| 2008-10-07 11:58:52 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. A PERMIT APPLICATION WAS NOT WITH THE SUBMITTAL. ANY |
| | OWNER, AUTHORIZED AGENT, OR CONTRACTOR WHO INTENDES TO |
| | CONSTRUCT ENLARGE, ALTER, REPAIR, MOVE, DEMOLISH, OR |
| | CHANGE THE OCCUPANCY OF A BUILDING STRUCTURE, SHALL |
| | FIRST MAKE APPLICATION TO THE BUILDING OFFICIAL AND |
| | OPTAIN THE REQUIRED PERMIT. PER FBC-2004 CHAPTER 1, |
| | (W.P.B. AS AMENDED) SECTION 105.1 REQUIRED. |
| | |
| | 2. DECLARE THE GOVERNING CODE ON THE PLANS (FBC-2004 |
| | WITH 2007 REVISIONS). PER FBC-2004 CHAPTER 1, (W.P.B. |
| | AS AMENDED) SECTION 106.5 RETENTION OF CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004 |
| | EXISTING BUILDING CHAPTER 3. |
| | |
| | 4. THE PLAN SUBMITTED DOES NOT CONTAIN ENOUGH |
| | INFORMATION TO DO A PROPER PLUMBING PLAN REVIEW. PLEASE |
| | PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR |
| | PLAN CLEARLY INDICATING ALL PROPOSED CHANGES TO THE |
| | STRUCTURE. PLEASE KNOW THAT IF THERE IS NEW PROPOSED |
| | PLUMBING FOR THE STRUCTURE THAT SANITARY AND POTABLE |
| | WATER RISER DIAGRAMS ARE REQUIRED. PER FBC-2004 CHAPTER |
| | 1, (W.P.B. AS AMENDED) SECTION 106.3.1.3 PLUMBING (3), |
| | (4), (8), (10), (11), (12), (13). |
| | |
| | 5. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION |
| | AND OCCUPANCY LOAD ON THE PLANS. |
| | PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR |
| | PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT |
| | TO OCCUPANCY OF THE GROUP LISTED BELOW. |
| | DAY CARE (SEE SECTION 313): GROUP D |
| | |
| | 6. PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM NUMBER OF |
| | REQUIRED PLUMBING FIXTURES FOR OCCUPANCY GROUP D, ARE |
| | PER THE FOLLOWING. |
| | |
| | A} WATER CLOSETS MALE/FEMALE= 1 PER 50. |
| | |
| | B} LAVATORIES MALE/FEMALE= 1 PER 50. |
| | |
| | C} DRINKING FOUNTAIN= 1 PER 100. |
| | |
| | D} 1 SERVICE SINK. |
| | |
| | E} (D) FOR DAY CARE NURSERIES, A MAXIMUM OF ONE BATHTUB |
| | SHALL BE REQUIRED. |
| | |
| | NOTE: PLEASE KNOW THAT THE SUBMITTED FLOOR PLAN DOES |
| | NOT CLEARLY INDICATE THE REQUIRED DRINKING FOUNTAIN AND |
| | BATHTUB. PLEASE KNOW THAT ALL PLUMBING FIXTURES SHALL |
| | BE ACCESSIBLE PER FBC-2004 CHAPTER 11, FLORIDA |
| | ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION THE |
| | FOLLOWING SECTIONS. |
| | |
| | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| | (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING |
| | INFORMATION) |
| | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| | MAXIMUM. |
| | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN |
| | 3" OF THE FRONT OF FOUNTAIN. |
| | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| | MOUNTED NEAR FRONT EDGE. |
| | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| | SPACE. |
| | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| | |
| | **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH |
| | THE FOLLOWING INFORMATION) |
| | 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. |
| | 11-4.16.3 HEIGHT. 17" TO 19". |
| | 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C |
| | 36" LONG. |
| | 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" |
| | HIGH. |
| | 11-4.16.6 DISPENSERS. SEE FIGURE 29(B). |
| | |
| | **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL |
| | REQUIRED WITH THE FOLLOWING INFORMATION) |
| | 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR |
| | COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE |
| | FIGURE 31) |
| | 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND |
| | A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE |
| | 32) |
| | 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO |
| | PROTECT AGAINST CONTACT. |
| | 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND |
| | ELECTRONICALLY CONTROLLED ARE EXAMPLES. |
| | 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F. |
| | |
| | ** 11-4.20 BATHTUBS (ELEVATION DETAIL REQUIRED WITH THE |
| | FOLLOWING INFORMATION) |
| | 11-4.20.2 FLOOR SPACE. (SEE FIGURE 33) |
| | 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34) |
| | 11-4.20.4 GRAB BARS. REQUIRED. (SEE FIGURE 33 & 34) |
| | 11-4.20.5 CONTROLS. (SEE FIGURE 34) |
| | 11-4.20.6 SHOWER UNIT. SHOWER SPRAY UNIT WITH A HOSE |
| | MINIMUM 60" LONG USED BOTH AS A FIXED OR HAND HELD |
| | SHALL BE PROVIDED. |
| | |
| | **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER |
| | ROOMS. |
| | 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR |
| | SPACE |
| | 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE |
| | SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR |
| | SPACE (PER 11-4.2.3) |
| | |
| | 7. PLAN SHEET IS INDICATING A KITCHEN: PLEASE KNOW THAT |
| | A GREASE INTERCEPTOR MAY BE REQUIREDTO RECIEVE THE |
| | DRAINAGE FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN |
| | WASTE LOCATED IN FOOD PREPERATION AREAS. THE MINIMUM |
| | SIZE GREASE INTERCEPTOR REQUIRED IS 750 GAL. PER |
| | MUNICIPAL CODE ARTICLE III SECTION 90-124, THE |
| | EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED AND |
| | LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE |
| | UTILITY DEPARTMENT. PLEASE CONTACT HOLLY MCGRATH |
| | (LABORATORY SUPERVISOR) HER PHONE NUMBER IS (561) |
| | 822-2200 EXT. 2271, HER E-MAIL ADDRESS IS |
| | [email protected] AND HER FAX NUMBER IS (561) 822-2279. |
| | NOTE: WRITTEN APPROVAL IS REQUIRED OF THE |
| | EXISTING/PROPOSED GREASE INTERCEPTOR OR DOCUMENTATION |
| | THAT A GREASE INTERCEPTOR IS NOT REQUIRED FROM |
| | ENVIRONMENTAL COMPLIANCE BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 8. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, |
| | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA |
| | STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | **PLEASE KNOW THAT ADDITIONAL COMMENTS MAY APPEAR ON |
| | THE NEXT REVIEW WHEN A COMPLETE SET OF ARCHITECTURAL |
| | PLANS ARE SUBMITTED. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |