Plan Review Details - Permit 08090223
Plan Review Stops For Permit 08090223
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-03 Cont ID  
Sent By jwitmer Date 2008-11-03 Time 11:29 Rev Time 0.00
Received By jwitmer Date 2008-11-03 Time 11:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-29 Cont ID  
Sent By jwitmer Date 2008-09-29 Time 16:14 Rev Time 1.33
Received By jwitmer Date 2008-09-29 Time 16:14 Sent To  
Notes
2008-09-29 16:38:04BUILDING PLAN REVIEW
 PERMIT: 08090223
 ADD: 6910 S DIXIE HWY.
 CONT: SULLIVAN BUILDERS OF FLORIDA
 TEL: (561)310-1899
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) I INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) SHEET A-1 THE FRONT ENTRY PORCH HAS A 6 INCH DROP
 MAKING IT IMPASSIBLE FOR WHEEL CHAIR USERS. 11-4.3.2(1)
 AT LEAST ONE ACCESSIBLE ROUTE WITHIN THE BOUNDARY OF
 THE SITE SHALL BE PROVIDED FROM PUBLIC TRANSPORTATION
 STOPS, ACCESSIBLE PARKING, AND ACCESSIBLE PASSENGER
 LOADING ZONES, AND PUBLIC STREETS OR SIDEWALKS TO THE
 ACCESSIBLE BUILDING ENTRANCE THEY SERVE. THE ACCESSIBLE
 ROUTE SHALL, TO THE MAXIMUM EXTENT FEASIBLE, COINCIDE
 WITH THE ROUTE FOR THE GENERAL PUBLIC.
  
 3) SHEET S-3 IS MISSING THE WIND DESIGN CRITERIA:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 4) SHEET A-2 INDICATES THE PORCH TO BE A STUCCO FINISH,
 S-1 DETAIL# 3 DOES NOT PROVIDE INFORMATION AS TO THE
 TYPE OF SUB-BASE THE STUCCO WILL BE ADHERED TOO ( WIRE
 LATH?) NOR THE WEIGHT OR GAUGE OF WIRE LATH NOR TYPE OF
 LATH TO BE INSTALLED. 2510.3/ ASTM C1063. INSTALATION
 OF LATH AND FURRING CEMENT STUCCO PLASTER.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-31 Cont ID  
Sent By dpalmer Date 2008-10-31 Time 13:31 Rev Time 0.00
Received By dpalmer Date 2008-10-31 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-03 Cont ID  
Sent By dpalmer Date 2008-10-03 Time 09:09 Rev Time 0.00
Received By dpalmer Date 2008-10-03 Time 09:09 Sent To  
Notes
2008-10-03 09:09:45 
 ** DENIED **
  
  
  
  
 1) NOTE: PLEASE PROVIDE THE EXTERIOR LIGHTING
 PERFORMANCE CALCULATIONS PER FBC 13-415.2,
 13-415.2.ABC.1.3.
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-05 Cont ID  
Sent By mawillia Date 2008-11-05 Time 15:13 Rev Time 0.00
Received By mawillia Date 2008-11-05 Time 14:50 Sent To  
Notes
2008-11-05 15:11:13*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW (HANDRAILS NOT
 REQUIRED AS PER YOUR RESPONSE) WERE ACKNOWLEDGED; PLAN
 SHEET A-2 STAMPED, INITIALED, AND DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-07 Cont ID  
Sent By mawillia Date 2008-10-07 Time 12:57 Rev Time 0.00
Received By mawillia Date 2008-10-07 Time 12:38 Sent To  
Notes
2008-10-07 12:57:22*****PROVISO*****
  
  
 1. STAIRS AND RAMPS SHALL HAVE HYANDRAILS ON BOTH
 SIDES.
  
 2. PROVIDE PRESCRIPITIVE STRENGHTS FOR THE RAMP'S
 GUARDRAIL/HANDRAILS.
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMED WHEN THE
 ABOVE ITEMS AS WELL THE OTHER REVIEWERS' COMMENTS HAVE
 BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-19 Cont ID  
Sent By adarroug Date 2008-11-19 Time 08:36 Rev Time 0.00
Received By adarroug Date 2008-11-19 Time 08:36 Sent To Z
Notes
2008-11-19 08:36:54TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-21 Cont ID  
Sent By adarroug Date 2008-10-21 Time 16:48 Rev Time 0.00
Received By adarroug Date 2008-10-21 Time 16:48 Sent To  
Notes
2008-10-21 16:49:45TO "COMM" BD#24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-07 Cont ID  
Sent By mawillia Date 2008-10-07 Time 12:57 Rev Time 0.00
Received By mawillia Date 2008-09-12 Time 08:58 Sent To  
Notes
2008-10-06 11:08:1610/6/08--FIRE THE LAST TO REVIEW. PLANS TAKEN OFF THE
 BD AND ROUTED TO MIKE WILLIAMS DESK.
2008-09-12 09:05:38TO "COMM" BD#10

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2008-12-02 Cont ID  
Sent By rkussner Date 2008-12-02 Time 16:44 Rev Time 0.00
Received By rkussner Date 2008-12-02 Time 16:44 Sent To PC
Notes
2008-12-02 16:46:46***LANDSCAPE REVIEW PASSED***
  
 LANDSCAPING WAS ORIGINALLY APPROVED ON 11/6/08. THIS
 APPROVAL IS BASED UPON THE NEWEST REVISED PLAN. ---RAK

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-11-06 Cont ID  
Sent By rkussner Date 2008-11-06 Time 12:12 Rev Time 0.00
Received By rkussner Date 2008-11-06 Time 12:11 Sent To  
Notes
2008-11-06 12:17:13***LANDSCAPE REVIEW APPROVED***
  
 THE APPLICANT SHALL REMOVE THE MELALEUCA TREES ALONG
 THE EAST PERIMETER--NO TREE ALTERATION PERMIT IS
 REQUIRED. A REVISED LANDSCAPE PLAN SHALL BE SUBMITTED
 AND APPROVED SHOWING THE NEW TREES, HEDGE AND
 IRRIGATION TO BE INSTALLED ALONG THE EAST PERIMETER
 PRIOR TO THE LANDSCAPE FINAL INSPECTION BEING CALLED
 IN. THE DUMPSTER ENCLOSURE AND LANDSCAPE SCREENING
 SHALL ALSO BE SHOWN ON THE LANDSCAPE PLAN. NEW SITE
 LIGHTING WILL NOT BE INSTALLED AT THIS TIME. --RAK
 11/6/08

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By rkussner Date 2008-10-23 Time 15:18 Rev Time 0.00
Received By rkussner Date 2008-10-23 Time 15:17 Sent To  
Notes
2008-10-23 15:47:18***LANDSCAPE REVIEW FAILED***
  
 1. PLEASE REMOVE THE STREET LIGHT FROM THE LANDSCAPE
 ISLAND AND THE OTHER STREET LIGHT LOCATED BEHIND AN
 ISLAND NEAR THE DUMPSTER. LIGHTING SHALL BE CENTERED
 BETWEEN TREES ALONG THE PERIMETER OF THE SITE AND KEPT
 OUT OF LANDSCAPE ISLANDS.
  
 2. PURSUANT TO SECTION 94-448(F)(11), TREES WHICH ARE
 INCLUDED AS PROHIBITED TREES PURSUANT TO SUBSECTION
 94-445(4)I, SHALL BE REMOVED AND DISPOSED OF FROM THE
 ENTIRE SITE BEFORE A CERTIFICATE OF OCCUPANCY CAN BE
 OBTAINED. UPON VISITING THE SITE, I FOUND THAT THERE IS
 A ROW OF MELALEUCA TREES ALONG THE EAST PROPERTY LINE.
 THESE TREES SHALL BE REMOVED AND REPLACED WITH AN
 APPROPRIATE SPECIES (30 FOOT ON CENTER). TREE SPECIES
 SHALL COMPLY WITH FPL'S "PLANT THE RIGHT TREE IN THE
 RIGHT PLACE" GUIDELINES. THE WALL THAT IS REQUIRED TO
 BE SCREENED WITH LANDSCAPING FROM THE ADJACENT
 RIGHT-OF-WAY ALONG THE EAST PERIMETER OF THE SITE WAS
 MISSING THE REQUIRED HEDGE.
  
 3. PURSUANT TO SECTION 94-446(2), LANDSCAPING SHALL BE
 MAINTAINED IN GOOD CONDITION, SHALL PRESENT A HEALTHY,
 NEAT AND ORDERLY APPEARANCE, AND SHALL BE FREE FROM
 REFUSE AND DEBRIS. ALL LANDSCAPED AREAS SHALL BE
 PROVIDED WITH A PERMANENT AUTOMATIC IRRIGATION SYSTEM.
 LANDSCAPING (TREES AND SHRUBS) ARE MISSING THROUGHOUT
 THE SITE. PLEASE RESTORE THE LANDSCAPING THROUGHOUT,
 WHICH WILL INCLUDE A PERIMETER HEDGE AND TREE ROW.
 ALSO, A TREE IS REQUIRED TO BE PLANTED IN EVERY
 LANDSCAPE ISLAND.
  
  
  
 IF YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS,
 PLEASE CONTACT ROBERT KUSSNER @(561) 822-1462.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-28 Cont ID  
Sent By kdfreema Date 2008-10-23 Time 15:09 Rev Time 0.00
Received By kdfreema Date 2008-10-28 Time 15:12 Sent To  
Notes
2008-10-23 15:15:47***PROVISO***
  
 THE LANDSCAPE ISLAND NEXT TO PARKING SPACE 23 SHALL
 HAVE A MINIMUM INTERIOR WIDTH OF 5 FEET FROM INSIDE OF
 CURB TO INSIDE OF CURB.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR 561-822-1435 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-18 Cont ID  
Sent By kdfreema Date 2008-09-18 Time 14:36 Rev Time 0.00
Received By kdfreema Date 2008-09-18 Time 14:36 Sent To  
Notes
2008-09-18 15:44:21***FAILED***
  
 1. AN ORIGINAL SURVEY MUST BE PROVIDED.
  
 2. SEC. 94-442(A) OF THE ZONING CODE REQUIRES ALL
 LANDSCAPE PLANS TO BE PREPARED BY A REGISTERED
 LANDSCAPE ARCHITECT.
  
 3. SEC. 94-443(B)(4) REQUIRES AT LEAST ONE SHADE OR
 FLOWERING TREE TO BE PLANTED FOR EACH 30 LINEAR FEET OF
 BUFFER. ADDING TWO TREES ALONG DIXIE, ONE DIRECTLY WEST
 OF THE BOUNDARY OF PARKING SPACES 3 AND 4 AS WELL AS
 ONE DIRECTLY WEST OF PARKING SPACES 7 AND 8 WILL
 SATISFY THIS REQUIREMENT IN THE WEST BUFFER. ON THE
 NORTH SIDE, A TREE NORTH OF SPACE 20 WILL SUFFICE.
  
 4. INDICATE THE VISIBILITY TRIANGLE ON THE LANDSCAPE
 PLAN, AS SET FORTH IN SEC. 94-305(E) AND ENSURE
 COMPLIANCE.
  
 5. SEC. 94-443(C)(3)(A) AND (B) REQUIRES TERMINAL AND
 INTERIOR LANDSCAPE ISLANDS BE A MINIMUM OF 5 FEET IN
 WIDTH. THE 5 FEET IS MEASURED INSIDE OF CURB TO INSIDE
 OF CURB. PLEASE REVISE PLANS ACCORDINGLY.
  
 6. THE PROPOSED TREE AND PARKING LOT LIGHT NEXT TO
 PARKING SPACE 23 ARE IN CONFLICT. PLEASE RELOCATE
 PARKING LOT LIGHT TO THAT IT DOES NOT INTERFERE WITH
 LANDSCAPING.
  
 7. PLEASE PROVIDE THE HEIGHT SPECIFICATIONS ON THE
 PROPOSED WILD TAMARIND.
  
 8. CLEARLY INDICATE CURBING VERSUS STRIPING ON THE
 LANDSCAPE PLAN. IT IS IMPOSSIBLE TO DIFFERENTIATE
 BETWEEN THE TWO.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR 561-822-1435 WITH QUESTIONS.