Plan Review Details - Permit 08090306
Plan Review Stops For Permit 08090306
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-03 Cont ID  
Sent By jwitmer Date 2008-11-03 Time 10:51 Rev Time 0.77
Received By jwitmer Date 2008-11-03 Time 10:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-06 Cont ID  
Sent By jwitmer Date 2008-10-06 Time 16:54 Rev Time 1.33
Received By jwitmer Date 2008-10-06 Time 16:54 Sent To  
Notes
2008-10-06 16:56:59BUILDING PLAN REVIEW
 PERMIT: 08090306
 ADD: 525 OKEECHOBEE BLVD SUITE 1050
 CONT: BUTLER
 TEL: (561)644-3579
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION, PLEASE
 CORRECT PLANS INDICATE BY FINAL
 COVERSHEET.
  
 1E) : PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS COVER SHEET DOES NOT
 INCLUDE 2007 SUPPLEMENTS, PLEASE CORRECT.
  
 2) SHEET A-1 DOOR NOTE # 5 INDICATES THE USE OF CARD
 READERS AND ELECTRONIC LOCKS, PLANS FAIL TO INDICATE IF
 THE LOCKS AUTOMATICLLY SET TO A FAIL SAFE OPEN POSITION
 WITH LOSS OF POWER. 1008.1.3.4.
  
 3) SHEET A-1 TENANT SEPERATION WALLS ARE A 1 HR RATED
 WALL. THE DOOR SCHEDULE DOES NOT INDICATE OPENING
 PROTECTION FOR 2 OF THE 3 ENTRY DOORS. DOOR# 1029 UNDER
 REMARKS DOES INDICATE 20 MINUTE DOOR WITH CLOSERE.
 DOOR# 1001 INDICATES HOLD OPEN DEVICES AND DOOR CLOSERS
 BUT NOT A RATED DOOR AND DOOR# ETR UNDER REMARKS ONLY
 INDICATES AN ELETRIC STRIKE. NO MENTION OF A DOOR
 CLOSER OR FIRE RATING OF DOOR AND JAMB. OPENING
 PROTECTIVES TABLE 715.3./708.1.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-31 Cont ID  
Sent By dpalmer Date 2008-10-31 Time 12:10 Rev Time 0.00
Received By dpalmer Date 2008-10-31 Time 12:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-03 Cont ID  
Sent By dpalmer Date 2008-10-03 Time 17:04 Rev Time 0.00
Received By dpalmer Date 2008-10-03 Time 17:04 Sent To  
Notes
2008-10-03 17:04:21 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,.1.2
 AND COORDINATE ALL LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE BE SURE THE TYPE OF FIXTURES, NUMBER OF FIXTURES
 AND WATTAGES COORDINATED WITH THE CALCULATIONS AS
 SHOWN.
 ONE EXAMPLE: THE 34WATTS INPUT REQUIRED FOR RECESSED
 DOWN LIGHTS IS NOT THE SAME. SHOWN AS 32WATTS ON
 CALCULATIONS HOWEVER THE INPUT NEEDS TO BE 34WATTS. THE
 COUNT OF THE 34 WATT FIXTURES IS ALSO NOT ACCURATE.
  
 ** ONE EXAMPLE GIVEN AS A BENEFIT TO DESIGN TEAM ONLY.
 THIS IS NOT AN EXHAUSTED LIST.
  
 2) NOTE: ROOM 1028 IS DEFINED ON PLANS AS AN IT ROOM.
 IF THIS IS THE CASE PLEASE SEE THE REQUIREMENTS OF
 NFPA-75 AND MORE IMPORTANTLY NEC 645 FOR DISCONNECTS,
 ETC REQUIRED. PLEASE CLARIFY THE SHUNT TRIP IN PANEL HA
 IS FOR THE AHU SYSTEM FRO THE ROOM. IF THIS IS NOT AN
 IT ROOM, NO WIRING METHODS IN NEC 645 ARE PERMITTED AND
 PLACE NOTES ON PLANS ACCORDINGLY.
 PLEASE ALSO CHANGE ROOM DESIGNATION.
  
 3) NOTE: PLEASE BE SURE ALL CIRCUITS ARE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. EXAMPLE: *LIGHTING*
 NOTED.
 408.4
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-07 Cont ID  
Sent By mwennerg Date 2008-11-07 Time 11:23 Rev Time 0.00
Received By mwennerg Date 2008-11-07 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-08 Cont ID  
Sent By mwennerg Date 2008-10-08 Time 11:29 Rev Time 0.00
Received By mwennerg Date 2008-10-08 Time 11:29 Sent To  
Notes
2008-10-08 11:35:47***DENIED***
  
 1) PLANS ILLUSTRATE CARD READERS. WORK SHALL COMPLY
 WITH NFPA 101, SEC. 7.2.1.6.2 FOR ACCESS CONTROLLED
 EGRESS DOORS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 ACCESS CONTROL SYSTEM.
  
 3) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 15:14 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 15:14 Sent To  
Notes
2008-10-21 10:10:04TO "COMM" BD#53
2008-10-17 15:14:51WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-08 Cont ID  
Sent By mwennerg Date 2008-10-08 Time 11:37 Rev Time 0.00
Received By mwennerg Date 2008-09-15 Time 09:29 Sent To  
Notes
2008-09-15 09:29:18TO "COMM" BD#8

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-08 Cont ID  
Sent By rregueir Date 2008-11-08 Time 16:49 Rev Time 0.00
Received By rregueir Date 2008-11-08 Time 16:46 Sent To PC
Notes
2008-11-08 16:49:41*****************PROVISO*******************
 EXHAUST DUCT PENETRATION OF RATED WALL SHALL BE
 PROTECTED BY A LISTED THROUGH-PENETRATION FIRESTOP
 SYSTEM IN ACCORDANCE WITH FBCM 607.1.1 AND FBCB 712.3.3
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-22 Cont ID  
Sent By rregueir Date 2008-09-22 Time 14:36 Rev Time 0.00
Received By rregueir Date 2008-09-22 Time 11:46 Sent To  
Notes
2008-09-22 14:36:14REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M2.1: THE CEILING MOUNTED EXHAUST FAN IN BATH
 ROOM 1027 WILL CREATE A POSITIVELY PRESSURIZED EXHAUST
 DUCT IN THE PLENUM CEILING. EXHAUST DUCTS UNDER
 POSITIVE PRESSURE SHALL NOT EXTEND INTO OR PASS THROUGH
 DUCTS OR PLENUMS IN ACCORDANCE WITH FBCM 601.3.
  
 2. PAGE M2.1: THE 4 INCH ROUND EXHAUST DUCT FROM BATH
 ROOM 1027 APPEARS TO BE PENETRATING AN EXISTING
 FIRE-RESISTANCE RATED WALL ASSEMBLY BASED ON THE
 PRESENCE OF FIRE DAMPERS IN OTHER DUCT PENETRATIONS OF
 THE SAME WALL. SHOW HOW THIS PENETRATION IS TO BE
 PROTECTED IN ACCORDANCE WITH FBCM 607.1.
  
 3. PAGE M2.1: HP-1 FOR THE IT ROOM HAS A SUPPLY FAN IN
 EXCESS OF 2000 CFM AND THEREFORE REQUIRES SHUT-DOWN BY
 SMOKE DETECTOR IN ACCORDANCE WITH FBCM 606.2. DUCT
 MOUNTED SMOKE DETECTORS SHALL BE CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH FBCM
 606.4.1.
  
 4. PAGE M2.1: WHAT IS THE RETURN AIR CAPACITY OF THE
 TITUS MLR-39 LINEAR RETURN GRILLS USED IN THE PERIMETER
 OFFICE APPLICATIONS? THE SCHEDULE ON PAGE M6.1 GIVES NO
 VALUES FOR THE LINEAR RETURN GRILLS. SHOW HOW BALANCED
 RETURN IS TO BE ACHIEVED IN THESE AREAS IN ACCORDANCE
 WITH FBCM 601.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-31 Cont ID  
Sent By kstevens Date 2008-10-31 Time 16:53 Rev Time 0.00
Received By kstevens Date 2008-10-31 Time 16:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-09-16 Cont ID  
Sent By kstevens Date 2008-09-16 Time 08:18 Rev Time 0.00
Received By kstevens Date 2008-09-16 Time 08:18 Sent To  
Notes
2008-09-16 08:19:22PASSED/PROVISO -- WATER HAMMER ARRESTORS ARE REQUIRED
 ON THE HOT & COLD WATER LINES TO THE ICE MAKER &
 DISHWASHER PER SECTION 604.9.


Account Summary | Usage Policy | Privacy Policy