Plan Review Details - Permit 08090222
Plan Review Stops For Permit 08090222
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-02 Cont ID  
Sent By dpalmer Date 2008-10-02 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2008-10-02 Time 10:38 Sent To PC
Notes
2008-10-02 11:22:11REDLINED PLANS.
  
 440.11 FOR AHU DISCONNECTS NOT SHOWN
 410.8 FOR REQUIRED CLEARANCE FOR CLOSET LIGHTS
 SA FOR SMOKE ALARMS TYPICAL PER NFPA-72 11.5.1.1,
 11.8.3
 CONDUCTORS FOR BRANCH CIRCUITS PER 310.16.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-12 Cont ID  
Sent By dpalmer Date 2008-09-12 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2008-09-12 Time 09:16 Sent To PC
Notes
2008-09-12 09:16:35 
  
  
  
 ** DENIED REVIEW **
  
  
  
 1) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK INCLUDING ALL EQUIPMENT AND LABOR SHALL MEET FBC
 108.3. BASED ON RISER AND SCOPE OF WORK AS SUBMITTED
 THE VALUE IS LOW.
  
 2) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 ALL LOADS. THE CALCULATIONS AS SUBMITTED CAN NOT BE
 POSSIBLE. THE RISER ALONE SHOWS A POOL SUB PANEL YET NO
 EQUIPMENT OR LOADS ARE SHOWN ON THE LOAD CALCULATIONS
 FOR THIS.
 WHAT ABOUT THE OTHER LOADS ALL COMING FROM THE SAME
 PANEL?
 NEC 220
 FBC 106.3.5.4, 106.1.1
  
 3) NOTE: PLEASE PROVIDE A LAYOUT/OVERVIEW OF THE
 LOCATIONS OF ALL PANELS.
 FBC 106.1.1.
  
 4) NOTE: PLEASE SEE THAT AN EQUIPMENT GROUNDING
 CONDUCTOR WILL BE REQUIRED FROM METER/MAIN TO THE
 200AMP SUB PANEL UNLESS USING SPECIFIC EMT CONNECTORS
 LISTED FOR EQUIPMENT GROUNDING PATH OUTSIDE.
 110.3.
 IF NOT, PLEASE INCLUDE THE EQUIPMENT GROUNDING
 CONDUCTOR. 250.110,250.122 ETC
  
 5) NOTE: PLEASE INDICATE THE AIC RATINGS FOR
 MAINS/SERVICE EQUIPMENT. 110.9
  
 6) NOTE: PLEASE INCLUDE SIZE OF GROUND ROD AND A
 MINIMUM OF TWO. 250.52(5), 250.56.
  
 7) NOTE: PLEASE VERIFY THE SIZE OF THE CONDUIT. BASED
 ON CONDUITS POSSIBLE LOCATIONS, WHETHER OR NOT SCHEDULE
 80 ETC THE SIZES AS SHOWN ON RISER MAY NOT BE NOT BE OF
 SUFFICIENT SIZE. 240.4,310.16. TABLE 9.
  
 8) NOTE: PLEASE VERIFY SCOPE OF WORK. THE PERMIT
 APPLICATION STATES TO BRING ELECTRICAL IN MAIN HOUSE UP
 TO CODE HOWEVER BASED ON PLANS THIS IS FOR SERVICE
 ONLY. NO PLANS WERE SUBMITTED FOR BRING ELECTRICAL IN
 MAIN HOUSE (RECEPTACLES, LIGHTS ETC).
 FBC 106.3.5.4, 106.1.1 FOR CLARITY AND ADDITIONAL
 INFORMATION ON APPLICATION.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  