| Plan Review Stops For Permit 08090322 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-01-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-01-20 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-01-20 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2009-01-20 16:53:11 | REVISED SHEET A2,A4,A5,S1,S2,S3,S4 AND S5 ARE OK. ONLY | | | 5 OF THE 8 SHEETS WERE REVISED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-12-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-12-17 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-12-17 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2008-12-17 15:00:16 | 2004 FBC W/2007 REVISIONS | | | ADDITION | | | | | | REVISION IS DENIED BY BUILDING | | | | | | 1) THE REVISED PLANS DO NOT SPECIFY THE SIZE AND | | | SPECIES OF WOOD THAT IS REQUIRED FOR THE CEILING JOISTS | | | IN THE PORTION OF THE ADDITION WITH THE FLAT CEILING. | | | R802.2.2 | | | | | | 2) SPECIFY THE SPECIES OF WOOD REQUIRED FOR THE | | | RAFTERS. R802.2.3 | | | | | | 3) THE BUILDING AND WALL SECTIONS ON ARCHITECTURAL | | | SHEETS A4 AND A5 SHOULD BE REVISED TO SHOW THE | | | CONVENTIONAL ROOF FRAMING AT 16" OC RATHER THAN THE | | | SCISSOR TRUSSES AT 24" OC. R801.2 | | | | | | 4) THE REVISED DETAIL 3 ON S-3 SPECIFIES VCT2 ANCHORS | | | AT 48" OC AT THE PIGGY BACK RAFTERS. HOW WILL THIS WORK | | | AS THE RAFTERS WILL NOT HAVE A BOTTOM CORD. A 2 X | | | NAILED TO THE TOP OF THE EXISTING TRUSSES AT THE VALLEY | | | FOR THE RAFTERS TO BEAR ON OR 2 X BLOCKING NAILED | | | BETWEEN THE RAFTERS AT THE VALLEY WILL BE REQUIRED. THE | | | RAFTER WILL NEED TO BE ANCHORED TO THE EXISTING | | | TRUSSES. PLEASE REVISE. R802.2.4 AND R802.2.2.9.1 | | | | | | 5) SPECIFY WHERE THE EXTERIOR WALL SECTION DETAIL IN | | | THE 8-1/2" X 11" DRAWING OCCURS. AN EXISTING FOOTING IS | | | SHOWN AT THE EXTERIOR WALL. THIS CONDITION DOES NOT | | | APPEAR TO BE INDICATED BY THE FOUNDATION PLAN ON SHEET | | | S-1. R401.2 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-10-21 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-10-21 |
Time |
14:47 |
Rev Time |
1.00 |
| Received By |
amorse |
Date |
2008-10-21 |
Time |
14:47 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-09-27 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-09-27 |
Time |
10:30 |
Rev Time |
4.00 |
| Received By |
amorse |
Date |
2008-09-27 |
Time |
07:56 |
Sent To |
PC |
|
| Notes |
| 2008-09-27 08:12:25 | | | | | | | DENIED | | | | | | 1) PROVIDE SUB-CLASSIFICATION TO THE CONSTRUCTION TYPE | | | V (A OR B) ON SHEET SP-1, ASSUMED NON PROTECTED TYPE VB | | | THEREFORE 1HR PROTECTION OF EXTERIOR WALLS ETC. IS NOT | | | REQUIRED, SEE TABLE 601 FBC. | | | | | | 2) PLEASE CORRECT THE DESIGN CRITERIA, SHEET SP-1 IS | | | EXPOSURE C AND THE FOUNDATION PLAN ON S-1 AND COMPONENT | | | & CLADDING ON S-4 ARE BOTH 140MPH EXPOSURE B. | | | | | | 3) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC*. | | | | | | 4) THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON | | | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER | | | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE | | | ADDED TO THE PERMIT APPLICATION FEES. | | | | | | NOTE: FEES ARE DUE IN THE AMOUNT OF $ 230.68 FOR | | | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS | | | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW. | | | | | | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, | | | AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE | | | INFORMATION. | | | | | | 6) PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER | | | R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES, 2'-6" | | | POCKET DOOR MAY NOT MAKE THIS REQUIREMENT. | | | | | | 7) SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT | | | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR | | | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND | | | APPROVED BY THE DESIGNER OF RECORD. | | | | | | 8) TWO SHEET A-6 IN PLAN SETS PLEASE CORRECT | | | ARCHITECTURAL DETAIL SHEET PER DRAWING LIST TO A-5. | | | | | | 9) PROVIDE NEW TO EXISTING FOUNDATION AND STEM WALL | | | CONNECTION DETAIL OR NOTE ON FOUNDATION PLAN. | | | | | | 10) DOES EXISTING FOUNDATION AT COLUMN LOCATION GET CUT | | | OUT AND REMOVED FOR NEW FOUNDATION OR IS THE NEW COLUMN | | | BASE POURED BENEATH EXISTING IF IT DOES NOT MEET | | | REQUIRED 18" WIDTH. | | | | | | 11) SECTION THROUGH LVL BEAM ON S-3 HAS INCORRECT SHEET | | | NUMBER | | | | | | 12) DETAIL 4/S-3 DOES NOT STATE HANGER TYPE AT | | | OUTLOOKER TO TRUSS CONNECTION | | | | | | 13) ADDITIONAL PERMIT WILL BE REQUIRED FOR NEW FENCE AT | | | SOUTHWEST CORNER OF BUILDING PLEASE SEE ATTACHED PERMIT | | | APPLICATION INFORMATION. PER SURVEY THE FENCE IS NOT IN | | | AN EASEMENT AND ONLY REQUIRES THE CITY OF WEST PALM | | | BEACH WATER UTILITIES DEPT. RELEASE. | | | | | | 14) THE PRODUCT APPROVAL FOR THE HORIZONTAL SLIDERS HAS | | | BEEN REVISED WITH THE STATE (FL 242-R7) AND THE | | | MIAMI-DADE NOA (07-0815.09) THAT IS USED AS THE | | | VALIDATION, PLEASE PROVIDE UPDATED APPROVAL | | | | | | 15) SUBMIT A COPY OF THE RECORDED NOTICE OF | | | COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-09-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-09-26 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-09-26 |
Time |
13:13 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-10-31 |
Time |
08:09 |
Rev Time |
0.30 |
| Received By |
mperson |
Date |
2008-10-31 |
Time |
08:09 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2008-10-15 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-10-15 |
Time |
11:36 |
Rev Time |
0.30 |
| Received By |
mperson |
Date |
2008-10-15 |
Time |
11:36 |
Sent To |
Z |
|
| Notes |
| 2008-10-15 11:59:16 | GAS PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | DUE TO THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON | | | SHEET P-2 THE FOLLOWING CORRECTIONS/INFORMATION ARE | | | REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE | | | AND THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE SECTION 401.1 SCOPE.. | | | **NOTE: THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON | | | SHEET P-2 DOES NOT INDICATE THE CORRESPONDING LENGTH TO | | | CUT SECTION OF PIPE TO THE NEW RANGE RISER. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. | | | **NOTE: THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON | | | SHEET P-2 DOES NOT INDICATE THE GAS PIPE SIZES TO THE | | | NEW RANGE. | | | | | | 3. SHEET P-2 GAS ISOMETRIC: THE GAS PIPE SIZE OF 3/4" | | | TO THE NEW INST. HOT (TANKLESS WATER HEATER) IS SIZED | | | WRONG. PER TABLE 402.4(2) SCH. 40 METALLIC PIPE, WITH A | | | LONGEST LENGTH OF 40' AND WITH 189,000 BTU'S THE GAS | | | PIPING TO THE NEW INST. HOT (TANKLESS WATER HEATER) | | | SHALL BE 1". PLEASE REFERENCE FBC-2004 FUEL GAS TABLE | | | 402.4(2) ATTACHED TO THESE COMMENTS INDICATING THIS. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | *IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2008-09-26 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-09-26 |
Time |
16:38 |
Rev Time |
0.30 |
| Received By |
mperson |
Date |
2008-09-26 |
Time |
16:38 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-01-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-08 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-08 |
Time |
15:53 |
Sent To |
B |
|
| Notes |
| 2009-01-08 15:53:33 | TO "RMCDOUGAL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-12-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-08 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-08 |
Time |
16:13 |
Sent To |
B |
|
| Notes |
| 2008-12-08 16:13:56 | TO "LMARTINEZ" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-10-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-30 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-30 |
Time |
15:49 |
Sent To |
G |
|
| Notes |
| 2008-10-30 15:49:39 | TO "MPERSON" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-10-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-14 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-14 |
Time |
12:35 |
Sent To |
P |
|
| Notes |
| 2008-10-14 12:36:40 | TO "P" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-09-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-24 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-24 |
Time |
08:23 |
Sent To |
E |
|
| Notes |
| 2008-09-24 08:23:40 | TO "SFR" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-09-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-15 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2008-09-15 14:30:47 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2008-09-16 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-09-16 |
Time |
12:19 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-09-16 |
Time |
12:19 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-10-31 |
Time |
08:07 |
Rev Time |
0.30 |
| Received By |
mperson |
Date |
2008-10-31 |
Time |
08:07 |
Sent To |
G |
|
| Notes |
| 2008-10-31 08:09:10 | ****************PROVISO**************** | | | PER FBC-2004 PLUMBING SECTION 604.9 WATER HAMMER. A | | | WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE | | | QUICK-CLOSING VALVES ARE UTILIZED. | | | NOTE: A WATER-HAMMER ARRESTOR IS REQUIRED ON THE HOT | | | WATER TO THE NEW DISHWASHER. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-10-15 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-10-15 |
Time |
11:28 |
Rev Time |
0.30 |
| Received By |
mperson |
Date |
2008-10-15 |
Time |
11:28 |
Sent To |
G |
|
| Notes |
| 2008-10-15 11:35:37 | ****************PROVISO**************** | | | PER FBC-2004 PLUMBING SECTION 604.9 WATER HAMMER. A | | | WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE | | | QUICK-CLOSING VALVES ARE UTILIZED. | | | NOTE: A WATER-HAMMER ARRESTOR IS REQUIRED ON THE HOT | | | WATER TO THE NEW DISHWASHER. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-09-26 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-09-26 |
Time |
16:13 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2008-09-26 |
Time |
16:13 |
Sent To |
G |
|
| Notes |
| 2008-09-26 16:31:42 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET P-1, 1ST FLOOR PLUMBING PLAN AND SHEET P-2 | | | SANITARY ISOMETRIC RISER: THE WASHING MACHINE AND | | | DOUBLE BOWL KITCHEN SINK WITH DISHWASHER MUST DRAIN | | | DOWNSTREAM OF THE EXISTING WET VENTED BATHROOM. | | | NOTE: PER FBC-2004 PLUMBING SECTION 909.1 WET VENT | | | PERMITTED. ANY COMBINATION OF FIXTURES WITHIN TWO | | | BATHROOM GROUPS LOCATED ON THE SAME FLOOR LEVEL ARE | | | PERMITTED TO BE VENTED BY A WET VENT. THE WET VENT | | | SHALL BE CONSIDERED THE VENT FOR THE FIXTURES AND SHALL | | | EXTEND FROM THE CONNECTION OF THE DRY VENT ALONG THE | | | DIRECTION OF THE FLOW IN THE DRAIN PIPE TO THE MOST | | | DOWNSTREAM FIXTURE DRAIN CONNECTION TO THE HORIZONTAL | | | BRANCH DRAIN. ONLY THE FIXTURES WITHIN THE BATHROOM | | | GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL | | | BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-10-21 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-10-21 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-10-21 |
Time |
12:01 |
Sent To |
B |
|
| Notes |
| 2008-10-21 12:01:45 | ROUTED TO LUIS MARTINEZ |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2008-09-23 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-09-23 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-09-23 |
Time |
11:28 |
Sent To |
I |
|
| Notes |
|
|