Plan Review Details - Permit 08090337
Plan Review Stops For Permit 08090337
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-02-05 Cont ID  
Sent By jwitmer Date 2009-02-05 Time 11:08 Rev Time 0.77
Received By jwitmer Date 2009-02-05 Time 11:08 Sent To  
Notes
2009-02-05 11:10:41RESION
 "E" 1-14-09 SHEETS A-1, A2 RELOCATED WALLS IN ROOMS 101
 & 113.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-04 Cont ID  
Sent By jwitmer Date 2008-11-04 Time 14:48 Rev Time 0.77
Received By jwitmer Date 2008-11-04 Time 14:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-07 Cont ID  
Sent By jwitmer Date 2008-10-07 Time 11:29 Rev Time 0.88
Received By jwitmer Date 2008-10-07 Time 11:29 Sent To  
Notes
2008-10-07 11:44:15BUILDING PLAN REVIEW
 PERMIT: 08090337
 ADD: 1601 FORUM PLACE# 400
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B)INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS THE
 COVER- SHEET REFERENCED STANDARDS INDICATES THE 2006
 REVISIONS PLEASE CORRECT.
  
 2) SHEET A-3 ACCESSIBLITY NOTES: THE ACCESSIBILITY NOTE
 FOR THE SINK BASE CABINET DOES NOT MAKE IT CLEAR THAT
 THE DOORS BENEATH THE SINK ARE TO BE REMOVED TO MAKE
 THE SINK AN ACCESSIBLE SINK FOR A FRONT APPROACH.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-19 Cont ID  
Sent By dpalmer Date 2009-02-19 Time 14:59 Rev Time 0.00
Received By dpalmer Date 2009-02-19 Time 14:59 Sent To  
Notes
2009-02-19 14:59:39REV E-2 AND 3

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-04 Cont ID  
Sent By dpalmer Date 2008-11-04 Time 16:21 Rev Time 0.00
Received By dpalmer Date 2008-11-04 Time 16:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-06 Cont ID  
Sent By dpalmer Date 2008-10-06 Time 16:22 Rev Time 0.00
Received By dpalmer Date 2008-10-06 Time 16:22 Sent To  
Notes
2008-10-06 16:22:48 
 ** DENIED REVIEW **
  
 1) NOTE: BASED ON MECHANICAL COMMENTS THERE WILL BE A
 NEED TO REVISE ELECTRICAL PLANS FOR DUCT SMOKE
 DETECTORS.
  
 2) NOTE: THE OVER CURRENT PROTECTION FROM PANEL *H* TO
 TRANSFORMER IS TOO HIGH PER 450.3
 PLEASE SEE 240.6 FOR THE NEXT HIGHER STANDARD.
 PLANS CALL FOR RE-USING A 45K TRANSFORMER.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-02-19 Cont ID  
Sent By mwennerg Date 2009-02-19 Time 15:50 Rev Time 0.00
Received By mwennerg Date 2009-02-19 Time 15:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-04 Cont ID  
Sent By mawillia Date 2008-11-04 Time 16:52 Rev Time 0.00
Received By mawillia Date 2008-11-04 Time 16:34 Sent To  
Notes
2008-11-04 16:52:10*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-1, A-2, A-4, FP-1, AND E-2 &
 E-3 WERE STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-21 Cont ID  
Sent By mawillia Date 2008-10-21 Time 15:20 Rev Time 0.00
Received By mawillia Date 2008-10-21 Time 14:21 Sent To  
Notes
2008-10-21 15:19:55*****DENIED*****
  
  
 1. FLORIDA FIRE PREVENTION CODE 2004 EDITION SHALL BE
 REFERENCED, NOT 2002 AS LISTED IN THE REFERENCED
 STANDARDS ON COVER SHEET T.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH DAY OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH
 ACCESS TO / EGRESS FROM THE SAID FLOOR OR THE BUILDING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-28 Cont ID  
Sent By adarroug Date 2009-01-28 Time 10:36 Rev Time 0.00
Received By adarroug Date 2009-01-28 Time 10:36 Sent To  
Notes
2009-01-28 10:42:01TO "COMM" BD#51

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-11-03 Time 09:45 Rev Time 0.00
Received By adarroug Date 2008-11-03 Time 09:45 Sent To  
Notes
2008-11-03 09:49:04TO "COMM" BD#31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-21 Cont ID  
Sent By mawillia Date 2008-10-21 Time 14:21 Rev Time 0.00
Received By mawillia Date 2008-09-15 Time 14:54 Sent To  
Notes
2008-09-15 14:56:53TO "COMM" BD#42

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-02-21 Cont ID  
Sent By rregueir Date 2009-02-21 Time 17:38 Rev Time 0.00
Received By rregueir Date 2009-02-21 Time 17:37 Sent To PC
Notes
2009-02-21 17:38:10REVISED M-2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-15 Cont ID  
Sent By rregueir Date 2008-11-15 Time 14:51 Rev Time 0.00
Received By rregueir Date 2008-11-15 Time 14:33 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-23 Cont ID  
Sent By rregueir Date 2008-09-23 Time 11:12 Rev Time 0.00
Received By rregueir Date 2008-09-22 Time 16:57 Sent To  
Notes
2008-09-23 11:12:16REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-2: FLOOR PLANS SHOWS DUCT SMOKE DETECTOR ONLY
 ON HP-5. HOWEVER, ALL HEAT PUMPS IN THIS SPACE SHARE A
 COMMON RETURN AIR PLENUM. THEREFORE, EACH UNIT SHALL BE
 PROTECTED BY DUCT SMOKE DETECTOR IN ACCORDANCE WITH
 FBCM 606.2.2.
 NOTE: DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH FBCM
 606.4.1.
  
 2. OUTSIDE AIR INTAKES SHALL BE PROVIDED WITH SHUTOFF
 DAMPER CONTROLS IN ACCORDANCE WITH FBCB
 13-409.1.ABC.3.3.
  
 3. EACH HYDRONIC HEAT PUMP SHALL HAVE A TWO-POSITION
 AUTOMATIC VALVE INTERLOCKED TO SHUT OFF WATER FLOW WHEN
 THE COMPRESSOR IS OFF IN ACCORDANCE WITH FBCB
 13-411.1.ABC.1.4.
  
 4. PAGE M-3 CEILING DIFFUSER DETAIL PLACES A MAXIMUM
 LENGTH LIMIT OF 8 FEET FOR FLEXIBLE DUCTS. SEVERAL FLEX
 DUCTS ON FLOOR PLAN (PAGE M-2) ARE SHOWN TO BE WELL IN
 EXCESS OF THIS LIMIT. PLEASE COORDINATE DETAILS AND
 FLOOR PLANS AND CLARIFY THE INTENT. FBCM 603.1 AND FBCB
 106.1.1
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-11-14 Cont ID  
Sent By kstevens Date 2008-11-14 Time 07:39 Rev Time 0.00
Received By kstevens Date 2008-11-14 Time 07:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-17 Cont ID  
Sent By kstevens Date 2008-09-17 Time 07:17 Rev Time 0.00
Received By kstevens Date 2008-09-16 Time 12:57 Sent To  
Notes
2008-09-17 07:52:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
  
 1. SHT T REFERENCE STANDARDS SHALL INCLUDE THE 2007
 REVISIONS TO THE 2004 FLORIDA BUILDING CODE.
  
 2. SHT A-1 DEMO NOTES #4. PLEASE SHOW WHERE THE
 PLUMBING WASTE LINES ARE TO BE CAPPED. IN THE REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5. ALL DEMO'D/CAPPED LINES
 SHALL BE INSPECTED PRIOR TO COVERING.
  
 3. SHT A-3 NOTE FOR BREAK ROOM SINK INDICATES CABINET
 DOORS AT THE SINK. THIS IS NOT APPROVED AS DOORS SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE. THE SINK SHALL BE ACCESSIBLE, NOT ADAPTABLE.
 CLEAR FLOOR SPACE SHALL BE UNOBSTRUCTED. SECTION 11-3.
 PLEASE DELETE NOTE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  