Plan Review Details - Permit 08090349
| Plan Review Stops For Permit 08090349 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-10-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-10-27 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-10-27 |
Time |
16:52 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-09-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-09-26 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-09-26 |
Time |
07:05 |
Sent To |
FIRE |
|
| Notes |
| 2008-09-26 07:11:00 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON | | | THE PLANS, MUST SIGN AND SEAL THE PLAN PER | | | 481.221(1)(B)FS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-10-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-28 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-10-28 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2008-10-28 14:03:24 | 1) WORK SHALL COMPLY WITH NFPA 101, 2003 SEC. | | | 7.2.1.6.2. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-10-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-02 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-10-02 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2008-10-02 14:40:41 | ***DENIED*** | | | | | | 1) WORK SHALL COMPLY WITH NFPA 101, 2003 SEC. | | | 7.2.1.6.2. | | | | | | 2) PROVIDE MANUFACTURER SPECIFICATION SHEETS FOR ACCESS | | | CONTROL EQUIPMENT. | | | | | | 3) PLEASE SEE ELECTRICAL RECVIEW COMMENT #1 REGARDING | | | DESIGN PROFESSIONAL REQUIREMENTS. | | | | | | 4) ADDRESS SHALL BE DISPLAYED ON ALL SUBMITTED SHEETS. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-10-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-23 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-23 |
Time |
09:34 |
Sent To |
E |
|
| Notes |
| 2008-10-23 09:35:07 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-10-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-02 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-09-17 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2008-09-17 09:47:44 | TO "E" BOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy