Plan Review Details - Permit 08090396
Plan Review Stops For Permit 08090396
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-03 Cont ID  
Sent By mjacobs Date 2008-10-03 Time 07:08 Rev Time 0.00
Received By mjacobs Date 2008-10-03 Time 07:08 Sent To  
Notes
2008-10-03 07:08:25BUILDING PLAN REVIEW
 PERMIT: 08090396
 ADD: 8190 OKEECHOBEE BLVD.
 CONT:?
 TEL: (561)478-7477
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 NOTE: A CHANGE OF OCCUPANCY SHALL MEET THE REQUIREMENTS
 OF THE FBC (EXISTING) CH. 8.
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE INDICATED ON THE DRAWINGS.
  
 3) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS.
  
 4) 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS.
  
 61G15-23.002(2) FL. ADMIN. CODE. EACH SHEET OF PLANS
 AND PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471, F.S, SHALL BE SEALED, SIGNED AND DATED BY
 THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. A
 TITLE BLOCK SHALL BE USED ON EACH SHEET CONTAINING THE
 PRINTED NAME, ADDRESS, AND LICENSE NUMBER OF THE
 ENGINEER.
  
 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 5) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 6) PLEASE INDICATE THE TYPE OF BUILDING PER CHAPTER 6
 AND TABLE 601. THE USE AND OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 3 SHALL ALSO BE STATED ON THE PLANS. FBC 1004
 THE OCCUPANT LOAD OF THE SPACE SHALL BE STATED ON THE
 DRAWINGS. SHOW THE OCCUPANT LOAD OF EACH ROOM ON THE
 PLANS. PLEASE INDICATE IF THE BUILDING IS EQUIPPED WITH
 A FIRE SPRINKLER SYSTEM.
  
 7) PROVIDE AN EXISTING FLOOR PLAN AND PROPOSED FLOOR
 PLAN SHOWING ALL THE CHANGES TO THE LAYOUT OF THE
 STRUCTURE. 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 8) PER TABLE 302.3.2 FIRE PARTITIONS SEPARATING A
 BUSINESS OCCUPANCY AND A DAYCARE OCCUPANCY SHALL HAVE A
 2 HOUR RATING; PROVIDE THE UL ASSEMBLY FOR THE WALL.
 FBC (EXISTING) 812.1.2 DUE TO THE FACT THAT THIS IS A
 CHANGE OF OCCUPANCY WITH A SEPARATION WALL, THE
 SEPARATED WALL SHALL MEET THE REQUIREMENTS OF FBC
 CHAPTER 7
  
 9) SUBMIT A LIFE SAFETY PLANS SHOWING THE MEANS OF
 EGRESS WHICH SHALL INCLUDE THE EXIT ACCESS FBC 1013,
 THE EXIT FBC 1017 AND THE EXIT DISCHARGE FBC 1023.
 INDICATE THE EARLY WARNING SYSTEM, SMOKE CONTROL SYSTEM
 ETC.
  
 10) FBC 1008.1.2 DOORS SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 OR
 MORE.
  
 11) SHOW THE ACCESSIBLE ROUTE TO THE BUILDING
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING
 WITH 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS WITHIN THE BUILDING OR FACILITY.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) THE CORRIDORS SHALL BE FIRE-RESISTANCE RATED IN
 ACCORDANCE WITH TABLE 1016.1 PLEASE INDICATE THE WIDTH
 OF EACH CORRIDOR ON THE PLANS PER 1016.2.
 14) THE PLANS SUBMITTED ARE MISSING SOME ROOM AND DOOR
 DIMENSIONS WHICH ARE IMPORTANT FOR THE REVIEW. DETAIL
 ELEVATION DRAWINGS FOR THE SINK IN THE TODDLER ROOM ARE
 MISSING FROM THE DRAWINGS. WILL THE KITCHEN BE USED TO
 PREPARE MEALS FOR THE KIDS? IF SO, PROVIDE INFORMATION
 ON THE SUPPRESSION SYSTEM FOR THE KITCHEN IN
 CONFORMANCE WIT 904.2.1 ADDITIONAL INFORMATION IS
 REQUIRED 106.1.2*
  
 NOTE: ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT REVIEW
 WHEN A FULL SET OF ARCHITECTURAL PLANS ARE SUBMITTED. A
 GENERAL CONTRACTOR SHALL BE SIGNED ON THE APPLICATION
 TO DO THE WORK AT THIS PROJECT. A FAIR MARKET VALUE
 SHALL BE INDICATED ON THE PERMIT APPLICATION WHICH
 SHALL INCLUDE, STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, ARCHITECTURAL DESIGN FEES,
 MARKETING COSTS, AND OVERHEAD AND PROFIT EXCLUDING
 LAND. 108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-19 Cont ID  
Sent By tmoore Date 2008-09-19 Time 12:23 Rev Time 0.00
Received By tmoore Date 2008-09-19 Time 12:18 Sent To  
Notes
2008-09-19 12:22:48DENIED. CHANGE OF OCCUPANCY TO DAYCARE WILL REQUIRE
 PLANS TO MODIFY SHARED BUILDING'S FIRE PROTECTION,
 EGRESS, ACCESSABILITY, ECT. OWNER STATES AN OCCUPANCY
 LOAD OF APPROXIMATELY 90 CHILDREN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-03 Cont ID  
Sent By btrobaug Date 2008-10-03 Time 11:17 Rev Time 0.00
Received By btrobaug Date 2008-10-03 Time 11:02 Sent To  
Notes
2008-10-03 11:17:13 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THERE IS NO APPLICATION WITH THIS PACKAGE. 105.3
 APPLICATION FOR PERMIT. TO OBTAIN A PERMIT, THE
 APPLICANT SHALL FIRST FILE AN APPLICATION THEREFORE IN
 WRITING ON A FORM FURNISHED BY THE BUILDING DEPARTMENT
 FOR THAT PURPOSE. PERMIT APPLICATION FORMS SHALL BE IN
 THE FORMAT PRESCRIBED BY A LOCAL ADMINISTRATIVE BOARD,
 IF APPLICABLE, AND MUST COMPLY WITH THE REQUIREMENTS OF
 SECTION 713.135(5) AND (6), FLORIDA STATUTES.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 3} THERE IS NO ELECTRICAL PLAN SHOWN ON THE PLANS
 SUBMITTED. SUBMIT PLANS INDICATING THE ELECTRICAL
 SYSTEMS COMPLIANCE WITH ALL APPLICABLE CODES.SEE ABOVE
 MENTIONED CODES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-03 Cont ID  
Sent By mwennerg Date 2008-10-03 Time 15:21 Rev Time 0.00
Received By mwennerg Date 2008-10-03 Time 15:21 Sent To  
Notes
2008-10-03 16:09:16***DENIED***
  
 1) SEE BUILDING COMMENTS #3 AND #4 FOR FS AND FAC
 REQUIREMENTS FOR PLAN SUBMITTAL.
  
 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003. ADD NOTE TO
 PLANS
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241. ADD NOTE TO PLANS
  
 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING SPECIFIC TO THIS PROJECT.
  
 5) IS BUILDING CURRENTLY PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM?
  
 6) FIRE ALARM SYSTEM IN ACCORDANCE WITH 101, SEC. 9.6
 IS REQUIRED. ADDITIONALLY, SEPARATE SHOP DRAWINGS AND
 PERMIT REQUIRED PRIOR TO INSTALLATION.
  
 7) PROVIDE LIFE SAFETY SHEET ILLUSTRATING REQUIRED
 MEANS OF EGRESS AND MAXIMUM TRAVEL DISTANCE
 INFORMATION.
  
 8) PROVIDE OCCUPANT LOAD INFORMATION.
  
 9) ILLUSTRATE THE LOCATIONS OF ALL ILLUMINATED EXIT
 SIGNS AND EMERGENCY LIGHTING FACILITIES.
  
 10) EVERY ROOM OR SPACE SHALL BE PROVIDED WITH A RESCUE
 WINDOW UNLESS BUILDING IS PROTECTED BY AN AUTOMATIC
 FIRE SPRINKLER SYSTEM, OR THE ROOM OR SPACE DOOR LEADS
 DIRECTLY TO THE OUTSIDE.
  
 11) EMERGENCY PLANS IN ACCORDANCE WITH 101, SEC 4.8
 SHALL BE PROVIDED AND SHALL BE FORWARDED TO THE BUREAU
 OF FIRE PREVENTION FOR REVIEW AND APPROVAL. (561)
 804-4724
  
 12) ANY DOOR IN A REQUIRED MEANS OF EGRESS SERVING AN
 AREA OF 100 OR GREATER OCCUPANTS SHALL BE PROVIDED WITH
 PANIC OR FIRE EXIT HARDWARE.
  
 13) BATHROOM DOORS SHALL BE DESIGNED TO BE OPENED FROM
 THE OUTSIDE BY STAFF.
  
 14) PLANS SHOW A KITCHEN. PROVIDE INFORMATION AS TO THE
 USE OF THAT AREA REGARDING COOKING. FOODS THAT PRODUCE
 GREASE LADEN VAPORS SHALL BE COOKED UNDER APPROVED
 HOOD/SUPPRESSION PROTECTED EQUIPMENT.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-07 Cont ID  
Sent By mperson Date 2008-10-07 Time 13:40 Rev Time 0.00
Received By mperson Date 2008-09-30 Time 12:09 Sent To PC
Notes
2008-09-30 12:09:18TO "BOB"#9

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-03 Cont ID  
Sent By tgordon Date 2008-10-03 Time 13:31 Rev Time 0.45
Received By tgordon Date 2008-10-03 Time 13:31 Sent To  
Notes
2008-10-03 13:54:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 CHANGE OF OCCUPANCY
 *** DENIED ***
  
 1) PLAN SUBMITTED DOES NOT CONTAIN ENOUGH INFORMATION
 TO DO A PROPER PLAN REVIEW. PLEASE SUBMIT A MECHANICAL
 PLAN THAT SHOWS THE A/C DUCT SYSTEM WITH EXISTING OR
 NEW FIRE DAMPERS IN ALL REQUIRED DUCTS AND AIR TRANSFER
 OPENINGS THAN PENETRATE RATED WALLS FOR SEPARATION OF
 MIXED OCCUPANCIES AND RATED CORRIDORS, PER 2004 FBC/EB
 812.1.2, FBC TABLE 302.3.2 AND FBC/M 607.
  
 2) SHOW ON MECHANICAL PLAN THE OUTDOOR AIR CALCULATIONS
 SO IT MAY BE ADJUSTED FOR THIS OCCUPANCY, PER 2004
 FBC/EB 809.1 AND FBC/M 401.3 AND 403.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-07 Cont ID  
Sent By mperson Date 2008-10-07 Time 08:57 Rev Time 3.00
Received By mperson Date 2008-10-07 Time 08:57 Sent To I
Notes
2008-10-07 11:58:52PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. A PERMIT APPLICATION WAS NOT WITH THE SUBMITTAL. ANY
 OWNER, AUTHORIZED AGENT, OR CONTRACTOR WHO INTENDES TO
 CONSTRUCT ENLARGE, ALTER, REPAIR, MOVE, DEMOLISH, OR
 CHANGE THE OCCUPANCY OF A BUILDING STRUCTURE, SHALL
 FIRST MAKE APPLICATION TO THE BUILDING OFFICIAL AND
 OPTAIN THE REQUIRED PERMIT. PER FBC-2004 CHAPTER 1,
 (W.P.B. AS AMENDED) SECTION 105.1 REQUIRED.
  
 2. DECLARE THE GOVERNING CODE ON THE PLANS (FBC-2004
 WITH 2007 REVISIONS). PER FBC-2004 CHAPTER 1, (W.P.B.
 AS AMENDED) SECTION 106.5 RETENTION OF CONSTRUCTION
 DOCUMENTS.
  
 3. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 4. THE PLAN SUBMITTED DOES NOT CONTAIN ENOUGH
 INFORMATION TO DO A PROPER PLUMBING PLAN REVIEW. PLEASE
 PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN CLEARLY INDICATING ALL PROPOSED CHANGES TO THE
 STRUCTURE. PLEASE KNOW THAT IF THERE IS NEW PROPOSED
 PLUMBING FOR THE STRUCTURE THAT SANITARY AND POTABLE
 WATER RISER DIAGRAMS ARE REQUIRED. PER FBC-2004 CHAPTER
 1, (W.P.B. AS AMENDED) SECTION 106.3.1.3 PLUMBING (3),
 (4), (8), (10), (11), (12), (13).
  
 5. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 AND OCCUPANCY LOAD ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY OF THE GROUP LISTED BELOW.
 DAY CARE (SEE SECTION 313): GROUP D
  
 6. PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES FOR OCCUPANCY GROUP D, ARE
 PER THE FOLLOWING.
  
 A} WATER CLOSETS MALE/FEMALE= 1 PER 50.
  
 B} LAVATORIES MALE/FEMALE= 1 PER 50.
  
 C} DRINKING FOUNTAIN= 1 PER 100.
  
 D} 1 SERVICE SINK.
  
 E} (D) FOR DAY CARE NURSERIES, A MAXIMUM OF ONE BATHTUB
 SHALL BE REQUIRED.
  
 NOTE: PLEASE KNOW THAT THE SUBMITTED FLOOR PLAN DOES
 NOT CLEARLY INDICATE THE REQUIRED DRINKING FOUNTAIN AND
 BATHTUB. PLEASE KNOW THAT ALL PLUMBING FIXTURES SHALL
 BE ACCESSIBLE PER FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION THE
 FOLLOWING SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28.
 11-4.16.3 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 ** 11-4.20 BATHTUBS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.20.2 FLOOR SPACE. (SEE FIGURE 33)
 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.4 GRAB BARS. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.5 CONTROLS. (SEE FIGURE 34)
 11-4.20.6 SHOWER UNIT. SHOWER SPRAY UNIT WITH A HOSE
 MINIMUM 60" LONG USED BOTH AS A FIXED OR HAND HELD
 SHALL BE PROVIDED.
  
