIFY HOW THEY WILL BE | | | INSTALLED. FBC R301.2.1 | | | | | | NOTE: THE ENERGY CALCULATIONS HAVE THE WRONG | | | JURISDICTION SPECIFIED. THIS HAS BEEN CORRECTED. | | | | | | IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE SUBMIT A | | | RESPONSE LETTER WITH THE RESUBMITTAL THAT INDICATES HOW | | | THE ABOVE ITEMS HAVE BEEN ADDRESSED. THANK YOU. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-10-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-10-23 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-10-23 |
Time |
13:20 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-09-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-09-29 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-09-26 |
Time |
13:40 |
Sent To |
P |
|
| Notes |
| 2008-09-26 16:27:02 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE | | | EFFECTIVE 8 DECEMBER 2006. FOR RECORD RETENTION PER | | | 106.5 FBC, AND CLARITY IN THE FIELD WHEN WORKING FROM | | | THIS DOCUMENT, PLEASE INDICATE THE CODE CYCLES UNDER | | | WHICH THIS PLAN WAS DESIGNED. ***SEE NOTE #1 SHEET | | | E2.1. | | | | | | 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). CIRCUITS 1,4,8 AND 10 PANEL | | | "B" AND CIRCUITS 9 AND 10 IN PANEL "A" HAVE THESE | | | CIRCUITS ON 15 AMP OCP AND #14 CONDUCTORS. | | | | | | 3} THE DINING ROOM CIRCUIT #6 IN PANEL "A" IS REQUIRED | | | TO BE ON A SMALL APPLIANCE CIRCUIT PER 210.52(B)(1). | | | | | | 4} THE CIRCUIT BREAKER, OCP, FOR CIRCUIT #24 GARAGE | | | DOOR OPENER, PANEL "A" IS INCORRECTLY LABELED 10 AMP. | | | SEE 240.6(A) FOR STANDARD RATINGS. | | | | | | NOTE: IN THE CALCULATION SUB TOTALS THE DIVIDER IS | | | SHOWN AS 24 VOLTS, BUT CORRECTLY CALCULATED USING 240 | | | VOLTS. | | | | | | 5} 9B-3.0472 CARBON MONOXIDE PROTECTION. | | | (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW | | | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A | | | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, | | | OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON | | | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM | | | USED FOR SLEEPING PURPOSES. | | | (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR | | | PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING | | | IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS | | | SHALL HAVE BATTERY BACK UP. | | | (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE | | | LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING | | | LABORATORY. | | | SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED | | | 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. | | | HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN. | | | NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE.*** | | | REVISE SHEET E1.2 FOR COMPLIANCE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-11-24 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-11-24 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2008-11-24 09:41:29 | COMPLIANCE WITH ALL COMMENTS FROM PREVIOUS REVIEW UNDER | | | SEPARATE PERMIT WILL BE REQUIRED. LM |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2008-10-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-10-27 |
Time |
10:39 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2008-10-27 |
Time |
10:39 |
Sent To |
B |
|
| Notes |
