| | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK INCLUDING ALL EQUIPMENT AND LABOR SHALL MEET FBC |
| | 108.3. BASED ON RISER AND SCOPE OF WORK AS SUBMITTED |
| | THE VALUE IS LOW. |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | ALL LOADS. THE CALCULATIONS AS SUBMITTED CAN NOT BE |
| | POSSIBLE. THE RISER ALONE SHOWS A POOL SUB PANEL YET NO |
| | EQUIPMENT OR LOADS ARE SHOWN ON THE LOAD CALCULATIONS |
| | FOR THIS. |
| | WHAT ABOUT THE OTHER LOADS ALL COMING FROM THE SAME |
| | PANEL? |
| | NEC 220 |
| | FBC 106.3.5.4, 106.1.1 |
| | |
| | 3) NOTE: PLEASE PROVIDE A LAYOUT/OVERVIEW OF THE |
| | LOCATIONS OF ALL PANELS. |
| | FBC 106.1.1. |
| | |
| | 4) NOTE: PLEASE SEE THAT AN EQUIPMENT GROUNDING |
| | CONDUCTOR WILL BE REQUIRED FROM METER/MAIN TO THE |
| | 200AMP SUB PANEL UNLESS USING SPECIFIC EMT CONNECTORS |
| | LISTED FOR EQUIPMENT GROUNDING PATH OUTSIDE. |
| | 110.3. |
| | IF NOT, PLEASE INCLUDE THE EQUIPMENT GROUNDING |
| | CONDUCTOR. 250.110,250.122 ETC |
| | |
| | 5) NOTE: PLEASE INDICATE THE AIC RATINGS FOR |
| | MAINS/SERVICE EQUIPMENT. 110.9 |
| | |
| | 6) NOTE: PLEASE INCLUDE SIZE OF GROUND ROD AND A |
| | MINIMUM OF TWO. 250.52(5), 250.56. |
| | |
| | 7) NOTE: PLEASE VERIFY THE SIZE OF THE CONDUIT. BASED |
| | ON CONDUITS POSSIBLE LOCATIONS, WHETHER OR NOT SCHEDULE |
| | 80 ETC THE SIZES AS SHOWN ON RISER MAY NOT BE NOT BE OF |
| | SUFFICIENT SIZE. 240.4,310.16. TABLE 9. |
| | |
| | 8) NOTE: PLEASE VERIFY SCOPE OF WORK. THE PERMIT |
| | APPLICATION STATES TO BRING ELECTRICAL IN MAIN HOUSE UP |
| | TO CODE HOWEVER BASED ON PLANS THIS IS FOR SERVICE |
| | ONLY. NO PLANS WERE SUBMITTED FOR BRING ELECTRICAL IN |
| | MAIN HOUSE (RECEPTACLES, LIGHTS ETC). |
| | FBC 106.3.5.4, 106.1.1 FOR CLARITY AND ADDITIONAL |
| | INFORMATION ON APPLICATION. |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |