| 2008-09-29 13:16:03 | BUILDING PLAN REVIEW |
| | PERMIT: 08090378 |
| | ADD: 150 CLEARWATER DRIVE |
| | CONT: CATALFUMO |
| | TEL: (561)694-8853 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | BUS SHELTER# 2 |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS SHEET |
| | S-3 NEEDS TO UPDATE SUPPLEMENTS OF THE 2007SUPPLEMENTS. |
| | |
| | 1D) THE PERMIT APPLICATION UNDER ADDRESS IS INDICATED |
| | AS 150 CLEARWATER DRIVE, THIS IS A SITE ADDRESS AND |
| | WILL REQUIRE A SEPERATE ADDRESS FOR THE RESTROOMS. |
| | PLEASE CONTACT JAMES JUDGE AT (561)822-1226, 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 1E) THE PERMIT APPLICATION INDICATES A BUS SHELTER# 1 |
| | TO BE CONSTRUCTED. PLANS SUBMITTED ARE TWO SETS OF A6 & |
| | A7 AND SEVEN 2OF 65 CIVIL DRAWINGS. SINCE THIS WAS NOT |
| | SUBMITTED AS A MASTER PLAN, EACH INDIVIDUAL PERMIT |
| | APPLICATION WILL NEED TO SUBMIT 2 SETS OF ALL |
| | DOCUMENTS. PLEASE PROVIDE THE REQUIED (2) SETS OF PLANS |
| | WITHIN THIS PERMIT APPLICATION FOR COMPLIANCE WITH |
| | MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS |
| | 106.3.5.1.1. |
| | SITE PLAN |
| | OCCUPANCY GROUP REQUIREMENTS SHALL BE DETERMINED |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED PLEASE |
| | PROVIDE THE MINIMUM BUILDING TYPE CONSTRUCTION. TABLE |
| | 503/ TABLE 601 |
| | SOILS CONDITION |
| | BUILDING ENVELOPE COMPONENTS |
| | WIND DESIGN CRITERIA, STRUCTURAL NOTES LOCATED ON SHEET |
| | A3 ARE INDICATED ON SHEET A6 BUT NOT INCLUDED. |
| | |
| | 1F) AS OF 9-29-08 PERMIT FEE S HAVE NOT BEEN PAID, FEES |
| | ARE TO BE PAID AT TIME OF PERMIT APPLICATION. FEES OWED |
| | ARE $780.52,. CITY CODE OF ORDINANCES18.1(D) ALL PERMIT |
| | FEES MUST BE PAID IN FULL AT TIME OF PERMIT |
| | APPLICATION. |
| | |
| | 2) PLEAS E SUBMIT 2 ORIGINALS SIGNED AND SEALED SOILS |
| | REPORTS. 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 3) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE |
| | 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR OF |
| | PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 3A) GLASS WIND BREAK -FOR WIND, LARGE MISSILE TESTING |
| | NOT REQUIED RULE 9B-72 (31) (B) |
| | 3B) ROOFING ASSEMBLIES, UNDERLAYMENTS, ROOF TILE |
| | ADHESIVES, ROOF TILES AND OR ANY PART OF AN INTEGRAL |
| | PART OF ANY ROOFING ASSEMBLY.RULE 9B-72(31)(D). PLEASE |
| | CIRCLE THE METHOD OF ATTACHMENT FOR THE MOMENT OF |
| | OVERTURNING. 1715.2.1. |
| | |
| | 4) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 6) PLANS DO NOT PROVIDE INFORMATION ON TERMITE |
| | TREATMENT AS PER SECTION 1816.1, OR FOR A VAPOR BARRIER |
| | AS REQUIRED IN 1816.1.4. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |