Plan Review Details - Permit 08090363
Plan Review Stops For Permit 08090363
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-04-17 Cont ID  
Sent By jwitmer Date 2009-04-17 Time 16:14 Rev Time 1.33
Received By jwitmer Date 2009-04-17 Time 16:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-04-06 Cont ID  
Sent By jwitmer Date 2009-04-06 Time 16:17 Rev Time 0.77
Received By jwitmer Date 2009-04-06 Time 16:17 Sent To  
Notes
2009-04-06 16:19:19BUILDING PLAN REVIEW
 PERMIT: 08090363
 ADD: 701 BELVEDERE RD
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 APRIL 06/09
 3RD REVIEW
 ACTION: DENIED
  
 1) THE NEW PLANS ARE NOT SIGNED NOR SEALED. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-08 Cont ID  
Sent By jwitmer Date 2009-01-08 Time 11:55 Rev Time 3.55
Received By jwitmer Date 2009-01-08 Time 9.00 Sent To  
Notes
2009-01-08 11:38:21BUILDING PLAN REVIEW
 PERMIT: 08090363
 ADD: 701 BELVEDERE RD
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 JAN 08/09
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2-10) COMPLIED
  
 11A) 13-103.1.1 CODE COMPLIANCE PREPARATION. THE PERSON
 PREPARING THE COMPLIANCE CALCULATION SHALL CERTIFY THAT
 THE PLANS AND SPECIFICATIONS COVERED BY THE
 CALCULATION, OR AMENDMENTS THERETO, ARE IN COMPLIANCE
 WITH CHAPTER 13 OF THE FLORIDA BUILDING CODE. THIS CODE
 ARTICLE STANDS BECAUSE THE PLANS DO NOT MATCH THE
 R-VALUES STATED WITHIN THE DATA INPUT REPORT OF THE
 ENERGY CALCULATIONS.
 THE INPUT DATA REPORT INDICATE YOU ARE TAKING CREDIT
 FOR A R-VALUE OF 12.5 . PLEASE REVIEW CHAPTER 13
 APPENDIX B 2.5.5 SLABS ON GRADE AND THE F- FACTORS FOR
 SLABS-ON-GRADE FLOORS SHALL BE TAKEN FROM TABLE B-26.
 IN REVIEWING THIS TABLE DEPENDING ON THE F-VALUE OF THE
 INSULATION AND WIDTH OF INSULATION TO BE ADDES AT THE
 FLOOR LEVEL. PLEASE CORRELATE PLANS AND ENERGY CALCS .
  
 11B) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-30 Cont ID  
Sent By jwitmer Date 2008-09-30 Time 08:37 Rev Time 3.33
Received By jwitmer Date 2008-09-30 Time 06:47 Sent To  
Notes
2008-09-30 11:17:56BUILDING PLAN REVIEW
 PERMIT: 08090363
 ADD: 701 BELVEDERE RD
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE REVISE SHEET
 A1 TO THE CURRENT 2007 SUPPLEMENTS.
  
 1D) SHETT A-1 UNDER THE HEADING BUILDING DATA WHERE THE
 CURRENT CODES ARE LISTED, PLANS FAIL TO IDENTIFY THE
 2004FBC EXISTING BUILDING WITH 2007 SUPPLEMENTS NOR THE
 LEVEL OF ALTERATION HAS NOT BEEN DECLARED BY THE DESIGN
 PROFESSIONAL 2004 FBC EXIST. SECTION 301.5.
  
 2) SHEET A1 INDICATES A SECTION 4 OF A4 PLANS DO NOT
 PROVIDE WHAT THE HEIGHT DIFFERENCE IS IN THE FRONT CURB
 AND ACCESSIBLE RAMP AREAS. IT CAN NOT BE DETERMINED IF
 THERE IS A GREATER THAN 6" DIFFERENCE IN GRADE THAT
 ENACT 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER
 THAN 6" OR A HORIZONTAL PROJECTION GREATER THAN 72",
 THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 3) SHEET A-1 WALK IN COOLERS & FREEZERS THE TOTAL
 SQUARE FOOTAGE OF THE WALK-IN UNITS IS APPROX 417 SQ
 FT. 2603.4.1.3 LIMITS THE THE AGGREGATE FLOOR AREA TO
 400 SQ FT. PLEASE MODIFY, 2603.4.1.3.
 NOTE THAT THE ACTUAL COOLER AND MECHANICAL EQUIPMENT
 WILL REQUIRE A SEPERATE PERMIT WHERE AS THE REMAINDER
 OF THE REQUIREMENTS OF 2603.4.1.3 WILL NEED TO BE MET.
 SEPERATE REVIEWS WITH ASSOCIATED FEES WILL THEN OCCUR.
  
 4) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 4A) STORM SHUTTERS- THE REPORT SUBMITTED 02-0809.02
 EXPIRED 10/10/07 WILL REQUIRE NEW REPORT RULE 9B-72
 (31) ( E)
 4B) PRE-ENGINEERED A/C STANDS RULE 9B-72(31)(G)
  
 5) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS A COMPLETE INSTALLATION INSTALLATION SCHEDULE
 FOR SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE. PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING.
  
 FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 &
 EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
 A SAMPLE STORM SHUTTER SCHEDULE IS ATTACHED.
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1, ADMINISTRATIVE CODE2004 EDITION AS AMENDED
 BY THE CITY OF WEST PALM BEACH, PROVIDES THE ABILITY
 FOR THE BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 7) BOTH SHEETS A1 & A7 INDICATE A T8 FUTURE DEAL DWAWER
 BUT NO INFORMATION HAS BEEN PROVIDED PRODUCT
 INFORMATION, THE SECURING INTO THE STRUCTURAL SHELL OF
 THE BUILDING.1609.6.1.2. COMPONENTS AND CLADDING.
  
 8) SHEET A-1 MISSING THE REQUIRED 18" BETWEEN THE WATER
 COOLER AND LATCH SIDE OF THE RESTROOM DOOR. 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 9) SHEET A4 DETAIL 2 THE COUNTER HEIGHT IS 36" BUT THE
 COUNTER HEIGHT SHOULD BE 34" SECTION 11-5.2.
  
 10) THE ENRGY CALCULATIONS INDICATE THE USE OF 3"
 ICYNENE INSULATION AT THE CONCRETE DOUBLE TEE ROOF
 SYSTEM PROVIDING A R VALUE OF 12.3. PLEASE REVIEW
 2603.5.2 AND REQUIRED THERMAL BARRIER MEETING THE
 PROVISIONS OF SECTION 2603.4 .
  
 11A) THE ENERGY CALCULATIONS ALSO INDICATE A R-VALUE OF
 5.73 FOR A CONCRETE FLOOR WITH CARPET AND RUBBER
 PADDING. 804.5.1 MINIMUM CRITICAL RADIANT FLUX.
 INTERIOR FLOOR FINISH IN VERTICAL EXITS, EXIT
 PASSAGEWAYS AND EXIT ACCESS CORRIDORS SHALL NOT BE LESS
 THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT LESS THAN
 CLASS II IN GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S.
 IN ALL OTHER AREAS, THE INTERIOR FLOOR FINISH SHALL
 COMPLY WITH THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR, PART
 1630).
  
  
 11B) 11-4.5.3 CARPET . IF CARPET OR CARPET TILE IS USED
 ON A GROUND OR FLOOR SURFACE, THEN IT SHALL BE SECURELY
 ATTACHED; HAVE A FIRM CUSHION, PAD, OR BACKING, OR NO
 CUSHION OR PAD; AND HAVE A LEVEL LOOP, TEXTURED LOOP,
 LEVEL CUT PILE, OR LEVEL CUT/UNCUT PILE TEXTURE. THE
 MAXIMUM PILE THICKNESS SHALL BE ? INCH (13 MM) [SEE
 FIGURE 8 (F)]. EXPOSED EDGES OF CARPET SHALL BE
 FASTENED TO FLOOR SURFACES AND HAVE TRIM ALONG THE
 ENTIRE LENGTH OF THE EXPOSED EDGE. CARPET EDGE TRIM
 SHALL COMPLY WITH SECTION 11-4.5.2 . PLEASE PROVIDE
 MANUFACTURERS INFORMATION ON CARPET AND PAD.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-04-17 Cont ID  
Sent By dpalmer Date 2009-04-17 Time 11:11 Rev Time 0.00
Received By dpalmer Date 2009-04-17 Time 11:11 Sent To  
Notes
2009-04-17 11:17:17** REDLINED PLANS***
  
  
 SPOKE TO ELECTRICAL CONTRACRTOR. WILL PROVIDE FUSED SE
 RATED FUSED SAFETY SWITCH PER NOTES ON PLANS. 240.21

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-03-24 Cont ID  
Sent By dpalmer Date 2009-03-24 Time 16:20 Rev Time 0.00
Received By dpalmer Date 2009-03-24 Time 16:07 Sent To  
Notes
2009-03-24 16:20:37** PLANS DENIED **
 SOME OF THE SAME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: THIS IS A REPEAT REQUEST TO SUBMIT THE
 MANUFACTURES SPECS/CUT SHEETS FOR THE NEW PROPOSED
 TRANSFER SWITCH. BASED ON THE RISER THIS EQUIPMENT MUST
 BE SERVICE ENTRANCE RATED NOT ONLY RATED AS SERVICE
 EQUIPMENT. THIS EQUIPMENT MUST HAVE OVER CURRENT
 PROTECTION AND BE MUST ALSO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
 THERE SEEMS TO BE SOME SORT OF MISPRINT WITH THE RATING
 OF THE EQUIPMENT ALSO. SHOWN AS 1001.
 230.70, 230.71, 230.76, 230.79, 110.9, 110.3, 90.7
  
 2) NOTE: PLEASE SEE THE INPUT DATA REPORT FOR LIGHTING
 FOR EXTERIOR. WHEN USING LIGHTING PER HEALTH, SAFETY
 STATUTES, ORDINANCE, OR REGULATION THIS WILL EXEMPT THE
 LIGHTING AND REMOVE IT FROM THE OVER ALL FIGURE. AS
 THERE IS NO ORDINANCE, STATUTE OR OTHER REGULATIONS
 WHICH REQUIRES THIS LIGHTING, THIS USE MAY NOT BE USED.
 PLEASE ADJUST CALCULATIONS.
 13-415.2, 13-415.2.ABC.1.3.
 LIGHTING IN A RETAIL OCCUPANCY SPECIFIC TO DISPLAY
 AREAS HAS AN ADDITIONAL ALLOWANCE UNDER THE 2004 FBC
 HOWEVER IT IS SPECIFIC TO THE SQUARE FOOTAGE OF THE
 DISPLAY AREA.
  
 3) NOTE: PLEASE SEE NOTES MARKED AS *IMPORTANT* ON THE
 PREVIOUS REVIEW. PLEASE BE SURE TO REMOVE THE OLD
 VOIDED SHEETS FROM SETS AND INSERT THE NEW REVISED
 SHEETS INTO SETS FOR REVIEW AND STAMPING.
  
 4) NOTE: PLEASE SEE THE NEW REVISED SHEETS WHICH WERE
 SUBMITTED ARE NOT SIGNED, DATED OR SEALED BY THE
 DESIGNER OF RECORD. FS 481.221
  
 5) NOTE: PLEASE SEE RISER AS THIS STILL INDICATES AN
 EQUIPMENT GROUNDING CONDUCTOR FROM THE GUTTER TO THE
 NEW TRANSFER SWITCH. PER 250.6, 250.24 THERE CAN NOT BE
 ANY EQUIPMENT GROUNDING CONDUCTORS BEFORE THE FIRST
 MEANS OF DISCONNECT ON A SERVICE. ONLY AFTER THE FIRST
 MEANS OF DISCONNECT IS EQUIPMENT GROUNDING CONDUCTORS
 INSTALLED.
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-01-05 Cont ID  
Sent By dpalmer Date 2009-01-05 Time 15:32 Rev Time 0.00
Received By dpalmer Date 2009-01-05 Time 15:32 Sent To  
Notes
2009-01-05 15:33:01** DENIED 2ND REVIEW **
  
  
 **SEE NEW NOTES BELOW DUE TO REVISED RISER WHICH DID
 NOT CONTAIN SOME OF THESE ITEMS ON PREVIOUS REVIEWED
 PLANS.
  
  
  
 1) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 ON THE NEW PROPOSED SERVICE ENTRANCE RATE TRANSFER
 SWITCH.
 110.3,90.7, ETC
  
 2) NOTE: RISER NOW HAS BEEN REVISED TO INDICATE A #4
 NEUTRAL AS PART OF THE FEEDERS FROM PANEL *A* TO NEW
 SUB PANEL *D*. THIS MUST BE A MISPRINT FOR EQUIPMENT
 GROUNDING CONDUCTOR?
 250
 FBC 106.1.1, FOR CLARITY AND COORDINATION OF PLANS.
  
 3) NOTE: PLEASE ADJUST RISER WITH NEW CONDUCTORS NOW
 BEING SHOWN FROM GUTTER TO THE NE W TRANSFER SWITCH.
 THE NOTES ABOVE REQUEST THE SPECS/CUT SHEETS HOWEVER
 THE RISER INDICATES THE OLD DISCONNECT *C* BEING FED
 FROM TWO LOCATIONS.
 THE RISER ALSO INDICATES AN EQUIPMENT GROUNDING
 CONDUCTOR FROM THE GUTTER TO THE TRANSFER SWITCH WHICH
 IS NOT PERMITTED.250.6,250.24.
 * EQUIPMENT GROUNDING CONDUCTORS* ARE ONLY INSTALLED
 AFTER THE FIRS MEANS OF DISCONNECT.
  
 4) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT TO
 THE FLA COM ENERGY CALCULATIONS SUBMITTED. PART OF THE
 COMMENT IS THE FACT ALL THE INFORMATION ON PLANS NEEDS
 TO COORDINATE WITH THE SUBMITTED INPUT DATA REPORT.
 THIS IS NOT COMPLIANT.
 ONE EXAMPLE: THERE ARE MORE FIXTURES ON THE PLANS FOR
 THE INTERIOR LIGHTING THAN SHOWN ON THE IDR SUBMITTED.
 PLEASE SEE TYPE D, G ETC.
 PLEASE SEE ELECTRICAL PLANS WHICH ALSO CONTAIN A LIGHT
 FIXTURE SYMBOL HOWEVER NO DESIGNATION IS NOTED ALONG
 WITH NO CIRCUITING.
 PLEASE SEE 13-415.2,13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE COORDINATE ALL.
 THIS IS NOT THE ONLY ITEM.
 PLEASE SEE THE SUBMITTED SHEET 4 OF 8 WHICH IDENTIFIES
 THE BUILDING END USES. WHERE DOES THE DESIGN OF 358.30
 AND THE REFERENCE OF 390.30 COME FROM.
 THIS IS NOT LIKE ANY OTHER CALCULATIONS EVER SUBMITTED.
 THE REFERENCE HAS ALWAYS BEEN 100 AND THE DESIGN IS
 DOWN FROM THERE.
 13-101, 13-400.3.A.
 PLEASE SEE 13-401- 13-412 FOR OTHERS.
  
  
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-06 Cont ID  
Sent By dpalmer Date 2008-10-06 Time 15:20 Rev Time 0.00
Received By dpalmer Date 2008-10-06 Time 15:20 Sent To  
Notes
2008-10-06 15:20:50 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FS 526.143 AND PROVIDE BACK UP
 REQUIRED SYSTEM FOR MOTOR FUELING. IF A SYSTEM ALREADY
 EXISTS, PLEASE SHOW SYSTEM AND PROVIDE PERMITTING
 INFORMATION. NO CURRENT RECORDS WERE LOCATED IN OUR
 SYSTEM THAT THIS WORK HAS BEEN DONE. PLEASE SEE THE
 STATUTORY REQUIREMENT AS NOTED.
  
 2) NOTE: PLEASE SEE FBC 13-400.3.A, .3.B, ETC AS THE
 VERSION SUBMITTED FOR ENERGY CALCULATIONS IS NOT
 ADOPTED BY THE FBC. THIS SHOULD BE VERSION 2.5. PLEASE
 GO TO ENERGY GAUGE WEBSITE AS THERE IS A PATCH
 AVAILABLE TO CHANGE TO VERSION 2.5.
  
 3) NOTE: PLEASE SEE 13-101.1. AS THIS IS AN EXISTING
 BUILDING PLEASE PROVIDE HOW METHOD A IS BEING USED AS
 THIS WOULD BE A RENOVATION PER SECTION 202.
 ONLY IF ALL KNOWN COMPONENTS ARE KNOWN WOULD A METHOD A
 BE USED.
 IN EITHER CASE THE SUBMITTED CALCULATIONS ARE NOT CODE
 COMPLIANT. THE INPUT DATA REPORT ATTACHED AS REQUIRED
 IS NOT COMPLETE.
 FOR ONE EXAMPLE: PLEASE SEE THE IDR AS THIS SHOWS NO
 EXTERIOR LIGHTING. THIS SECTION OF THE IDR IS *BLANK*.
 HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY INDICATE
 MANY EXTERIOR FIXTURES?
 PLEASE SEE FBC 13-415.2.ABC.1.3 FOR LIGHTING
 PERFORMANCE CALCULATIONS FOR EXTERIOR.
 PLEASE ALSO SEE FBC 13-415.2.ABC.1.1, .1.2 FOR INTERIOR
 LIGHTING.
  
 FOR EXAMPLE: THE FIXTURE WATTAGES LISTED ON THE IDR ARE
 NOT ALL THE SAME AS SHOWN ON THE FIXTURE LEGEND. THERE
 ARE SEVERAL INCONSISTENCIES.
  
  
 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON ELECTRICAL PLANS AT A MINIMUM.
 2005 NFPA-70
 2003 NFPA-101
 2004 FBC W/2007 REVISIONS.
  
 5) NOTE: ALL LOW VOLTAGE SECURITY CAMERAS ETC WILL BE
 UNDER SEPARATE PERMITS WITH PLANS AND FEES.
  
 6) NOTE: PLEASE COORDINATE ELECTRICAL RISER. AS
 SUBMITTED THERE ARE SEVERAL ITEMS WHICH NEED TO BE
 ADDRESSED.
 THE NEW PANEL *D* IS BEING SHOWN WITH A LOAD WHICH FAR
 EXCEEDS THE RATING OF THE FEEDERS AND BREAKERS SHOWN IN
 PANEL *A*. IN FACT PANEL *A* SHOWS ONLY A 30AMP BREAKER
 AND FEEDERS WHEN IN FACT PANEL *D* HAS A LOAD OF 120.5
 AMPS.
 PLEASE ALSO SEE THE FEEDERS AS NOTED ON PANEL *D* ARE
 SHOWN AS 3/0 WHEN THE RISER SHOWS THESE AS 1/0. IN
 EITHER CASE BOTH OF THESE WOULD BE CODE COMPLIANCE
 BASED ON LOAD HOWEVER COORDINATION IS NEEDED WITH OVER
 CURRENT PROTECTION ETC.
 PLEASE SEE THE FEEDERS NOTED ON PANEL *A* ARE SHOWN AS
 500MCM IN A 3INCH CONDUIT, YET THE RISER SHOWS THE SAME
 CONDUCTORS IN A 2 INCH CONDUIT.
  
 7) NOTE: PLEASE INCLUDE NOTES FOR CONTRACTOR TO LABEL
 ALL MAINS FOR SERVICE PER 230.2E
  
 8) NOTE: PLEASE SHOW ALL EQUIPMENT GROUNDING PATHS/
 METHODS AFTER THE FIRST MEANS OF DISCONNECT.
  
 9) NOTE: PLEASE SEE 210.8B2 AS ALL 15,20AMP 120V
 RECEPTACLES SERVING KITCHEN AREAS WHETHER OR NOT
 FEEDING APPLIANCES OR EQUIPMENT ON THE COUNTER AREAS
 WILL BE REQUIRED TO BE GFI OR GFI PROTECTED WITH CLASS
 A PROTECTION.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED OR INCOMPLETE ON PLANS THERE MAY BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT POSSIBLY
 BE MADE AT THIS TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-03-06 Cont ID  
Sent By mawillia Date 2009-03-06 Time 13:36 Rev Time 0.00
Received By mawillia Date 2009-03-06 Time 13:16 Sent To  
Notes
2009-03-06 13:30:00*****APPROVED*****
  
  
 PLAN SHEETS A-1, A-3, AND E-1 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-14 Cont ID  
Sent By mwennerg Date 2009-01-14 Time 14:09 Rev Time 0.00
Received By mwennerg Date 2009-01-14 Time 14:09 Sent To  
Notes
2009-01-14 14:10:22COMMENTS FROM LAST FIRE REVIEW HAVE BEEN ADDRESSED.
 PLANS WILL BE STAMPED WHEN RETURNED WITH OTHER REVIEW
 COMMENT CORRECTIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-08 Cont ID  
Sent By mwennerg Date 2008-10-08 Time 15:19 Rev Time 0.00
Received By mwennerg Date 2008-10-08 Time 15:19 Sent To  
Notes
2008-10-08 15:49:19***DENIED***
  
 1) THE COOKING OF FOODS THAT PRODUCE GREASE LADEN VAPOR
 IS REQUIRED TO BE PROTECTED BY AN APPROVED
 HOOD/SUPPRESSION SYSTEM. PLEASE PROVIDE INFORMATION
 WITH SUBMITTAL AND IN ADDITION, SEPARATE SHOP DRAWINGS
 AND PERMITS ARE REQUIRED BEFORE INSTALLATION OF
 EQUIPMENT.
  
 2) PROVIDE LOCATIONS OF REQUIRED 2A-10B,C RATED FIRE
 EXTINGUISHERS.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241.
  
 4) IF RAMP MEETS THE REQUIREMENTS FOR HANDRAILS ON BOTH
 SIDES, PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDS IF APPLICABLE.
  
 5) PLEASE DELETE ANY REFERENCE TO FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS IF NOT PART OF THE SCOPE OF THIS
 WORK.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2009-01-28 Cont ID  
Sent By kstevens Date 2009-01-28 Time 14:07 Rev Time 0.00
Received By kstevens Date 2009-01-28 Time 14:07 Sent To  
Notes
2009-01-28 14:08:39SEPARATE GAS PERMIT TO BE SUBMITTED WITH REQUIRED
 INFORMATION BY GAS/PLUMBING CONTRACTOR.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-01-28 Cont ID  
Sent By kstevens Date 2008-09-18 Time 14:05 Rev Time 0.00
Received By kstevens Date 2008-09-18 Time 14:05 Sent To  
Notes
2009-01-28 14:07:42DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 1. SHT P-1 INDICATES GAS PIPING NOTES. A SEPARATE GAS
 PERMIT IS REQUIRED. THE FOLLOWING INFORMATION IS
 REQUIRED TO BE SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-04-14 Cont ID  
Sent By mjacobs Date 2009-04-14 Time 16:18 Rev Time 0.00
Received By mjacobs Date 2009-04-14 Time 16:18 Sent To  
Notes
2009-04-14 16:18:56TO "COMM" BD #5

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-02 Cont ID  
Sent By adarroug Date 2009-03-02 Time 10:20 Rev Time 0.00
Received By adarroug Date 2009-03-02 Time 10:20 Sent To  
Notes
2009-03-02 10:22:54TO "COMM" BD#54

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-19 Cont ID  
Sent By adarroug Date 2008-12-19 Time 08:21 Rev Time 0.00
Received By adarroug Date 2008-12-19 Time 08:21 Sent To  
Notes
2008-12-19 08:30:14TO "COMM" BD#42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-08 Cont ID  
Sent By mwennerg Date 2008-10-08 Time 16:04 Rev Time 0.00
Received By mwennerg Date 2008-09-17 Time 12:13 Sent To  
Notes
2008-09-17 12:16:47TO "COMM" BD#13

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-04-21 Cont ID  
Sent By rkussner Date 2009-04-21 Time 16:04 Rev Time 0.00
Received By rkussner Date 2009-04-21 Time 16:04 Sent To PC
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-03-11 Cont ID  
Sent By rkussner Date 2009-03-11 Time 12:12 Rev Time 0.00
Received By rkussner Date 2009-03-11 Time 11:41 Sent To Z
Notes
2009-03-11 12:45:55***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPONE TO ALL COMMENTS IN WRITING.
 1. REPEAT COMMENT: A TREE ALTERATION PERMIT IS
 REQUIRED. PLEASE SUBMIT TWO COPIES OF THE LANDSCAPE
 PLAN WITH THE APPLICATION. ALL EXISTING TREES SHALL BE
 IDENTIFIED AND THE STATUS (REMOVED, RELOCATED, REMAIN
 IN PLACE) SHALL BE PROVIDED. THERE ARE TWO HEALTHY
 QUEEN PALMS AT THE NORTHEAST CORNER OF THE BUILDING
 THAT HAVE NOT BEEN ACCOUNTED FOR IN ADDITION TO THE
 OTHER TREES THAT WILL BE REMOVED.
  
 2. REPEAT COMMENT: PURSUANT TO SECTION 94-443(E)(1), AT
 LEAST 30 PERCENT OF THE LINEAR FEET AROUND THE EXTERIOR
 OF ALL COMMERCIAL STRUCTURES SHALL BE PLANTED WITH
 TREES, SHRUBS OR HEDGES. THIRTY FEET WAS PROPOSED AND
 NOT THE REQUIRED 30 PERCENT. BECAUSE THERE IS A LACK OF
 FOUNDATION PLANTING, STAFF RECOMMENDS THAT THE HANDICAP
 SPACE BE SHIFTED TO THE SOUTH BY FIVE FEET AND PROVIDE
 A PLANTING AREA IN THE LOCATION OF THE CURRENTLY
 PROPOSED HANDICAP MANEUVERING AREA. THE NEW MANEUVERING
 AREA WOULD BE ADJACENT TO THE PLANTING BED.
  
 3. PURSUANT TO SECTION 94-444 (B), FUEL OIL OR PROPANE
 TANKS AND OTHER MECHANICAL EQUIPMENT SHALL NOT BE
 PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS.
  
 4. PURSUANT TO SECTION 94-443(C)(2), TREES SHALL BE
 PLANTED AT 30-FOOT INTERVALS AND HEDGES SHALL BE
 PLANTED AT TWO-FOOT INTERVALS FOR EACH REQUIRED
 LANDSCAPE BUFFER. A HEDGE SHALL BE INSTALLED ALONG THE
 INTERIOR PERIMETER OF THE LANDSCAPE BUFFER ADJACENT TO
 THE SOUTH AND EAST SIDES OF THE SITE.
  
 5. NO MORE THAN A 1 INCH LAYER OF MULCH SHALL COVER THE
 ROOT BALL OF ANY TREE OR SHRUB. THE THREE INCH LAYER OF
 MULCH IS APPLIED IN THE PLANT BEDS OUTSIDE OF THE
 ROOTBALLS. PLANTS AND TREES SHALL BE PLANTED SLIGHTLY
 ABOVE GRADE TO AVOID RAISING THE SOIL LEVEL AROUND
 THEIR BASE.
  
  
  
  
 IF YOU HAVE ANQ QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-12-30 Cont ID  
Sent By rkussner Date 2008-12-30 Time 11:25 Rev Time 0.00
Received By rkussner Date 2009-03-11 Time 12:12 Sent To  
Notes
2008-12-30 12:20:43***LANDSCAPE REVIEW FAILED***
  
 1. BECAUSE TREES WILL BE REMOVED, A TREE ALTERATION
 PERMIT IS REQUIRED. THE APPLICATION IS AVAILABLE AT THE
 FRONT DESK OF THE PLANNING AND ZONING DEPARTMENT.
 PLEASE SUBMIT (2) COPIES OF THE LANDSCAPE PLAN WITH THE
 APPLICATION. ALL EXISTING TREES SHALL BE IDENTIFIED AND
 THE STATUS (REMOVED, RELOCATED, REMAIN IN PLACE) SHALL
 BE PROVIDED. THERE ARE TWO HEALTHY QUEEN PALMS AT THE
 NORTHEAST CORNER OF THE BUILDING THAT HAVE NOT BEEN
 ACCOUNTED FOR.
  
 2. THE LIVE OAKS AND QUEEN PALMS LOCATED ALONG THE
 SOUTH AND EAST PERIMETER OF THE SITE ARE NOT FLORIDA #1
 GRADE OR BETTER WHICH IS A REQUIREMENT. THE OAKS HAVE
 BEEN PREVIOUSLY HATRACKED AND THE PALMS ARE NOT HEALTHY
 OR OF PROPER SIZE. PERHAPS, THE CITY COULD ALLOW (2) OR
 (3) OF THEM TO REMAIN BUT THEY WOULD NEED TO BE
 RELOCATED TO A LESS CONSPICUOUS LOCATION AND GROUPED
 TOGETHER.
  
 3. NEW TREES WILL BE REQUIRED ALONG THE EAST AND SOUTH
 PERIMETER OF THE SITE TO REPLACE THE EXISTING TREES
 THAT WILL NEED TO BE REMOVED. THERE ARE OVERHEAD WIRES
 ALONG THE SOUTH PERIMETER OF THE SITE. YOU SHALL COMPLY
 WITH FPL'S "PLANT THE RIGHT TREE IN THE RIGHT PLACE"
 GUIDELINES THAT RESTRICT THE SPECIES OF TREE THAT CAN
 BE PLANTED NEAR OR UNDER POWER LINES. IN ADDITION,
 THERE SHALL BE CONTINUITY WHEN SELECTING THE SPECIES.
 IF YOU DECIDE TO USE A PALM GROUPING, THEN ALL TREES
 WITHIN THE GROUPING SHALL BE OF THE SAME SPECIES. THE
 SAME APPLIES FOR PROPOSED TREES TO BE PLANTED ALONG
 EITHER THE EAST OR SOUTH SIDES OF THE SITE.
  
 4. PURSUANT TO SECTION 94-443(E)(1), AT LEAST 30
 PERCENT OF THE LINEAR FEET AROUND THE EXTERIOR OF ALL
 COMMERCIAL STRUCTURES SHALL BE PLANTED WITH TREES,
 SHRUBS OR HEDGES. BECAUSE THERE IS A LACK OF FOUNDATION
 PLANTING, STAFF RECOMMENDS THAT THE HANDICAP SPACE BE
 SHIFTED TO THE SOUTH BY (5) FEET AND PROVIDE A PLANTING
 AREA IN THE LOCATION OF THE CURRENTLY PROPOSED HANDICAP
 MANEUVERING AREA. THE NEW MANEUVERING AREA WOULD BE
 ADJACENT TO THE PLANTING BED. PLEASE NOTE THAT THERE IS
 AN ICE MACHINE THAT WILL NEED TO BE RELOCATED ELSEWHERE
 TO ALLOW PASSAGE TO THE FRONT DOOR FROM THE WEST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-04-27 Cont ID  
Sent By rregueir Date 2009-04-27 Time 15:33 Rev Time 0.00
Received By rregueir Date 2009-04-27 Time 15:33 Sent To B
Notes
2009-04-27 16:20:57SENT TO LMARTINEZ FOR PROCESSING

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-04-07 Cont ID  
Sent By hmoser Date 2009-04-07 Time 14:32 Rev Time 0.00
Received By hmoser Date 2009-04-07 Time 14:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-03-26 Cont ID  
Sent By rregueir Date 2009-03-26 Time 10:32 Rev Time 0.00
Received By rregueir Date 2009-03-26 Time 10:32 Sent To  
Notes
2009-03-26 10:34:31ALL PREVIOUS REVIEW COMMENTS HAVE BEEN ADDRESSED.
 HOWEVER, THE NEW M-1 SHEET WITH CORRECTIONS WAS NOT
 SIGNED AND SEALED BY THE DESIGNER OF RECORD. PLEASE
 MAKE SURE ALL SHEETS PREPARED BY THE DESIGNER ARE
 PROPERLY SIGNED, SEALED AND DATED IN ACCORDANCE WITH
 FAC RULE 61G-15.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-02-01 Cont ID  
Sent By rregueir Date 2009-02-01 Time 10:50 Rev Time 0.00
Received By rregueir Date 2009-02-01 Time 10:04 Sent To PC
Notes
2009-02-01 10:50:02REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY:
  
 1. *PREVIOUS COMMENT* PAGE M-1 FLOOR PLAN SHOWS DUCT
 SMOKE DETECTORS ON THE RETURN SIDE OF AHU 1 AND AHU 2.
 DUCT DETECTORS SHALL BE ON THE SUPPLY SIDE OF THE FANS
 IN ACCORDANCE WITH FBCM 606.2.1.
  
 *COMMENT #1 PARTIALLY ADDRESSED*: SOMKE DETECTORS HAVE
 BEEN RELOACTED TO SUPPLY SIDE OF THE SYSTEM AS REQUIRED
 BY FBCM 606.2.1. HOWEVER, THE DETECTOR FOR AHU 1 IS
 SHOWN DOWNSTREAM OF THE FIRST AND LARGEST SUPPLY
 BRANCH. SMOKE DETECTORS SHALL BE INSTALLED IN A
 LOCATION WHERE THEY WILL MONITOR THE ENTIRE AIRFLOW
 CONVEYED BY THE SYSTEM IN ACCORDANCE WITH FBCM 606.3.
 IN OTHER WORDS, THE DETECTOR MUST BE LOCATED BEFORE OR
 UPSTREAM OF THE FIRST SUPPLY BRANCH. SHOW THIS DETECTOR
 ON PLANS IN A LOCATION WHICH IS IN COMPLIANCE WITH THIS
 FBCM 606.2.1 AND 606.3. PLEASE SHOW COMPLIANCE ON
 PLANS, DO NOT JUST QUOTE THE CODE SECTION IN ACCORDANCE
 WITH FBCB 106.1.1.
  
 2. *PREVIOUS COMMENT* OUTSIDE AIR INTAKES FOR AHU-1 AND
 AHU-2 SHALL BE PROVIDED WITH SHUTOFF DAMPER CONTROLS IN
 ACCORDANCE WITH FBCB 13-409.1.ABC.3.3.
  
 *COMMENT #2 PARTIALLY ADDRESSED*: ARE MOTORIZED OR
 MANUAL BACKDRAFT DAMPERS TO BE INSTALLED AT THIS
 LOCATION? IF A MOTORIZED DAMPER IS TO BE USED,
 PROVISIONS FOR POWER AND CONTROL WILL BE REQUIRED.
 PLEASE SHOW ON PLANS HOW COMPLIANCE WITH FBCB
 13-407.1.ABC.3.3 IS TO BE ACHIEVED RATHER THAN QUOTING
 THE SECTION PER FBCB 106.1.1.
  
 3. OK
  
 4. OK
  
 5. *PREVIOUS COMMENT* NO INSTALLATION DETAILS PROVIDED
 IN PLANS. PROVIDE DETAILED INSTALLATION INSTRUCTIONS
 FOR ALL MECHANICAL EQUIPMENT AND APPLIANCES WHICH ARE
 TO BE INSTALLED OUTDOORS. ALSO INCLUDE SUPPORTING
 DOCUMENTATION FOR WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH FBCM 301.13. ALSO
 REQUIRED IS DATA FROM ALL OUTDOOR APPLIANCE
 MANUFACTURERS SHOWING THEIR APPLIANCES ARE DESIGNED AND
 CONSTRUCTED TO RESIST WIND PRESSURES IN ACCORDANCE WITH
 THIS SECTION. THIS INCLUDES ALL CONDENSING UNITS AND
 HOOD EXHAUST/MAKE-UP AIR FANS.
  
 *COMMENT ADDRESSED*: HOWEVER, WIND RESISTANCE
 REQUIREMENTS FOR ALL OUTDOOR APPLIANCES AND EQUIPMENT
 NOT COVERED BY THIS PERMIT MUST BE DEMONSTRATED AT TIME
 OF SEPARATE PERMIT APPLICATION SUCH AS THE KITCHEN
 EXHAUST FAN, MAKEUP AIR FAN, REMOTE CONDENSERS FOR
 WALK-IN COOLERS.
  
 6. OK. SUBMIT SEPARAT PERMIT APPLICATIONS WITH FULL
 DOCUMENTATION FOR THE KITCHEN HOOD AND VENTILATION
 EQUIPMENT. ALSO, A SEPARATE PERMIT APPLICATION IS
 REQUIRED FOR THE KITCHEN HOOD FIRE SUPPRESSION SYSTEM.
  
 7. OK SUBJECT TO FIELD INSPECTOR'S VERIFICATION.
  
 8. OK
 NOTE: MECHANICAL ONLY REVIEWS FOR MECHANICAL PORTIONS
 OF THE ENERGY CALCULATIONS. PLEASE SEE OTHER TRADE
 REVIEWS FOR POSSIBLE ADDITIONAL ENERGY CODE RELATED
 COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-29 Cont ID  
Sent By rregueir Date 2008-09-29 Time 14:01 Rev Time 0.00
Received By rregueir Date 2008-09-29 Time 11:27 Sent To  
Notes
2008-09-29 14:01:26REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-1 FLOOR PLAN SHOWS DUCT SMOKE DETECTORS ON
 THE RETURN SIDE OF AHU 1 AND AHU 2. DUCT DETECTORS
 SHALL BE ON THE SUPPLY SIDE OF THE FANS IN ACCORDANCE
 WITH FBCM 606.2.1.
  
 2. OUTSIDE AIR INTAKES FOR AHU-1 AND AHU-2 SHALL BE
 PROVIDED WITH SHUTOFF DAMPER CONTROLS IN ACCORDANCE
 WITH FBCB 13-409.1.ABC.3.3.
  
 3. PLAN SHOWS SECONDARY DRAIN LINES FROM AHU-1 AND
 AHU-2 TO TERMINATE AT SOFFIT ON EAST SIDE OF BUILDING.
 THIS DOES NOT APPEAR TO BE A CONSPICUOUS LOCATION. THE
 AUXILIARY PAN DRAIN SHALL DISCHARGE TO A CONSPICUOUS
 POINT OF DISPOSAL TO ALERT OCCUPANTS IN THE EVENT OF A
 STOPPAGE OF THE PRIMARY DRAIN IN ACCORDANCE WITH FBCM
 307.2.3(1).
  
 4. HVAC SPECIFICATION #19 CALLS FOR CONDENSATE DISPOSAL
 AT ROOF DRAINS WHILE FLOOR PLAN CALLS FOR A DRYWELL.
 PLEASE COORDINATE FLOOR PLANS WITH SPECIFICATIONS TO
 ACCURATELY REFLECT THE SCOPE OF WORK IN ACCORDANCE WITH
 FBCB 106.1.1. CONDENSATE FROM ALL COOLING COILS AND
 EVAPORATORS SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET
 TO AN APPROVED PLACE OF DISPOSAL IN ACCORDANCE WITH
 BFCM 307.2.1.
  
 5. NO INSTALLATION DETAILS PROVIDED IN PLANS. PROVIDE
 DETAILED INSTALLATION INSTRUCTIONS FOR ALL MECHANICAL
 EQUIPMENT AND APPLIANCES WHICH ARE TO BE INSTALLED
 OUTDOORS. ALSO INCLUDE SUPPORTING DOCUMENTATION FOR
 WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT
 AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM
 301.13. ALSO REQUIRED IS DATA FROM ALL OUTDOOR
 APPLIANCE MANUFACTURERS SHOWING THEIR APPLIANCES ARE
 DESIGNED AND CONSTRUCTED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH THIS SECTION. THIS INCLUDES ALL
 CONDENSING UNITS AND HOOD EXHAUST/MAKE-UP AIR FANS.
  
 6. NO INFORMATION WAS PROVIDED WITH THESE PLANS RELATED
 TO THE COMMERCIAL KITCHEN HOOD SYSTEM. PROVIDE SEPARATE
 PLANS AND PERMIT APPLICATIONS FOR EACH OF THE FOLLOWING
 SYSTEMS. SEPARATE PERMITS ARE REQUIRED FOR THE
 FOLLOWING: HOODS, HOOD SUPPRESSION SYSTEMS, WALK-IN
 COOLERS. NO PORTIONS OF HOOD OR WALK-IN COOLER SYSTEMS
 HAVE BEEN REVIEWED FOR CODE COMPLIANCE AT THIS TIME.
  
 7. AHU-1 AND AHU-2 DO NOT APPEAR, BASED ON THE FLOOR
 PLANS, TO BE FULLY ACCESSIBLE FOR SERVICE AND
 REPLACEMENT. CLEARANCES AROUND APPLIANCES TO ELEMENTS
 OF PERMANENT CONSTRUCTION, INCLUDING OTHER INSTALLED
 EQUIPMENT AND APPLIANCES, SHALL BE SUFFICIENT TO ALLOW
 INSPECTIONS, SERVICE, REPAIR OR REPLACEMENT WITHOUT
 REMOVING SUCH ELEMENTS OF PERMANENT CONSTRUCTION IN
 ACCORDANCE WITH FBCM 306.1. PLEASE SHOW HOW THESE
 APPLIANCES ARE TO BE ACCESSED FOR SERVICE AND/OR
 REPLACEMENT.
  
 8. ENERGY CALCULATIONS: A SYSTEM SIZING SUMMARY HAS
 BEEN PROVIDED IN LIEU OF COOLING LOAD CALCULATIONS AS
 ALLOWED UNDER FBCB 13-407.1.ABC.1, EXCEPTION #1. THE
 SYSTEM SIZING SUMMARY SHALL BE SIGNED AND SEALED BY THE
 DESIGNER OF RECORD IN ACCORDANCE WITH THIS EXCEPTION.
 NOTE: MECHANICAL ONLY REVIEWS FOR MECHANICAL PORTIONS
 OF THE ENERGY CALCULATIONS. PLEASE SEE OTHER TRADE
 REVIEWS FOR POSSIBLE ADDITIONAL ENERGY CODE RELATED
 COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-01-28 Cont ID  
Sent By kstevens Date 2009-01-28 Time 14:19 Rev Time 0.00
Received By kstevens Date 2009-01-28 Time 14:19 Sent To  
Notes
2009-01-28 14:20:50SEPARATE GAS PERMIT REQUIRED -- PLANS AND INFORMATION
 INDICATED ON SHT P-1 TO BE SUBMITTED WITH GAS
 APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-19 Cont ID  
Sent By kstevens Date 2008-09-19 Time 08:11 Rev Time 0.00
Received By kstevens Date 2008-09-18 Time 16:01 Sent To  
Notes
2008-09-19 13:53:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 CITY WPB MUNICIPAL CODE
  
 1. SHT A0-1 SHOWS A NEW GREASE INTERCEPTOR. THE GREASE
 INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT,
 INDUSTRIAL PRETREATMENT DIVISION. PLEASE CONTACT MR.
 WILLIAM ROBERTS ENVIRONMENTAL COMPLIANCE AT (561)
 822-2272, FAX (561) 659-7458 OR E-MAIL
 [email protected]. ARTICLE III SECTION 90-124.
  
 2. SHT A0-1A DEMOLITION PLAN. PER SECTION 704.5 IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS ARE
 PROHIBITED. ALL DEMO'D - CAPPED PIPING SHALL REMAIN
 UNCOVERED UNTIL INSPECTED BY THE FIELD INSPECTOR.
  
 3. SHT A-1 CODE STANDARDS SHALL INCLUDE THE 2007
 REVISIONS.
  
 4. SHT P-1 THE 3 COMPARTMENT SINK DETAIL SHOWS THE AIR
 GAP AS 3". PER SECTION 802.2.1 THE MINIMUM AIR GAP IS
 TWICE THE EFFECTIVE OPENING OF THE INDIRECT PIPING. THE
 INDIRECT PIPING IS INDICATED AS 2". THE MINIMUM AIR GAP
 REQUIRED IS 4".
  
 5. SHT P-2 SANITARY RISER DIAGRAM, THE FLOOR DRAIN IN
 THE TOILET ROOM IS NOT VENTED AS INDICATED. SECTION
 901.2.1. THE FLOOR DRAIN SHOULD BE CONNECTED TO THE LAV
 RISER. -- SHOW THE PIPE SIZES FOR THE TOILET FIXTURES,
 (W/C & FLOOR DRAIN). TABLES 709.1 & 710.1(1)(2).
  
 6. SHT P-2 SANITARY RISER DIAGRAM, THE PIPING TO THE
 URINAL IS AN "S" TRAP WHICH IS NOT APPROVED. SECTION
 1002.3. PLEASE SHOW THE DRAIN LINE FROM THE URINAL
 CONNECTING STRAIGHT INTO THE STACK WITHOUT THE VERTICAL
 DROP AS INDICATED ON THE RISER. (SEE RED LINE
 CORRECTION ON ONE SET OF PLANS).
  
 7. SHT P-2 SANITARY RISER DIAGRAM, CLEANOUTS ARE
 REQUIRED NEAR THE JUNCTION OF THE BUILDING DRAIN AND
 THE BUILDING SEWER PER SECTION 708.3.5. -- ALSO TWO WAY
 CLEANOUTS ARE REQUIRED AT THE AFFLUENT PIPING & THE
 EFFLUENT PIPING OF THE GREASE INTERCEPTOR PER UTILITY
 STANDARD FOR GREASE INTERCEPTORS.
  
 8. SHT P-2 WATER ISOMETRIC RISER DIAGRAM. A WATER
 HAMMER ARRESTOR IS REQUIRED ON THE SUPPLY PIPE FOR THE
 ICE MAKER INSTALLED NEAR THE FIXTURE IN AN EFFECTIVE
 RANGE PER PDI-HW 201. PLEASE SHOW ON RISER DIAGRAM.
 SECTION 604.9.
  
 9. SHT P-1 INDICATES GAS PIPING NOTES. A SEPARATE GAS
 PERMIT IS REQUIRED. THE FOLLOWING INFORMATION IS
 REQUIRED TO BE SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2009-04-28 Cont ID  
Sent By jroach Date 2009-04-28 Time 09:29 Rev Time 0.00
Received By jroach Date 2009-04-28 Time 09:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2009-04-21 Cont ID  
Sent By jroach Date 2009-04-21 Time 09:36 Rev Time 0.00
Received By jroach Date 2009-04-21 Time 09:36 Sent To  
Notes
2009-04-21 09:50:28ZONING PLAN REVIEW
  
 PERMIT NO.: 08090363
 ADDRESS: 701 BELVEDERE
 CONTRACTOR/CONTACT: DAVID
 TELEPHONE NO.: 662.3377
 SCOPE OF REVIEW: RESUBMITTAL OF RENOVATED GAS
 STATION/CONVENIENCE STORE. REVISIONS TO SHEETS LP-1,
 LP-2, TP-1, AO-1, M1, EO.1, E1, AND E2.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 THE FOLLOWING IS/ARE REPEAT COMMENT(S):
  
 1) PURSUANT TO THE FINAL ORDER FOR ZBA CASE NO. 3212,
 THE CITY OF WEST PALM BEACH POLICE DEPARTMENT - CRIME
 PREVENTION UNIT, SHALL REVIEW AND APPROVE THE
 CONSTRUCTION DRAWINGS TO ENSURE THE ADHERENCE TO
 GENERALLY-ACCEPTED CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED) PRINCIPLES. PLEASE PROVIDE
 WRITTEN CONFIRMATION FROM KELLY CARSILLO, CRIME
 PREVENTION OFFICE, THAT SUCH APPROVAL HAS BEE ISSUED.
 MS. CARSILLO MAY BE REACHED AT (561) 822-1620. YOUR
 RESPONSES INDICATE THAT A LETTER WAS PROVIDED, HOWEVER,
 NO LETTER WAS INCLUDED IN THE RESUBMITTAL PACKAGE.
  
 2) THE ORIGINAL LANDSCAPE PLAN IDENTIFIED BOUGAINVILLEA
 ON THE EXTERIOR OF THE FENCE SURROUNDING THE MECHANICAL
 EQUIPMENT. THIS WAS REQUIRED AS AN ALTERNATE TO PUTTING
 IN A SOLID OPAQUE FENCE. THE REVISED PLANS HAVE REMOVED
 THIS PLANTING MATERIAL. THE LANSCAPE PLANS SHALL BE
 REVISED TO SHOW THE INSTALLATION OF THE LANDSCAPE
 SCREENING, OR A SOLID OPAQUE FENCE SHALL BE PROVIDED.
 THE LANDSCAPE PLAN DOES SHOW BOUGAINVILLEA ALONG A
 MAJORITY OF THE CHAINLINK FENCE, BUT NOT IN FRONT OF
 THAT PORTION OF THE FENCE THAT SURROUNDS THE MECHANCIAL
 EQUIPMENT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2009-03-10 Cont ID  
Sent By jroach Date 2009-03-10 Time 20:07 Rev Time 0.00
Received By jroach Date 2009-03-10 Time 20:07 Sent To  
Notes
2009-03-10 20:11:09ZONING PLAN REVIEW
  
 PERMIT NO.: 08090363
 ADDRESS: 701 BELVEDERE
 CONTRACTOR/CONTACT: DAVID
 TELEPHONE NO.: 662.3377
 SCOPE OF REVIEW: RESUBMITTAL OF RENOVATED GAS
 STATION/CONVENIENCE STORE. REVISIONS TO SHEETS AO-1,
 M-1, EO.1, E-1, E-2, LP-1, LP-2, AND TP-1
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 THE FOLLOWING IS/ARE REPEAT COMMENT(S):
  
 1) PURSUANT TO THE FINAL ORDER FOR ZBA CASE NO. 3212,
 THE CITY OF WEST PALM BEACH POLICE DEPARTMENT - CRIME
 PREVENTION UNIT, SHALL REVIEW AND APPROVE THE
 CONSTRUCTION DRAWINGS TO ENSURE THE ADHERENCE TO
 GENERALLY-ACCEPTED CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED) PRINCIPLES. PLEASE PROVIDE
 WRITTEN CONFIRMATION FROM KELLY CARSILLO, CRIME
 PREVENTION OFFICE, THAT SUCH APPROVAL HAS BEE ISSUED.
 MS. CARSILLO MAY BE REACHED AT (561) 822-1620. YOUR
 RESPONSES INDICATE THAT A LETTER WAS PROVIDED, HOWEVER,
 NO LETTER WAS INCLUDED IN THE RESUBMITTAL PACKAGE.
  
 THE FOLLOWING IS/ARE NEW COMMENT(S) BASED UPON
 MODIFICATIONS THAT WERE MADE ON THE REVISED SHEET(S):
  
 1) THE ORIGINAL LANDSCAPE PLAN IDENTIFIED BOUGAINVILLEA
 ON THE EXTERIOR OF THE FENCE SURROUNDING THE MECHANICAL
 EQUIPMENT. THIS WAS REQUIRED AS AN ALTERNATE TO PUTTING
 IN A SOLID OPAQUE FENCE. THE REVISED PLANS HAVE REMOVED
 THIS PLANTING MATERIAL. THE LANSCAPE PLANS SHALL BE
 REVISED TO SHOW THE INSTALLATION OF THE LANDSCAPE
 SCREENING, OR A SOLID OPAQUE FENCE SHALL BE PROVIDED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2008-12-24 Cont ID  
Sent By jroach Date 2008-12-24 Time 11:16 Rev Time 0.00
Received By jroach Date 2008-12-24 Time 11:16 Sent To  
Notes
2008-12-24 11:41:08ZONING PLAN REVIEW
  
 PERMIT NO.: 08090363
 ADDRESS: 701 BELVEDERE ROAD
 CONTRACTOR/CONTACT: DAVE - GRUBER HALL CORP.
 TELEPHONE NO.: (561) 662-3377
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PURSUANT TO THE FINAL ORDER FOR ZBA CASE NO. 3212,
 THE CITY OF WEST PALM BEACH POLICE DEPARTMENT - CRIME
 PREVENTION UNIT, SHALL REVIEW AND APPROVE THE
 CONSTRUCTION DRAWINGS TO ENSURE THE ADHERENCE TO
 GENERALLY-ACCEPTED CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED) PRINCIPLES. PLEASE PROVIDE
 WRITTEN CONFIRMATION FROM KELLY CARSILLO, CRIME
 PREVENTION OFFICE, THAT SUCH APPROVAL HAS BEE ISSUED.
 MS. CARSILLO MAY BE REACHED AT (561) 822-1620.
  
 2) PURSUANT TO THE FINAL ORDER FOR ZBA CASE NO. 3212,
 LIGHTING SHALL NOT EXCEED 0.5 FOOT CANDLES WHEN
 MEASURED FROM THE ADJACENT RESIDENTIAL ZONING DISTRICT.
 SHEET E0.1 SHOWS LEVELS EXTENDING UP TO 2.4
 FOOTCANDLES. THE PLANS PROVIDE A NOTE REGARDING
 MITIGATION BY THE EXISTING FENCE, HOWEVER, WILL THIS
 FENCE RESULT IN LEVELS OF 0.5 FOOTCANDLES OR LESS?
 PLEASE CLARIFY.
  
 3) THE SITE PLAN AND THE LANDSCAPE PLAN DO NOT
 CORRESPOND REGARDING THE SIZE OF THE SCREENED
 MECHANICAL AREA AT THE NORTHWEST CORNER OF THE
 BUILDING. THE SITE PLAN SHOWS A MUCH LARGER ENCLOSURE
 AND APPEARS TO CONFLICT WITH SOME OF THE PROPOSED
 LANDSCAPING. PLEASE ENSURE THAT ALL PLANS MATCH
 ACCORDINGLY. ADDITIONALLY, THE SITE DATA TABLE MAY NEED
 TO BE ADJUSTED AS A PORTION OF THIS AREA IS NO LONGER
 PROPOSED TO BE LANDSCAPING.
  
 THE FOLLOWING ITEMS DO NOT NEED TO BE CORRECTED, BUT
 ARE SIMPLY NOTES REGARDING THE PROJECT:
  
 A) THE OWNER WILL BE RESPONSIBLE FOR ROLLING THE
 DUMPSTER TO A SUITABLE LOCATION FOR PICK-UP BY THE
 SANITATION TRUCK AND RETURNED TO THE ENCLOSURE UPON
 PICK-UP.
  
 B) ALL SIGNAGE SHALL BE SUBMITTED UNDER SEPARATE
 PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By bpowell Date 2008-09-26 Time 16:49 Rev Time 0.00
Received By bpowell Date 2008-09-26 Time 16:49 Sent To  
Notes
2008-09-26 16:48:461. THE PARKING DETAIL SHALL BE CORRECTED TO SHOW THAT
 THE PARKING SPACES ARE DOUBLE STRIPED, PER SECTION
 94-485(G) REQUIRED OFF-STREET PARKING SPACES SHALL BE
 DELINEATED BY FOUR INCH WHITE DOUBLE STRIPED LINES.
 PLEASE SEE THE ATTACHED DETAIL.
 2. THE LOCATION OF THE GREASE TRAP WILL CONFLICT WITH
 THE PLACEMENT OF THE DAHOON HOLLY TREES.
  
 IF YOU HAVE ANY QUESTIONS OR COMMENTS PLEASE CONTACT;
 BOBBY POWELL JR., PLANNER, [email protected], (561)
 822-1401.