| 2008-10-27 10:47:41 | GAS PLAN REVIEW: | | | DENIED **2ND TIME: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND | | | WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE | | | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW | | | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW | | | COMMENTS. (RESUBMITTED GAS PLANS LOCATED IN THE | | | SUPPLEMENTAL INFORMATION BOOK) | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE SECTION 401.1 SCOPE. | | | *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE | | | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. | | | PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS | | | OF PIPE WITH NO CORRESPONDING LENGTHS. | | | | | | **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC | | | STILL HAS CUT SECTIONS OF PIPE WITH NO CORRESPONDING | | | LENGTHS. PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT | | | SECTION OF PIPE WITH NO CORRESPONDING LENGTHS AND | | | COMPLY ON THE NEXT RESUBMITTAL. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE. | | | *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE ANY OF | | | THE ABOVEGROUND PIPING MATERIAL AS WELL AS SOME CUT | | | SECTIONS OF UNDERGROUND PIPING. THE ISOMETRIC ALSO DOES | | | NOT INDICATE PIPE SIZES TO ALL CUT SECTIONS OF PIPE. | | | | | | **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC | | | ONLY INDICATION OF ABOVE GROUND PIPING MATERIAL IS ONE | | | CUT SECTION OF 3/4" GALV. PIPE TO ONE TANKLESS WATER | | | HEATER. WHAT IS THE PIPING MATERIAL TO THE OTHER ABOVE | | | GROUND CUT SECTIONS OF PIPE? THE RESUBMITTED GAS | | | ISOMETRIC ALSO STILL DOES NOT INDICATE THE PIPING | | | MATERIAL ABOVE/UNDERGROUND OR PIPE SIZES TO THE TWO GAS | | | LAMPS ON THE OUTLET SIDE OF THE MP REGULATORS. THE | | | UNDERGROUND PIPING MATERIAL TO THE TANKLESS WATER | | | HEATERS IS NOT INDICATED. | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | *NOTE: THE ISOMETRIC INDICATES 97' D.L. (LONGEST | | | LENGTH), HOWEVER NOT ALL CUT SECTIONS OF GAS PIPE HAVE | | | CORRESPONDING LENGTHS. PLEASE REFERENCE COMMENT #1 AND | | | COMPLY. | | | | | | **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS ISOMETRIC | | | NOW INDICATES 108' D.L. (LONGEST LENGTH) AND STILL NOT | | | ALL CUT SECTIONS OF GAS PIPE HAVE CORRESPONDING | | | LENGTHS. AGAIN PLEASE REFERENCE COMMENT #1 AND COMPLY. | | | UNTIL COMMENT #1 IS FULLY ADDRESSED AND THIS COMMENT IS | | | CORRELATED WITH COMMENT #1, THE COMMENT SHALL REMAIN. | | | | | | 4. "OK" COMMENT WAS ADDRESSED> | | | | | | 5. CLEARLY INDICATE THE LOCATION OF THE MP REGULATORS | | | (2 PSI TO 0.5 PSI REGULATORS) ON THE RESUBMITTED | | | ISOMETRIC OR PROVIDE A LEGEND OF HOW THEY APPEAR ON THE | | | PLANS. ALSO PROVIDE A DETAIL OF THE GAS LAMP VALVE BOX | | | CLEARLY INDICATING THE LOCATION OF THE SHUT OFF VALVE | | | AND MP REGULATOR. PLEASE CLARIFY THE LOCATION OF THE | | | GAS LAMP VALVE BOXES. IT APPEARS TO BE LOCATED AT | | | FINNISH GRADE LEVEL. PLEASE CLARIFY HOW THE MP | | | REGULATORS WILL WORK IF VALVE BOX FILLS WITH WATER | | | DURING A STORM. PER FBC-2004 FUEL GAS CODE SECTION | | | 401.1 SCOPE. | | | | | | **RESPONSE NOTED, AND COMMENT WAS PARTIALLY ADDRESSED. | | | THE RESUBMITTED GAS ISOMETRIC STILL DOES NOT CLEARLY | | | INDICATE THE REQUIRED MP REGULATORS (2 PSI TO 0.5 PSI | | | REGULATORS) ON THE PLANS OR PROVIDE A LEGEND OF HOW | | | THEY APPEAR ON THE PLANS. | | | | | | 6. THE COOK TOP NEEDS A SHUT OFF VALVE BEFORE THE MP | | | REGULATOR IF THE CIRCLE IS A MP REGULATOR (REFERENCE | | | COMMENT #5). PER FBC-2004 FUEL GAS, SECTION 409.4 MP | | | REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE | | | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | | | **RESPONSE NOTED, HOWEVER UNTIL THE MP REGULATORS ARE | | | CLEARLY IDENTIFIED ON THE PLANS AS ASKED FOR IN COMMENT | | | #5 THIS COMMENT SHALL REMAIN. | | | | | | 7. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATORS | | | (2/PSI TO 0.5/PSI REGULATORS) TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS | | | CODE SEC 402.2. THE MANUFACTURER SHEETS SHOULD CLEARLY | | | INDICATE THE MP REGULATOR MAKE, MODEL NUMBER, BTU LOAD | | | CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED | | | TESTING LABORATORY SUCH AS CSA, AGA, OR UL. | | | | | | **RESPONSE NOTED, HOWEVER THIS COMMENT WAS NOT | | | ADDRESSED. THE REQUIRED MANUFACTURE SHEETS FOR THE MP | | | REGULATORS WAS NOT IN THE RESUBMITTAL PACKAGE. | | | | | | 8. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING | | | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE | | | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE | | | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER | | | SECTION *106.3.4.3. | | | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, | | | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, | | | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA | | | STATUTES 481 AND 471 RESPECTIVELY. | | | | | | **RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS | | | ISOMETRICS DO NOT HAVE ORIGINAL SIGNATURES ON THEM OF | | | THE PERSON TAKING THE RESPONSIBILITY FOR THEM. THE | | | SIGNATURES ARE COPIED FROM A FAX. | | | | | | **THE FOLLOWING IS A NEW COMMENT DUE TO THE RESUMITTED | | | GAS ISOMETRIC. | | | | | | 9. A MP REGULATOR (2 PSI TO 0.5 PSI REGULATOR) IS | | | REQUIRED FOR THE FUTURE B.B.Q. AND SHALL BE INSTALLED | | | BEFORE FINAL GAS INSPECTION. PER FBC-2004 FUEL GAS CODE | | | SECTION 410.1 PRESSURE REGULATOR. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | **PLEASE CALL IF THERE ARE ANY QUESTIONS. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-09-30 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-09-30 |
Time |
08:39 |
Rev Time |
1.30 |
| Received By |
mperson |
Date |
2008-09-30 |
Time |
08:39 |
Sent To |
B |
|
| Notes |
| 2008-09-30 09:48:47 | GAS PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE.(GAS PLANS | | | LOCATED IN SUPPLEMENTAL INFORMATION BOOK) | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE SECTION 401.1 SCOPE. | | | *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE | | | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. | | | PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS | | | OF PIPE WITH NO CORRESPONDING LENGTHS. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE. | | | *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE ANY OF | | | THE ABOVEGROUND PIPING MATERIAL AS WELL AS SOME CUT | | | SECTIONS OF UNDERGROUND PIPING. THE ISOMETRIC ALSO DOES | | | NOT INDICATE PIPE SIZES TO ALL CUT SECTIONS OF PIPE. | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | *NOTE: THE ISOMETRIC INDICATES 97' D.L. (LONGEST | | | LENGTH), HOWEVER NOT ALL CUT SECTIONS OF GAS PIPE HAVE | | | CORRESPONDING LENGTHS. PLEASE REFERENCE COMMENT #1 AND | | | COMPLY. | | | | | | 4. THE FUTURE B.B.Q. NEEDS TO BE CAPPED GAS TIGHT. PER | | | FBC-2004 FUEL GAS SEC. 404.12 OUTLET CLOSURES: GAS | | | OUTLETS THAT DO NOT CONNECT TO APPLIANCES SHALL BE | | | CAPPED GAS TIGHT. | | | | | | 5. CLEARLY INDICATE THE LOCATION OF THE MP REGULATORS | | | (2/PSI TO 0.5/PSI REGULATORS) ON THE RESUBMITTED | | | ISOMETRIC OR PROVIDE A LEGEND OF HOW THEY APPEAR ON THE | | | PLANS. ALSO PROVIDE A DETAIL OF THE GAS LAMP VALVE BOX | | | CLEARLY INDICATING THE LOCATION OF THE SHUT OFF VALVE | | | AND MP REGULATOR. PLEASE CLARIFY THE LOCATION OF THE | | | GAS LAMP VALVE BOXES. IT APPEARS TO BE LOCATED AT | | | FINNISH GRADE LEVEL. PLEASE CLARIFY HOW THE MP | | | REGULATORS WILL WORK IF VALVE BOX FILLS WITH WATER | | | DURING A STORM. PER FBC-2004 FUEL GAS CODE SECTION | | | 401.1 SCOPE. | | | | | | 6. THE COOK TOP NEEDS A SHUT OFF VALVE BEFORE THE MP | | | REGULATOR IF THE CIRCLE IS A MP REGULATOR (REFERENCE | | | COMMENT #5). PER FBC-2004 FUEL GAS, SECTION 409.4 MP | | | REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE | | | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | | | 7. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATORS | | | (2/PSI TO 0.5/PSI REGULATORS) TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS | | | CODE SEC 402.2. THE MANUFACTURER SHEETS SHOULD CLEARLY | | | INDICATE THE MP REGULATOR MAKE, MODEL NUMBER, BTU LOAD | | | CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED | | | TESTING LABORATORY SUCH AS CSA, AGA, OR UL. | | | | | | 8. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING | | | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE | | | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE | | | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER | | | SECTION *106.3.4.3. | | | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, | | | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, | | | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA | | | STATUTES 481 AND 471 RESPECTIVELY. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-10-19 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-10-19 |
Time |
14:21 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-03-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-03-31 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-03-31 |
Time |
14:15 |
Sent To |
Z |
|
| Notes |
| 2009-03-31 14:16:23 | TO "Z" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-03-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-03-19 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-03-19 |
Time |
10:55 |
Sent To |
M |
|
| Notes |
| 2009-03-19 10:55:30 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-11-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-06 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-06 |
Time |
08:43 |
Sent To |
Z |
|
| Notes |
| 2008-11-06 08:43:45 | TO "Z" BOX/RESUB--FOR "Z" AND "L" REVIEWS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-10-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-17 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-17 |
Time |
16:29 |
Sent To |
Z |
|
| Notes |
| 2008-10-17 16:29:45 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-10-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-10-01 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-09-19 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2008-09-19 11:51:37 | TO "SFR" "Z" |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
5 |
Status |
P |
Date |
2009-10-21 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-10-21 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-10-21 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
P |
Date |
2009-04-01 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-04-01 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-04-01 |
Time |
09:21 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
P |
Date |
2008-11-13 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-11-13 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2008-11-13 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2008-11-13 12:39:01 | ***LANDSCAPE APPROVED WITH PROVISO*** | | | | | | MUST SUBMIT REVISED LANDSCAPE PLAN TO ADDRESS PREVIOUS | | | COMMENTS AND HAVE PLAN APPROVED PRIOR TO C/O.---RAK | | | 11/13/08 |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
2008-11-10 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-11-10 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2008-11-10 |
Time |
10:23 |
Sent To |
PC |
|
| Notes |
| 2008-11-10 10:28:51 | ***LANDSCAPE REVIEW FAILED*** | | | | | | 1. PROPOSED TREES LOCATED AT REAR OF SITE SHALL COMPLY | | | WITH FPL'S "PLANT THE RIGHT TREE IN THE RIGHT PLACE" | | | PROGRAM. THE PROPOSED TABEBUIA TREES WILL BE TOO CLOSE | | | TO THE OVERHEAD LINES. PLEASE SELECT ANOTHER SPECIES | | | THAT COMPLIES WITH FPL. | | | | | | 2. REPEAT COMMENT: PLEASE SHOW TREES ON NEIGHBORING | | | PROPERTIES THAT ARE CLOSE TO THE COMMON PROPERTY LINES | | | TO AVOID CONFLICTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @(561) 822-1462. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2008-10-22 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-10-22 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2008-10-22 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2008-10-22 17:06:03 | ***LANDSCAPE REVIEW FAILED*** | | | | | | 1. PURSUANT TO SECTION 94-442(D), PRIVATE LAND AND | | | PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK | | | SURFACES AND LANDSCAPED OPEN SPACE SHALL BE PLANTED | | | WITH GRASS. | | | | | | 2. PURSUANT TO SECTION 94-445(4)(G)(3), AUTOMATIC | | | IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED | | | LANDSCAPED AREAS FOR ALL PROPERTIES. THIS INCLUDES THE | | | RIGHT-OF-WAY AREA MENTIONED IN ITEM #1. | | | | | | 3. BASED UPON THE LANDSCAPE CALCULATIONS PROVIDED, FOUR | | | SHADE OR FLOWERING TREES ARE REQUIRED AND ONLY THREE | | | HAVE BEEN PROVIDED. | | | | | | 4, PURSUANT TO SECTION 94-442(C), PALM TREES MAY BE | | | SUBSTITUTED FOR NOT MORE THAN 35 PERCENT OF THE SHADE | | | OR FLOWERING TREES REQUIRED BY THIS ARTICLE. | | | | | | 5. PROVIDE A PLANT LIST IN TABULAR FORM THAT IDENTIFIES | | | ALL EXISTING AND PROPOSED PLANT MATERIAL BY NAME, | | | QUANTITIY, SIZE AND SPACING. THE QUANTITY OF PLANT | | | MATERIAL SHALL BE SHOWN IN EACH PLANTING AREA, AS WELL. | | | | | | 6. PURSUANT TO SECTION 94-442(B)(1), ALL OPEN SPACE, | | | EXCLUDING VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES | | | AND SURFACE PARKING, SHALL BE COVERED WITH GRASS, | | | GROUND COVER, SHRUBBERY OR OTHER SUTIABLE PLANT | | | MATERIAL. THE LOOSE STONE THAT WAS PROPOSED DOES NOT | | | MEET THIS REQUIREMENT. | | | | | | 7. PROVIDE SCREENING FOR ALL MECHANICAL EQUIPMENT SUCH | | | AS THE AIR CONDITIONING UNITS AND POOL EQUIPMENT. | | | | | | 8. PROVIDE THE LOCATION ON THE LANDSCAPE PLAN OF ALL | | | UTILITIES, EASEMENTS, OVERHANGING TREE LIMBS FROM | | | NEIGHBORING PROPERTY AND ANYTHING ELSE THAT MAY | | | INTERFERE WITH THE PROPOSED LANDCAPING. | | | | | | 9. CERTAIN NOTES MUST APPEAR ON THE LANDSCAPE PLAN SUCH | | | AS DEPTH OF MULCH IN THE PLANT BEDS. REMOVAL OF ALL | | | PROHIBITED PLANT SPECIES AND THE REQUIRED PLANT GRADE. | | | | | | 10.PURSUANT TO SECTION 94-442(G), ALL NEW DEVELOPMENT | | | SHALL BE REQUIRED TO APPLY CERTAIN XERISCAPE TECHNIQUES | | | FOR LANDSCAPING PRIOR TO RECEIVING A CERTIFICATE OF | | | COCCUPANCY. THE ADOPTED DESIGN OPTIONS AND THE | | | ACCOMPANYING POINTS USED TO MEET THE XERISCAPE | | | REQUIREMENTS SHALL BE CLEARLY TABULATED ON THE | | | LANDSCAPE PLAN AS REQUIRED IN SUBSECTION | | | 94-448(D)(2)(G). SUCH A LANDSCAPE PLAN MUST SATISFY A | | | MINIMUM TOTAL OF 15 POINTS FOR A SINGLE FAMILY HOME. | | | | | | | | | IF YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS, | | | PLEASE CONTACT ROBERT KUSSNER @ (561) 822-1462. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-04-03 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2009-04-03 12:12:34 | REVISED PLANS HAVE BEEN REVIEWED FOR COMPLIANCE. | | | ORIGINAL PLANS WERE SIGNED AND SEALED BY THE ARCHITECT | | | OF RECORD. THEREFORE, THESE PLANS MUST BE APPROVED BY | | | THE ARCHITECT OF RECORD IN ORDER TO BE INCORPORATED | | | INTO THE RECORD SET OF PLANS. PLEASE RESUBMIT PLANS | | | APPROVED BY THE ARCHITECT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-10-23 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-10-23 |
Time |
15:32 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-10-23 |
Time |
15:32 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-09-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-09-19 |
Time |
15:37 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2008-09-19 |
Time |
15:37 |
Sent To |
Z |
|
| Notes |
| 2008-09-19 15:43:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-607.1.ABC.1. | | | | | | 2) SEE PLAN M1.2 THE FOLLOWING SUPPLY AIR DUCTS (FLEX) | | | NEED TO BE SIZED, LAUNDRY ROOM, STAIRS, BATH 4, HALL, | | | FOYER, AND BEDROOM 5 CLOSET (SEE YELLOW HIGH LIGHTED | | | DUCTS ON PLAN) PER 2004 FBC/R M1601.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-10-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-10-27 |
