Plan Review Details - Permit 08090316
Plan Review Stops For Permit 08090316
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-02 Cont ID  
Sent By jwitmer Date 2008-10-02 Time 08:31 Rev Time 1.11
Received By jwitmer Date 2008-10-02 Time 08:31 Sent To  
Notes
2008-10-02 08:45:24BUILDING PLAN REVIEW
 PERMIT: 08090316
 ADD: 2903 HILLSBORO RD
 CONT: TIM JOHNSON REMODELING
 TEL: (561)707-7058
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 PRODUCT APPROVALS AND OR SUBMITTALS FOR REVIEW FOR
 PERMIT. 106.1* /2004 WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) MISSING WIND DESIGN INFORMATION :1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3A) WALL LOUVER
  
 3B) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) SPRAY ROOM REQUIREMENTS:
 416.1 GENERAL.
 THE PROVISIONS OF THIS SECTION SHALL APPLY TO THE
 CONSTRUCTION, INSTALLATION AND USE OF BUILDINGS AND
 STRUCTURES, OR PARTS THEREOF, FOR THE SPRAYING OF
 FLAMMABLE PAINTS, VARNISHES AND LACQUERS OR OTHER
 FLAMMABLE MATERIALS OR MIXTURES OR COMPOUNDS USED FOR
 PAINTING, VARNISHING, STAINING OR SIMILAR PURPOSES.
 SUCH CONSTRUCTION AND EQUIPMENT SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE .
 SPRAY
 416.2 SPRAY ROOMS.
 SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS
 AND HORIZONTAL ASSEMBLIES OR BOTH WITH NOT LESS THAN A
 1-HOUR FIRE-RESISTANCE RATING. FLOORS SHALL BE
 WATERPROOFED AND DRAINED IN AN APPROVED MANNER.
  
 416.2.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH
 AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE
 OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING, AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM
 SHALL NOT BE USED.
  
 416.3 SPRAYING SPACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR
 VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL . WHERE SUCH SPACES ARE NOT SEPARATELY
 ENCLOSED, NONCOMBUSTIBLE SPRAY CURTAINS SHALL BE
 PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE VAPORS.
  
 416.3.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE
 SMOOTH AND CONTINUOUS WITHOUT EDGES, AND SHALL BE SO
 CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR
 FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE
 WASHING AND CLEANING, AND SHALL BE SO DESIGNED TO
 CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM
 SHALL NOT BE USED.
  
 416.4 FIRE PROTECTION.
 AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE
 PROVIDED IN ALL SPRAY , DIP AND IMMERSING SPACES AND
 STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE
 WITH CHAPTER 9 .
  
 5) PLEASE PROVIDE INFORMATION AS TO HOW THE EXHAUST
 VENT WILL BE MOUNTED TO THE BUILDING IN A HIGH WIND
 EVENT. 1609.6.2.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-03 Cont ID  
Sent By dpalmer Date 2008-10-03 Time 16:31 Rev Time 0.00
Received By dpalmer Date 2008-10-03 Time 16:31 Sent To  
Notes
2008-10-03 16:31:47 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT COMPLETE ELECTRICAL PLANS UNDER
 DESIGN OF NFPA-70, NFPA-33 AND FBC 2004 W/2007
 REVISIONS.
 PLEASE SEE NEC 516 AND NEC 500 AND SHOW ALL CLASS
 LOCATIONS.
  
 2) NOTE: PLEASE SUBMIT PLANS WHICH WILL SHOW
 CIRCUITING, LOADS, FEEDS, BRANCH CIRCUITS ETC.
 408.4,220,310.16, 240.4 ETC
 FBC 106.1.1, 106.3.5.1.2
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-06 Cont ID  
Sent By mawillia Date 2008-10-06 Time 16:58 Rev Time 0.00
Received By mawillia Date 2008-10-06 Time 15:27 Sent To  
Notes
2008-10-06 16:29:11*****DENIED*****
  
  
 1. NFPA 33, STANDARD FOR SPRAY APPLICATION USING
 FLAMMABLE OR COMBUSTIBLE MATERIALS, 2003 EDITION SHALL
 BE REFERENCED.
  
 2. PLEASE LIST THE TYPE OF OCCUPANCY THAT THE SPRAY
 BOOTH IS TO BE INSTALLED.
  
 3. LIST THE FIRE RESISTIVE RATING OF THE CONSTRUCTION
 ASSEMBLIES (WALLS, CEILINGS) SURROUNDING THE PAINT
 BOOTH.
  
 4. SHOW THE LOCATION OF THE PAINT BOOTH IN RELATION TO
 MEANS OF EGRESS (DOORS, WINDOWS) THAT MEET THE
 REQUIREMENTS OF NFPA 101.
  
 5. SPRAY BOOTHS SHALL BE SEPARATED FROM OTHER
 OPERATIONS BY A MINIMUM OF 3 FT. OR BY A WALL,
 PARTITION, OR FLOOR/CEILING ASSEMBLY HAVING A MINIMUM
 FIRE RESTIVE RATING OF 1 HOUR.
  
 6. THE SPRAY BOOTH SHALL BE PROTECTED WITH AN APPROVED
 AUTOMATIC FIRE PROTECTION SYSTEM. PLEASE INDICATE THE
 TYPE OF SYSTEM THIS WILL BE.
  
 7. SHOW THE LOCATION OF THE PORTABLE FIRE EXTINGUISHERS
 INDEPENDENT OF THE PAINT BOOTH'S SUPPRESSION SYSTEM.
  
 8. NO SMOKING OR OPEN FLAMES SIGNS IN LARGE LETTERS ON
 CONTRASTING COLOR BACKGROUND SHALL BE CONSPICUOUSLY
 POSTED AT ALL SPRAY AREAS AND PAINT STORAGE AREAS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW THE COMMENT HAS BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-06 Cont ID  
Sent By mawillia Date 2008-10-06 Time 15:27 Rev Time 0.00
Received By mawillia Date 2008-09-15 Time 11:30 Sent To  
Notes
2008-10-06 11:13:2310/6/08--FIRE THE LAST TO DO REVIEW. PLANS TAKEN OFF BD
 AND ROUTED TO MIKE WILLIAMS.
2008-09-15 11:46:27TO "COMM" BD#24

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-23 Cont ID  
Sent By rregueir Date 2008-09-23 Time 12:54 Rev Time 0.00
Received By rregueir Date 2008-09-23 Time 12:04 Sent To  
Notes
2008-09-23 12:54:33REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE INFORMATION SHOWING HOW THE EXHAUST FAN IS
 TO BE INTERLOCKED WITH THE SPRAYING EQUIPMENT. SPRAYING
 EQUIPMENT SHALL BE INTERLOCKED WITH THE VENTILATION OF
 THE SPRAYING AREA SUCH THAT SPRAYING OPERATIONS CANNOT
 BE CONDUCTED UNLESS THE VENTILATION SYSTEM IS IN
 OPERATION IN ACCORDANCE WITH FBCM 502.7.3.1.
  
 2. PROVIDE INFORMATION SHOWING A TIME DELAY IN EFFECT
 TO ASSURE FAN RUNS FOR A PERIOD AFTER SPRAYING
 OPERATIONS HAVE STOPPED. MECHANICAL VENTILATION SHALL
 BE KEPT IN OPERATION FOR A SUFFICIENT TIME THEREAFTER
 TO ALLOW VAPORS FROM DRYING COATED ARTICLES AND
 FINISHING MATERIAL RESIDUE TO BE EXHAUSTED IN
 ACCORDANCE WITH FBCM 502.7.3.1.
  
 3. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE
 EXHAUST TERMINATION WITH RESPECT TO PROPERTY LINES AND
 ADJACENT BUILDINGS. THE TERMINATION POINT FOR EXHAUST
 DUCTS DISCHARGING TO THE ATMOSPHERE SHALL BE LOCATED
 WITH THE FOLLOWING MINIMUM DISTANCES:
  
 - 30 FEET (9144 MM) FROM THE PROPERTY LINE;
 - 10 FEET (3048 MM) FROM OPENINGS INTO THE BUILDING;
 - 6 FEET (1829 MM) FROM EXTERIOR WALLS AND ROOFS;
 - 30 FEET (9144 MM) FROM COMBUSTIBLE WALLS AND OPENINGS
 INTO THE BUILDING WHICH ARE IN THE DIRECTION OF THE
 EXHAUST DISCHARGE;
 - 10 FEET (3048 MM) ABOVE ADJOINING GRADE.
  
 4. PROVIDE SPECIFICATIONS FOR THE EXHAUST FAN. ELECTRIC
 MOTORS DRIVING EXHAUST FANS SHALL NOT BE PLACED INSIDE
 DUCTS. FAN ROTATING ELEMENTS SHALL BE NONFERROUS OR
 NONSPARKING OR THE CASING SHALL CONSIST OF, OR BE LINED
 WITH, SUCH MATERIAL. BELTS SHALL NOT ENTER THE DUCT OR
 BOOTH UNLESS THE BELT AND PULLEY WITHIN THE DUCT ARE
 TIGHTLY ENCLOSED IN ACCORDANCE WITH FBCM 502.7.3.7.
  
 5. EAST EXTERIOR ELEVATION IDENTIFIES THE EXHAUST
 TERMINATION AS A LOUVERED VENT. THIS APPEARS TO BE AN
 UP-TURNED 90 DEGREE ELBOW, NOT A LOUVER. PLEASE
 CLARIFY. ALSO, SEE COMMENT #3 ABOVE, THIS TERMINATION
 SHALL BE A MINIMUM OF 6 FEET FROM THE EXTERIOR OF THE
 BUILDING. SHOW WHAT TYPE OF WEATHERPROOF TERMINATION IS
 TO BE USED. EXHAUST OUTLETS SHALL BE PROTECTED AGAINST
 LOCAL WEATHER CONDITIONS IN ACCORDANCE WITH FBCM 401.6
  
 6: THE MAKE-UP AIR LOVER IS REQUIRED TO HAVE A PRODUCT
 APPROVAL IN ACCORDANCE WITH FBCB 1609 AND FAC RULE
 9B-72. PROVIDE PRODUCT APPROVAL DOCUMENTATION APPROVED
 IN WRITING BY THE ARCHITECT IN ACCORDANCE WITH FBCB
 106.3.3.
  
 7. SHOW HOW THE EXTERIOR EXHAUST DUCT AND TERMINATION
 ARE TO BE SECURED AND INSTALLED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-23 Cont ID  
Sent By jroach Date 2008-09-23 Time 10:55 Rev Time 0.00
Received By jroach Date 2008-09-23 Time 10:55 Sent To  
Notes
2008-09-23 10:58:47***FAILED***
  
 AS THE INSTALLATION OF THE SPRAY BOOTH PROVIDES FOR
 IMPROVEMENTS ON THE EXTERIOR OF THE BUILDING (I.E.
 INSTALLATION OF THE VENT), THE FOLLOWING SHALL BE
 PROVIDED:
  
 1) TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 2) THE SITE PLAN SHALL BE MODIFIED TO SHOW THE LOCATION
 OF THE PROPERTY LINES. DIMENSIONS SHALL BE PROVIDED
 FROM THE PROPERTY LINES TO THE VENT, AND SHALL CONFORM
 TO THE MINIMUM SETBACK REQUIREMENTS OF THE INDUSTRIAL
 (I) ZONING DISTRICT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.