Plan Review Details - Permit 08090400
Plan Review Stops For Permit 08090400
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-05-28 Cont ID  
Sent By shill Date 2009-05-28 Time 11:10 Rev Time 0.00
Received By shill Date 2009-05-28 Time 11:10 Sent To  
Notes
2009-05-28 11:10:34REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-12-15 Cont ID  
Sent By shill Date 2008-12-15 Time 17:16 Rev Time 0.00
Received By shill Date 2008-12-15 Time 17:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-09 Cont ID  
Sent By shill Date 2008-10-09 Time 08:49 Rev Time 0.00
Received By shill Date 2008-10-09 Time 08:49 Sent To  
Notes
2008-10-09 08:50:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE A DETAIL FOR THE GENERATOR SLAB FBC R301. IF
 A PREFAB SLAB IS USED, ENGINEERING/CALCULATIONS ARE
 REQUIRED TO SHOW HOW THIS WILL RESIST WIND LOADS, FBC
 R301, FBC*106.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-05-15 Cont ID  
Sent By btrobaug Date 2009-05-15 Time 10:11 Rev Time 0.00
Received By btrobaug Date 2009-05-15 Time 08:53 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-09-25 Cont ID  
Sent By btrobaug Date 2008-09-25 Time 11:14 Rev Time 0.00
Received By btrobaug Date 2008-09-25 Time 11:01 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-05-20 Cont ID  
Sent By kstevens Date 2009-05-20 Time 11:34 Rev Time 0.00
Received By kstevens Date 2009-05-20 Time 11:34 Sent To M
Notes
2009-05-20 11:34:55GAS REVISION OK -- CHANGED TO 20KW, SMALLER LP TANK,
 DISTANCE TO GENERATOR FROM TANK & PIPE SIZE.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-12-11 Cont ID  
Sent By kstevens Date 2008-12-11 Time 10:10 Rev Time 0.00
Received By kstevens Date 2008-12-11 Time 10:10 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By mperson Date 2008-09-26 Time 09:05 Rev Time 1.30
Received By mperson Date 2008-09-26 Time 09:05 Sent To B
Notes
2008-09-26 09:35:55GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE PROVIDE A DETAIL ON HOW THE 1000 GAL U/G
 PROPANE TANK FITTING HOUSING, HOUSING COVER, TANK
 CONNECTIONS AND PIPING ARE TO BE PROTECTED AGAINST
 VEHICULAR DAMAGE IN THE DRIVEWAY. PER NFPA CHAPTER 58,
 SECTION 6.6.6.1 (B) (C) (D) (E).
  
 2. PLEASE KNOW THAT THE 1000 GAL PROPANE TANK DETAIL IS
 NOT LEGIBLE. PLEASE PROVIDE A DETAIL THAT IS LEGIBLE
 AND CLARIFIES IF THE PROPANE TANK IS AN ASME APPROVED
 NONINTERCHANGABE UNDERGROUND CONTAINER OR AN APPROVED
 INTERCHANGABLE ABOVEGROUND-UNDERGROUND CONTAINER. PER
 (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 13:06 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-14 Cont ID  
Sent By adarroug Date 2008-11-14 Time 10:54 Rev Time 0.00
Received By adarroug Date 2008-11-14 Time 10:53 Sent To G
Notes
2008-11-14 10:54:16TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 16:20 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 16:20 Sent To E
Notes
2008-09-22 16:20:37TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-09 Cont ID  
Sent By shill Date 2008-10-09 Time 08:51 Rev Time 0.00
Received By shill Date 2008-09-18 Time 10:33 Sent To  
Notes
2008-09-18 10:33:33TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2009-05-27 Cont ID  
Sent By rregueir Date 2009-05-27 Time 13:24 Rev Time 0.00
Received By rregueir Date 2009-05-27 Time 13:24 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-09-23 Cont ID  
Sent By tgordon Date 2008-09-23 Time 08:50 Rev Time 0.30
Received By tgordon Date 2008-09-23 Time 08:50 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-05-12 Cont ID  
Sent By mcruz Date 2009-05-12 Time 13:01 Rev Time 0.00
Received By mcruz Date 2009-05-12 Time 13:01 Sent To E
Notes
2009-05-12 13:02:16ROUTED TO BT FOR ELEC REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-09-21 Cont ID  
Sent By mcruz Date 2008-09-21 Time 15:54 Rev Time 0.00
Received By mcruz Date 2008-09-21 Time 15:54 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved