Plan Review Details - Permit 08090322
Plan Review Stops For Permit 08090322
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-01-20 Cont ID  
Sent By rmcdouga Date 2009-01-20 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2009-01-20 Time 16:51 Sent To  
Notes
2009-01-20 16:53:11REVISED SHEET A2,A4,A5,S1,S2,S3,S4 AND S5 ARE OK. ONLY
 5 OF THE 8 SHEETS WERE REVISED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-12-17 Cont ID  
Sent By rmcdouga Date 2008-12-17 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2008-12-17 Time 16:24 Sent To  
Notes
2008-12-17 15:00:162004 FBC W/2007 REVISIONS
 ADDITION
  
 REVISION IS DENIED BY BUILDING
  
 1) THE REVISED PLANS DO NOT SPECIFY THE SIZE AND
 SPECIES OF WOOD THAT IS REQUIRED FOR THE CEILING JOISTS
 IN THE PORTION OF THE ADDITION WITH THE FLAT CEILING.
 R802.2.2
  
 2) SPECIFY THE SPECIES OF WOOD REQUIRED FOR THE
 RAFTERS. R802.2.3
  
 3) THE BUILDING AND WALL SECTIONS ON ARCHITECTURAL
 SHEETS A4 AND A5 SHOULD BE REVISED TO SHOW THE
 CONVENTIONAL ROOF FRAMING AT 16" OC RATHER THAN THE
 SCISSOR TRUSSES AT 24" OC. R801.2
  
 4) THE REVISED DETAIL 3 ON S-3 SPECIFIES VCT2 ANCHORS
 AT 48" OC AT THE PIGGY BACK RAFTERS. HOW WILL THIS WORK
 AS THE RAFTERS WILL NOT HAVE A BOTTOM CORD. A 2 X
 NAILED TO THE TOP OF THE EXISTING TRUSSES AT THE VALLEY
 FOR THE RAFTERS TO BEAR ON OR 2 X BLOCKING NAILED
 BETWEEN THE RAFTERS AT THE VALLEY WILL BE REQUIRED. THE
 RAFTER WILL NEED TO BE ANCHORED TO THE EXISTING
 TRUSSES. PLEASE REVISE. R802.2.4 AND R802.2.2.9.1
  
 5) SPECIFY WHERE THE EXTERIOR WALL SECTION DETAIL IN
 THE 8-1/2" X 11" DRAWING OCCURS. AN EXISTING FOOTING IS
 SHOWN AT THE EXTERIOR WALL. THIS CONDITION DOES NOT
 APPEAR TO BE INDICATED BY THE FOUNDATION PLAN ON SHEET
 S-1. R401.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-21 Cont ID  
Sent By amorse Date 2008-10-21 Time 14:47 Rev Time 1.00
Received By amorse Date 2008-10-21 Time 14:47 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-27 Cont ID  
Sent By amorse Date 2008-09-27 Time 10:30 Rev Time 4.00
Received By amorse Date 2008-09-27 Time 07:56 Sent To PC
Notes
2008-09-27 08:12:25 
  
 DENIED
  
 1) PROVIDE SUB-CLASSIFICATION TO THE CONSTRUCTION TYPE
 V (A OR B) ON SHEET SP-1, ASSUMED NON PROTECTED TYPE VB
 THEREFORE 1HR PROTECTION OF EXTERIOR WALLS ETC. IS NOT
 REQUIRED, SEE TABLE 601 FBC.
  
 2) PLEASE CORRECT THE DESIGN CRITERIA, SHEET SP-1 IS
 EXPOSURE C AND THE FOUNDATION PLAN ON S-1 AND COMPONENT
 & CLADDING ON S-4 ARE BOTH 140MPH EXPOSURE B.
  
 3) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*.
  
 4) THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES.
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ 230.68 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 6) PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER
 R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES, 2'-6"
 POCKET DOOR MAY NOT MAKE THIS REQUIREMENT.
  
 7) SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD.
  
 8) TWO SHEET A-6 IN PLAN SETS PLEASE CORRECT
 ARCHITECTURAL DETAIL SHEET PER DRAWING LIST TO A-5.
  
 9) PROVIDE NEW TO EXISTING FOUNDATION AND STEM WALL
 CONNECTION DETAIL OR NOTE ON FOUNDATION PLAN.
  
 10) DOES EXISTING FOUNDATION AT COLUMN LOCATION GET CUT
 OUT AND REMOVED FOR NEW FOUNDATION OR IS THE NEW COLUMN
 BASE POURED BENEATH EXISTING IF IT DOES NOT MEET
 REQUIRED 18" WIDTH.
  
 11) SECTION THROUGH LVL BEAM ON S-3 HAS INCORRECT SHEET
 NUMBER
  
 12) DETAIL 4/S-3 DOES NOT STATE HANGER TYPE AT
 OUTLOOKER TO TRUSS CONNECTION
  
 13) ADDITIONAL PERMIT WILL BE REQUIRED FOR NEW FENCE AT
 SOUTHWEST CORNER OF BUILDING PLEASE SEE ATTACHED PERMIT
 APPLICATION INFORMATION. PER SURVEY THE FENCE IS NOT IN
 AN EASEMENT AND ONLY REQUIRES THE CITY OF WEST PALM
 BEACH WATER UTILITIES DEPT. RELEASE.
  
 14) THE PRODUCT APPROVAL FOR THE HORIZONTAL SLIDERS HAS
 BEEN REVISED WITH THE STATE (FL 242-R7) AND THE
 MIAMI-DADE NOA (07-0815.09) THAT IS USED AS THE
 VALIDATION, PLEASE PROVIDE UPDATED APPROVAL
  
 15) SUBMIT A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-09-26 Cont ID  
Sent By btrobaug Date 2008-09-26 Time 13:14 Rev Time 0.00
Received By btrobaug Date 2008-09-26 Time 13:13 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-10-31 Cont ID  
Sent By mperson Date 2008-10-31 Time 08:09 Rev Time 0.30
Received By mperson Date 2008-10-31 Time 08:09 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-10-15 Cont ID  
Sent By mperson Date 2008-10-15 Time 11:36 Rev Time 0.30
Received By mperson Date 2008-10-15 Time 11:36 Sent To Z
Notes
2008-10-15 11:59:16GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 DUE TO THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON
 SHEET P-2 THE FOLLOWING CORRECTIONS/INFORMATION ARE
 REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE
 AND THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE..
 **NOTE: THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON
 SHEET P-2 DOES NOT INDICATE THE CORRESPONDING LENGTH TO
 CUT SECTION OF PIPE TO THE NEW RANGE RISER.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
 **NOTE: THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON
 SHEET P-2 DOES NOT INDICATE THE GAS PIPE SIZES TO THE
 NEW RANGE.
  
 3. SHEET P-2 GAS ISOMETRIC: THE GAS PIPE SIZE OF 3/4"
 TO THE NEW INST. HOT (TANKLESS WATER HEATER) IS SIZED
 WRONG. PER TABLE 402.4(2) SCH. 40 METALLIC PIPE, WITH A
 LONGEST LENGTH OF 40' AND WITH 189,000 BTU'S THE GAS
 PIPING TO THE NEW INST. HOT (TANKLESS WATER HEATER)
 SHALL BE 1". PLEASE REFERENCE FBC-2004 FUEL GAS TABLE
 402.4(2) ATTACHED TO THESE COMMENTS INDICATING THIS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2008-09-26 Cont ID  
Sent By mperson Date 2008-09-26 Time 16:38 Rev Time 0.30
Received By mperson Date 2008-09-26 Time 16:38 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-01-08 Cont ID  
Sent By adarroug Date 2009-01-08 Time 15:53 Rev Time 0.00
Received By adarroug Date 2009-01-08 Time 15:53 Sent To B
Notes
2009-01-08 15:53:33TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-08 Cont ID  
Sent By adarroug Date 2008-12-08 Time 16:13 Rev Time 0.00
Received By adarroug Date 2008-12-08 Time 16:13 Sent To B
Notes
2008-12-08 16:13:56TO "LMARTINEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-30 Cont ID  
Sent By adarroug Date 2008-10-30 Time 15:49 Rev Time 0.00
Received By adarroug Date 2008-10-30 Time 15:49 Sent To G
Notes
2008-10-30 15:49:39TO "MPERSON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-14 Cont ID  
Sent By adarroug Date 2008-10-14 Time 12:35 Rev Time 0.00
Received By adarroug Date 2008-10-14 Time 12:35 Sent To P
Notes
2008-10-14 12:36:40TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-24 Cont ID  
Sent By adarroug Date 2008-09-24 Time 08:23 Rev Time 0.00
Received By adarroug Date 2008-09-24 Time 08:23 Sent To E
Notes
2008-09-24 08:23:40TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-09-27 Time   Rev Time 0.00
Received By adarroug Date 2008-09-15 Time 14:30 Sent To  
Notes
2008-09-15 14:30:47TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-09-16 Cont ID  
Sent By tgordon Date 2008-09-16 Time 12:19 Rev Time 0.45
Received By tgordon Date 2008-09-16 Time 12:19 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-10-31 Cont ID  
Sent By mperson Date 2008-10-31 Time 08:07 Rev Time 0.30
Received By mperson Date 2008-10-31 Time 08:07 Sent To G
Notes
2008-10-31 08:09:10****************PROVISO****************
 PER FBC-2004 PLUMBING SECTION 604.9 WATER HAMMER. A
 WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED.
 NOTE: A WATER-HAMMER ARRESTOR IS REQUIRED ON THE HOT
 WATER TO THE NEW DISHWASHER.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-15 Cont ID  
Sent By mperson Date 2008-10-15 Time 11:28 Rev Time 0.30
Received By mperson Date 2008-10-15 Time 11:28 Sent To G
Notes
2008-10-15 11:35:37****************PROVISO****************
 PER FBC-2004 PLUMBING SECTION 604.9 WATER HAMMER. A
 WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED.
 NOTE: A WATER-HAMMER ARRESTOR IS REQUIRED ON THE HOT
 WATER TO THE NEW DISHWASHER.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By mperson Date 2008-09-26 Time 16:13 Rev Time 0.45
Received By mperson Date 2008-09-26 Time 16:13 Sent To G
Notes
2008-09-26 16:31:42PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-1, 1ST FLOOR PLUMBING PLAN AND SHEET P-2
 SANITARY ISOMETRIC RISER: THE WASHING MACHINE AND
 DOUBLE BOWL KITCHEN SINK WITH DISHWASHER MUST DRAIN
 DOWNSTREAM OF THE EXISTING WET VENTED BATHROOM.
 NOTE: PER FBC-2004 PLUMBING SECTION 909.1 WET VENT
 PERMITTED. ANY COMBINATION OF FIXTURES WITHIN TWO
 BATHROOM GROUPS LOCATED ON THE SAME FLOOR LEVEL ARE
 PERMITTED TO BE VENTED BY A WET VENT. THE WET VENT
 SHALL BE CONSIDERED THE VENT FOR THE FIXTURES AND SHALL
 EXTEND FROM THE CONNECTION OF THE DRY VENT ALONG THE
 DIRECTION OF THE FLOW IN THE DRAIN PIPE TO THE MOST
 DOWNSTREAM FIXTURE DRAIN CONNECTION TO THE HORIZONTAL
 BRANCH DRAIN. ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-21 Cont ID  
Sent By mcruz Date 2008-10-21 Time 12:01 Rev Time 0.00
Received By mcruz Date 2008-10-21 Time 12:01 Sent To B
Notes
2008-10-21 12:01:45ROUTED TO LUIS MARTINEZ

Review Stop Z ZONING
Rev No 1 Status P Date 2008-09-23 Cont ID  
Sent By mcruz Date 2008-09-23 Time 11:28 Rev Time 0.00
Received By mcruz Date 2008-09-23 Time 11:28 Sent To I
Notes
***NONE***