Time |
10:03 |
Rev Time |
0.30 |
| Received By |
mperson |
Date |
2008-10-27 |
Time |
10:03 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-09-29 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-09-29 |
Time |
14:54 |
Rev Time |
1.30 |
| Received By |
mperson |
Date |
2008-09-29 |
Time |
14:54 |
Sent To |
G |
|
| Notes |
| 2008-09-29 15:50:57 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET P1.1, PLUMBING NOTES #2: PLUMBING NOTE #2 | | | STATES "ALL SANITARY LINES SHALL HAVE A MINIMUM SLOPE | | | OF 1/8" RISE PER ONE HORIZONTAL FOOT OF PIPE, UNLESS | | | SPECIFICALLY INDICATED OTHERWISE". THIS IS NOT | | | COMPLIANT WITH THE FBC-2004 PLUMBING TABLE 704.1 SLOPE | | | OF HORIZONTAL DRAINAGE PIPE. TABLE 704.1 SPECIFICALLY | | | INDICATES THE FOLLOWING MINIMUM SLOPE FOR THE FOLLOWING | | | PIPE SIZES (2-1/2" OR LESS= 1/4" MINIMUM SLOPE PER | | | FOOT) (3" TO 6"= 1/8" MINIMUM SLOPE PER FOOT) (8" OR | | | LARGER= 1/16" MINIMUM SLOPE PER FOOT). PLEASE REVISE | | | NOTE #2 PER THE FBC-2004 PLUMBING TABLE 704.1. | | | | | | 2. SHEET P1.1, SANITARY PLUMBING RISER DIAGRAM: | | | CLEANOUTS ARE REQUIRED AT THE BASE OF THE FOLLOWING | | | STACKS PER THE FBC-2004 PLUMBING SECTION 708.3.4 BASE | | | OF STACK. | | | | | | A} HIS AND HER SANITARY STACK. | | | | | | B} BATH 2. | | | | | | C} BATH 3. | | | | | | D} BATH 4. | | | | | | 3. SHEET P1.1, SANITARY PLUMBING RISER DIAGRAM: THE | | | AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO | | | A BRANCH DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES | | | IN DIAMETER. PER FBC-2004 PLUMBING SECTION 406.3 WASTE | | | CONNECTION. | | | | | | 4. SHEET P1.1, SANITARY PLUMBING RISER DIAGRAM: CLEARLY | | | INDICATE THE SIZES OF ALL FIXTURE DRAINS AND WATER-SEAL | | | TRAPS OR PROVIDE A FIXTURE SCHEDULE INDICATING THE | | | REQUESTED SIZES. PER FBC-2004 PLUMBING SECTION 401.1 | | | SCOPE AND (W.P.B. AS AMENDED) SECTION 106.3.5.4 (9) | | | PLUMBING. | | | | | | 5. SHEET P1.1 WATER HEATER SCHEDULE: THE SCHEDULE | | | INDICATES A RECIRCULATING PUMP FOR THE WATER HEATER | | | SUPPLING HOT WATER TO HIS AND HER BATH, KITCHEN, AND | | | POWDER ROOM. PLEASE CLEARLY INDICATE THAT THE HOT WATER | | | RECIRCULATING PIPE WILL BE INSULATED WITH INSULATION OF | | | AT LEAST 1/2 INCH MINIMUM THICKNESS. PER FBC-2004 | | | CHAPTER 13, SECTION 13-612.ABC.5 PIPING INSULATION. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-11-23 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-11-23 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-11-23 |
Time |
15:13 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-10-23 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-10-23 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-10-23 |
Time |
08:40 |
Sent To |
E |
|
| Notes |
| 2008-10-23 08:41:56 | ***ZONING FAILED*** | | | | | | 1. SEE ATTACHED LANDSCAPE COMMENTS FROM CITY LANDSCAPE | | | PLANNER, ROBERT KUSSNER (561.822.1462). | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-09-25 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-09-25 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-09-25 |
Time |
15:48 |
Sent To |
I |
|
| Notes |
| 2008-09-25 15:52:20 | ***ZONING FAILED*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION | | | 94-441(C)(2): AS THE VALUE OF THE PROPOSED WORK EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT | | | VALUE" WITH THE P.B.C. PROPERTY APPRAISER'S OFFICE), | | | LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. | | | | | | PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | | THE ZLDRS. | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|
|