Plan Review Details - Permit 08090338
Plan Review Stops For Permit 08090338
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-12-22 Cont ID  
Sent By jgomez Date 2008-12-22 Time 16:45 Rev Time 0.00
Received By jgomez Date 2008-12-22 Time 16:44 Sent To PC
Notes
2008-12-22 16:52:19RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW SECOND
 CHECKLIST CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 FLORIDA STATUTE 713.13.
 ***NOTE: THIS MAY BE PROVIDED LATER AT TIME OF PERMIT
 PICK UP.
  
 2- PROVIDE CERTIFICATE OF AUTHORIZATION NUMBER FOR PALM
 COAST STRUCTURAL FIRM AS REQUIRED BY SEC.
 61G15-23.002(2) OF ENGINEERS FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 471 FLORIDA STATUTE. (REPEAT COMMENT).
 SEE ATTACHED COPY OF CERTIFICATE OF AUTHORIZATION
 REQUIREMENTS.
  
 3- FRENCH DOORS PRODUCT APPROVAL NOA 06-1121.15
 SUBMITTED IS FOR SMALL MISSILE IMPACT PROTECTION. NEED
 TO PROVIDE PRODUCT APPROVAL FOR LARGE MISSILE IMPACT
 PROTECTION AS REQUIRED BY SEC. R301.2.1.2 OF 2004
 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-29 Cont ID  
Sent By jgomez Date 2008-09-29 Time 10:53 Rev Time 0.00
Received By jgomez Date 2008-09-29 Time 10:53 Sent To Z
Notes
2008-09-29 11:21:19RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 FLORIDA STATUTE 713.13.
 ***NOTE: THIS MAY BE PROVIDED LATER AT TIME OF PERMIT
 PICK UP.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 3- PROVIDE CERTIFICATE OF AUTHORIZATION NUMBER FOR PALM
 COAST STRUCTURAL FIRM AS REQUIRED BY SEC.
 61G15-23.002(2) OF ENGINEERS FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 4- ENGINEER TO PROVIDE TITLE BLOCK WITH ALL HIS
 INFORMATION AS REQUIRED BY SEC. 61G15-23.002(2) OF
 ENGINEERS FLORIDA ADMINISTRATIVE CODE AND CHAPTER 471
 FLORIDA STATUTE.
  
 5- ENERGY CALCULATIONS CALL FOR R30 ATTIC INSULATION,
 WHILE PLANS CALL FOR R-19 INSULATION. REVISE PLANS AS
 REQUIRED TO MATCH THE ENERGY CALCULATIONS.
  
 6- FRENCH DOORS PRODUCT APPROVAL NOA 06-1121.15
 SUBMITTED IS FOR SMALL MISSILE IMPACT PROTECTION. NEED
 TO PROVIDE PRODUCT APPROVAL FOR LARGE MISSILE IMPACT
 PROTECTION AS REQUIRED BY SEC. R301.2.1.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7 ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3 CITY AMENDMENTS TO FBC 2004.
  
 8- ENERGY CALCULATIONS:
 A) REVISE TOTAL SQUARE FOOTAGE. SEE PLANS FOR
 DIMENSIONS AND REVISE AS REQUIRED.
 B) COMPLETE CLIMATE ZONE ON TOP OF FORM.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-12-16 Cont ID  
Sent By btrobaug Date 2008-12-16 Time 13:31 Rev Time 0.00
Received By btrobaug Date 2008-12-16 Time 11:20 Sent To M
Notes
2008-12-16 13:21:40 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:THE SAME COMMENTS FROM THE PREVIOUS REVIEW
 WHERE NOT RESPONDED TO, PLEASE REMOVE ALL OLD OR VOIDED
 SHEETS AND REPLACE WITH CORRECTED ONES WHEN
 RESUBMITTING. INCLUDE THEM SEPARATELY TO EXPEDITE THE
 REVIEW PROCESS. RESPOND TO REVIEW COMMENTS IN WRITING.
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). INDICATE THAT CIRCUIT ON
 THE PANEL SCHEDULE, AND THE GFI'S ON THE FLOOR PLAN***
 NOT IN THE PANEL SCHEDULE
  
 3} A TITLE BLOCK FOR THE ENGINEER WITH INFORMATION PER
 61G15-23.002(2) FAC. IS REQUIRED***THE CERTIFICATE OF
 AUTHORIZATION NUMBER MUST APPEAR IN THE COMPANY TITLE
 BLOCK..
  
 4} NEW COMMENT THIS SET OF PLANS: RECEPTACLE SPACING
 MUST COMPLY WITH 210.52(A)(1) AND 210.52(A)(2). 2005
 NEC*** INDICATE COMPLIANCE ON THE PLAN
  
 5} 210.70(A)(2)(B) FOR DWELLING UNITS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER, AT
 LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL
 ACCESS. A VEHICLE DOOR IN A GARAGE SHALL NOT BE
 CONSIDERED AS AN OUTDOOR ENTRANCE OR EXIT*** THESE
 LIGHTS WERE ON THE EXISTING BUILDING , BUT NEED TO BE
 SHOWN ON THE "NEW ELECTRIC PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-25 Cont ID  
Sent By tgordon Date 2008-09-25 Time 08:29 Rev Time 0.00
Received By btrobaug Date 2008-09-25 Time 16:20 Sent To B
Notes
2008-09-25 16:30:49 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). INDICATE THAT CIRCUIT ON
 THE PANEL SCHEDULE, AND THE GFI'S ON THE FLOOR PLAN.
  
 2} 210.8(A)(7) LAUNDRY, UTILITY, AND WET BAR SINKS ?
 WHERE THE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT)
 OF THE OUTSIDE EDGE OF THE SINK MUST BE GFI PROTECTED.
  
 3} A TITLE BLOCK FOR THE ENGINEER WITH INFORMATION PER
 61G15-23.002(2) FAC. IS REQUIRED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-08 Cont ID  
Sent By adarroug Date 2008-12-08 Time 16:02 Rev Time 0.00
Received By adarroug Date 2008-12-08 Time 16:02 Sent To Z
Notes
2008-12-08 16:02:55TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-29 Cont ID  
Sent By jgomez Date 2008-09-29 Time 11:22 Rev Time 0.00
Received By jgomez Date 2008-09-15 Time 15:06 Sent To  
Notes
2008-09-15 15:06:52TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-12-18 Cont ID  
Sent By hmoser Date 2008-12-18 Time 09:31 Rev Time 0.00
Received By hmoser Date 2008-12-18 Time 09:31 Sent To B
Notes
2008-12-18 09:34:2812/18/08
 WALL UNITS ON PLANS NO MECHANICAL PERMIT REQUIRED
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-16 Cont ID  
Sent By tgordon Date 2008-09-16 Time 08:12 Rev Time 0.40
Received By tgordon Date 2008-09-16 Time 08:12 Sent To E
Notes
2008-09-16 08:13:57PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) THE PLANS WERE SIGNED AND SEALED BY AN ENGINEER
 (MICHAEL F. PADULA) INFORMATION MISSING FROM TITLE
 BLOCK.
 SEE FAC 61G15-23.002 (2) A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) THE ENERGY CALCULATIONS ARE CALLING FOR R-30
 INSULATION IN THE ATTIC, THE PLANS ARE SHOWING R-19.
 PLEASE CORRECT PER 2004 FBC 13-103.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-12-17 Cont ID  
Sent By kstevens Date 2008-12-17 Time 12:15 Rev Time 0.00
Received By kstevens Date 2008-12-17 Time 12:15 Sent To M
Notes
2008-12-17 12:21:23DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. OK NOTICE GIVEN.
 4. OK
 5. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-17 Cont ID  
Sent By mperson Date 2008-09-17 Time 15:30 Rev Time 0.00
Received By mperson Date 2008-09-17 Time 15:30 Sent To E
Notes
2008-09-17 16:54:41PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 1 OF 2, SANITARY PLUMBING RISER: THE FOLLOWING
 ITEMS NEED CORRECTING PER THE FBC-2004 PLUMBING
 SECTIONS.
  
 A} THE 1-1/2" WASTE ARM FOR THE PROPOSED LAVATORY IS TO
 FAR FROM THE VENT. AN 1-1/2" WASTE ARM WITH AN 1-1/2"
 TRAP CAN ONLY BE 5' FROM THE VENT. A 2" WASTE ARM WITH
 AN 1-1/2" TRAP CAN ONLY BE 6' FROM THE VENT. PLEASE
 KNOW THAT PER 1/4" = 1' SCALE THE DEVELOPED LENGTH OF
 THE LAVATORY WASTE ARM IS ABOUT 7'. PER TABLE 906.1
 MAXIMUM DISTANCE OF FIXTURE TRAP FROM VENT.
  
 B} THE PROPOSED SINK IS INDICATING AN ISLAND VENT.
 PLEASE REFERENCE THE FOLLOWING CODE SECTIONS AND COMPLY
 FOR THE ISLAND VENT ALSO PLEASE REFERENCE FIGURE 913.2
 ISLAND FIXTURE VENT ATTACHED TO THESE COMMENTS FOR THE
 RESUBMITTAL.
  
 SECTION 913.2 VENT CONNECTION.
 THE ISLAND FIXTURE VENT SHALL CONNECT TO THE FIXTURE
 DRAIN AS REQUIRED FOR AN INDIVIDUAL OR COMMON VENT. THE
 VENT SHALL RISE VERTICALLY TO ABOVE THE DRAINAGE OUTLET
 OF THE FIXTURE BEING VENTED BEFORE OFFSETTING
 HORIZONTALLY OR VERTICALLY DOWNWARD. THE VENT OR BRANCH
 VENT FOR MULTIPLE ISLAND FIXTURE VENTS SHALL EXTEND TO
 A MINIMUM OF 6 INCHES (152 MM) ABOVE THE HIGHEST ISLAND
 FIXTURE BEING VENTED BEFORE CONNECTING TO THE OUTSIDE
 VENT TERMINAL.
  
 SECTION 913.3 VENT INSTALLATION BELOW THE FIXTURE FLOOD
 LEVEL RIM.
 THE VENT LOCATED BELOW THE FLOOD LEVEL RIM OF THE
 FIXTURE BEING VENTED SHALL BE INSTALLED AS REQUIRED FOR
 DRAINAGE PIPING IN ACCORDANCE WITH CHAPTER 7 , EXCEPT
 FOR SIZING. THE VENT SHALL BE SIZED IN ACCORDANCE WITH
 SECTION 916.2 . THE LOWEST POINT OF THE ISLAND FIXTURE
 VENT SHALL CONNECT FULL SIZE TO THE DRAINAGE SYSTEM.
 THE CONNECTION SHALL BE TO A VERTICAL DRAIN PIPE OR TO
 THE TOP HALF OF A HORIZONTAL DRAIN PIPE. CLEANOUTS
 SHALL BE PROVIDED IN THE ISLAND FIXTURE VENT TO PERMIT
 RODDING OF ALL VENT PIPING LOCATED BELOW THE FLOOD
 LEVEL RIM OF THE FIXTURES. RODDING IN BOTH DIRECTIONS
 SHALL BE PERMITTED THROUGH A CLEANOUT.
  
 NOTE: IT IS SUGGESTED THAT AN AIR ADMITTACE VALVE BE
 USED FOR THE PROPOSED SINK. PER SECTION 917 AIR
 ADMITTANCE VALVES.
  
 C} CLEARLY INDICATE THAT A TWO-WAY CLEANOUT WILL BE
 INSTALLED AT THE JUNCTION OF THE BUILDING DRAIN AND
 BUILDING SEWER. PER SECTION 708.3.5 JUNCTION OF
 BUILDING DRAIN AND BUILDING SEWER.
  
 2. INFORMATION MISSING FROM TITLE BLOCK ON ALL SHEETS.
 SEE FAC 61G15-23.002 (2) A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 3. PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT
 IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE -
 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY.. PER FS
 713.13 (2): IF THE IMPROVEMENT DESCRIBED IN THE NOTICE
 OF COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90
 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID
 AND OF NO FURTHER EFFECT.
  
 4. DECLARE THE GOVERNING CODE (FBC-2004 WITH 2007
 REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 5. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-12-12 Cont ID  
Sent By mcruz Date 2008-12-12 Time 12:29 Rev Time 0.00
Received By mcruz Date 2008-12-12 Time 12:16 Sent To E
Notes
2008-12-12 12:19:13NOTE: ACCESSORY STRUCTURE SHALL NOT BE UTILIZED AS A
 SEPARATE DWELLING UNIT AND SHALL NOT CONTAIN A KITCHEN
 OR ANY 220 CONNECTIONS. NO RENTAL LICENSE SHALL BE
 APPROVED FOR THIS STRUCTURE.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-30 Cont ID  
Sent By mcruz Date 2008-09-30 Time 11:32 Rev Time 0.00
Received By mcruz Date 2008-09-30 Time 11:26 Sent To  
Notes
2008-09-30 11:32:40***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-304(B)(2): REAR SETBACK
 IS FIVE FEET MINIMUM. THE SURVEY SHOWS IT IS CURRENTLY
 AT 4 FEET. ANY DEVIATION FROM THE AFOREMENTIONED SHALL
 BE APPROVED BY THE ZONING BOARD OF APPEALS. CONTACT THE
 PLANNING DEPARTMENT AT (561) 822-1435 FOR THE VARIANCE
 APPLICATION PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  