 **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 7. PLAN SHEET IS INDICATING A KITCHEN: PLEASE KNOW THAT
 A GREASE INTERCEPTOR MAY BE REQUIREDTO RECIEVE THE
 DRAINAGE FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN
 WASTE LOCATED IN FOOD PREPERATION AREAS. THE MINIMUM
 SIZE GREASE INTERCEPTOR REQUIRED IS 750 GAL. PER
 MUNICIPAL CODE ARTICLE III SECTION 90-124, THE
 EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED AND
 LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE
 UTILITY DEPARTMENT. PLEASE CONTACT HOLLY MCGRATH
 (LABORATORY SUPERVISOR) HER PHONE NUMBER IS (561)
 822-2200 EXT. 2271, HER E-MAIL ADDRESS IS
 [email protected] AND HER FAX NUMBER IS (561) 822-2279.
 NOTE: WRITTEN APPROVAL IS REQUIRED OF THE
 EXISTING/PROPOSED GREASE INTERCEPTOR OR DOCUMENTATION
 THAT A GREASE INTERCEPTOR IS NOT REQUIRED FROM
 ENVIRONMENTAL COMPLIANCE BEFORE A PERMIT CAN BE ISSUED.
  
 8. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **PLEASE KNOW THAT ADDITIONAL COMMENTS MAY APPEAR ON
 THE NEXT REVIEW WHEN A COMPLETE SET OF ARCHITECTURAL
 PLANS ARE SUBMITTED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-06 Cont ID  
Sent By adavila Date 2008-10-06 Time 16:05 Rev Time 0.00
Received By adavila Date 2008-10-06 Time 16:05 Sent To  
Notes
2008-10-06 16:06:27PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. THE SITE PLAN SUBMITTED WITH BUILDING PERMIT NO.
 08080616 DOES NOT MATCH THE SITE PLAN SUBMITTED WITH
 THIS BUILDING PERMIT. PLEASE CLARIFY HOW THE SITE WILL
 BE DEVELOPED/RENOVATED. ALL SITE PLANS, LANDSCAPE
 PLANS, ETC. TO BE APPROVED SHALL SHOW THE SAME
 CONDITIONS.
  
 2. ON SEPTEMBER 25, 2007, THE PLANNING AND ZONING
 DEPARTMENT APPROVED A SET OF SITE PLAN, LANDSCAPE PLAN
 AND PHOTOMETRIC PLAN FOR THE SUBJECT PROPERTY. WHILE
 THE PROPOSED CHANGES TO THE SITE DO NOT REQUIRE A NEW
 DEVELOPMENT APPLICATION TO THE PLANNING AND ZONING
 DEPARTMENT, THE CHANGES DO NEED TO COMPLY WITH ALL
 APPLICABLE REQUIREMENTS OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS ("ZLDRS"). THEREFORE, PROVIDE A
 REVISED SITE PLAN, LANDSCAPE PLAN AND PHOTOMETRIC PLAN
 WITH THIS PERMIT SHOWING COMPLIANCE WITH THE ZLDRS.
  
 PLEASE NOTE THAT IN THE EVENT THIS PERMIT WILL BE FOR
 INTERIOR RENOVATIONS ONLY AND ALL EXTERIOR SITE
 IMPROVEMENTS WILL BE REVIEWED AND APPROVED ON THE
 PERMIT MENTIONED IN COMMENT NO. 1 ABOVE, THE PLANS FOR
 PERMIT NO. 08080616 SHALL BE REVISED TO SHOW PROPOSED
 DAYCARE FACILITY WITH THE OUTDOOR PLAY AREAS.
  
 3. THE REVISED SITE PLAN SHOWS 3 REGULAR PARKING SPACES
 BEING REPLACED BY 2 NEW HANDICAP PARKING SPACES ALONG
 THE EAST PROPERTY LINE. ACCORDING TO THE APPROVED SITE
 PLAN, THE REGULAR PARKING SPACES ALONG THE EAST
 PROPERTY LINE ARE 8.5 FEET IN WIDTH. THREE REGULAR
 PARKING SPACES, WHICH ARE 8.5 FEET WIDE, EACH, DO NOT
 PROVIDE AMPLE SPACE TO ACCOMMODATE THE 2 HANDICAP
 PARKING SPACES WITH A 5 FOOT ACCESS AISLE. PLEASE
 REVISE.
  
 4. PROVIDE AMPLE SPACE ALONG THE SOUTH SIDE OF THE
 6,825 SQUARE FOOT PLAY AREA TO ACCOMMODATE A HEDGE
 BETWEEN THE FENCE AND THE DRIVE AISLE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved