| 2008-09-12 10:59:06 | |
| | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT A COMPLETED RISER. THE RISER |
| | APPEARS TO SHOW A SUB FEED, HOWEVER NO OTHER PANEL, |
| | SIZE, LOCATION ETC WAS SHOWN. |
| | 110.26,240.24, 408.4. |
| | |
| | 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS AS PLANS |
| | INDICATE NEW ADDITION. 220.87 |
| | |
| | 3) NOTE: PLEASE INDICATE THE MINIMUM FOR THE GROUNDING |
| | ELECTRODE SYSTEM WHICH NEEDS TO INCLUDE TWO GROUND RODS |
| | AND SIZES, COLD WATER PIPE IF METALLIC AND ANY OTHER |
| | PIPE BONDS. |
| | 250.50,250.52(5), 250.56, 250.104 |
| | |
| | 4) NOTE: PLEASE INCLUDE THE AIC RATING OF SERVICE |
| | EQUIPMENT. 110.9 |
| | |
| | 5) NOTE: PLEASE INDICATE THE RISER CONDUITS AND OTHER |
| | TYPES OF CONDUITS. |
| | 230, 110.3, FPL SERVICE STANDARDS 2008. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |