Plan Review Details - Permit 08090304
Plan Review Stops For Permit 08090304
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-17 Cont ID  
Sent By mjacobs Date 2008-10-17 Time 15:23 Rev Time 0.00
Received By mjacobs Date 2008-10-17 Time 15:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-17 Cont ID  
Sent By mjacobs Date 2008-09-17 Time 16:21 Rev Time 0.00
Received By mjacobs Date 2008-09-17 Time 14:42 Sent To  
Notes
2008-09-17 16:21:01 
 BUILDING PLAN REVIEW
 PERMIT: 08090304
 ADD: 222 LAKEVIEW AVE
 CONT: DEWHURST ASSOC.
 TEL: (561)241-1540
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A1.1 KEY NOTES #7 INDICATES A GARBAGE DISPOSAL
 WITH AN ADA COMPLIANT SINK: THE INFORMATION FOR THE
 SINK AND GARBAGE DISPOSAL IS MISSING FROM THE PACKAGE.
 SHOW THE DEPTH OF THE SINK ON SHEET A3.1 DETAIL A8
 WHICH SHALL BE A MAXIMUM DEPTH OF 6 ? ? INCH PER FBC
 11-4.24.4. THE LOCATION AND TYPE OF GARBAGE DISPOSAL
 SHALL ALSO BE SHOWN ON THAT DETAIL TO SHOW COMPLIANCE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-22 Cont ID  
Sent By dpalmer Date 2008-10-22 Time 10:25 Rev Time 0.00
Received By dpalmer Date 2008-10-22 Time 10:25 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-24 Cont ID  
Sent By dpalmer Date 2008-09-24 Time 11:06 Rev Time 0.00
Received By dpalmer Date 2008-09-24 Time 11:06 Sent To  
Notes
2008-09-24 11:06:43 
 ** DENIED REVIEW **
  
  
 1) NOTE: THE ELECTRICAL DISCONNECTS DO NOT APPEAR TO
 MEET 110.26 FOR HEIGHTS OR WORKING CLEARANCES. THIS IS
 A LIFE SAFETY ISSUE AND NEEDS TO BE VERIFIED AT THIS
 TIME. ONCE VERIFIED, THERE MAY BE A NEED TO RE-ARRANGE
 SERVICE DISCONNECTS.
 PLEASE SEE 110.26 ALL.
  
 2) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2
 FOR MINIMUM REQUIRED LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE COMPLETE THE FIXTURE LEGEND FOR SPECIFIC
 FIXTURES, TYPES, WATTAGES ETC.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-21 Cont ID  
Sent By mawillia Date 2008-10-21 Time 12:24 Rev Time 0.00
Received By mawillia Date 2008-10-21 Time 11:50 Sent To  
Notes
2008-10-21 12:23:10*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A1.1 THRU A3.1, E2, & FP1 WERE
 STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-30 Cont ID  
Sent By mawillia Date 2008-09-30 Time 14:39 Rev Time 0.00
Received By mawillia Date 2008-09-30 Time 14:05 Sent To  
Notes
2008-09-30 14:33:53*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. THE NUMBER OF EXIT LIGHTS SHOWN ON SHEET A2.1 AND
 SHEET E2 DON'T CORRELATE. NO EXIT LIGHT SHOWN IN THE
 CONFERENCE ROOM ON SHEET A2.1 AS INDICATED ON SHEET E2.
  
 3. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS LOCATED
 IN SCOPE OF WORK AREA. THESE MAY SHOWN ON THE REFLECTED
 CEILING PLAN (SHEET A2.1).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-16 Cont ID  
Sent By adarroug Date 2008-10-16 Time 14:20 Rev Time 0.00
Received By adarroug Date 2008-10-16 Time 14:20 Sent To  
Notes
2008-10-16 14:24:11TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-30 Cont ID  
Sent By mawillia Date 2008-09-30 Time 14:05 Rev Time 0.00
Received By mawillia Date 2008-09-12 Time 16:32 Sent To  
Notes
2008-09-12 16:36:44TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-09-15 Cont ID  
Sent By tgordon Date 2008-09-15 Time 16:36 Rev Time 0.30
Received By tgordon Date 2008-09-15 Time 16:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-17 Cont ID  
Sent By mperson Date 2008-10-17 Time 10:38 Rev Time 0.30
Received By mperson Date 2008-10-17 Time 10:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-16 Cont ID  
Sent By mperson Date 2008-09-16 Time 13:14 Rev Time 0.45
Received By mperson Date 2008-09-16 Time 13:14 Sent To  
Notes
2008-09-16 13:51:15PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A1.1 KEY NOTES NUMBER 7 INDICATES A GARBAGE
 DISPOSAL WITH AN ADA COMPLIANT SINK. PROVIDE
 MANUFACTURE SPECIFICATION SHEETS OF THE SINK AND
 GARBAGE DISPOSAL COMPLIANT WITH THE FOLLOWING FBC-2004
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
 SECTION 11-4.24.3 KNEE CLEARANCE (MINIMUM 27" HIGH, 30"
 WIDE, AND 19"DEEP). SECTION 11-4.24.4 SINK DEPTH
 (MAXIMUM 6-1/2" DEEP). SECTION 11-4.24.5 CLEAR FLOOR
 SPACE (30" X 48" AND CLEAR FLOOR SPACE SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK).
  
 2. SHEET A3.1 DETAIL A8, CAB. SECTION @ SINK: PLEASE
 CORRELATE DETAIL WITH SHEET A1.1 KEY NOTE NUMBER 7, AND
 CLEARLY INDICATE THE GARBAGE DISPOSAL ON THE DETAIL
 (PER FBC-2004 PLUMBING SECTION 401.1 SCOPE). ALSO
 PLEASE CLEARLY INDICATE THAT THE DISPOSAL SHALL BE
 COMPLIAMT WITH THE FOLLOWING FBC-2004 CHAPTER 11,
 FLORIDA ACCESSIBILITY CODE SECTIONS. SECTION 11-4.24.3
 KNEE CLEARANCES AND SECTION 11-4.24 5 CLEAR FLOOR
 SPACE.
  
 3. SHEET P2, PLUMBING SPECIFICATIONS NUMBER 8: PLEASE
 KNOW THAT AIR CHAMBERS ARE NOT ACCEPTABLE BY THE
 FBC-2004 PLUMBING CODE. PLEASE DELETE THE FOLLOWING
 "ALL OTHER FIXTURES AND SUPPLIES TO HAVE AIR CHAMBERS".
 PER FBC-2004 PLUMBING SECTION 604.9 WATER HAMMER.
  
 4. PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT
 IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE -
 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY.. PER FS
 713.13 (2): IF THE IMPROVEMENT DESCRIBED IN THE NOTICE
 OF COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90
 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID
 AND OF NO FURTHER EFFECT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]