| 2008-09-18 14:45:27 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. I AM IN RECEIPT OF THE LETTER INCLUDED IN THE PERMIT |
| | APPLICATION EXPLAINING THE SITUATION WITH BRITE LITE |
| | SHUTTERS. THE ORIGINAL PERMIT IS EXPIRED; THEREFORE, |
| | NEW PLANS AND A NEW PERMIT APPLICATION ARE REQUIRED |
| | (CANNOT DO A CHANGE OF CONTRACTOR). PLEASE INCLUDE ALL |
| | WORK (INCLUDING THE WORK COMPLETED BY THE FIRST |
| | CONTRACTOR) AS AN OPEN, ACTIVE PERMIT IS REQUIRED IN |
| | ORDER TO OBTAIN FINAL INSPECTION FOR THIS WORK. MY |
| | UNDERSTANDING IS THAT BUCHANAN SCREEN HAS BEEN HIRED TO |
| | RESOLVE OUTSTANDING ISSUES AS WELL AS INSTALL NEW |
| | HURRICANE SHUTTERS. IF THIS IS NOT CORRECT, AND |
| | BUCHANAN OBJECTS TO PERMITTING WORK WHICH THEY DID NOT |
| | INSTALL, PLEASE CONTACT ME IN ORDER TO DISCUSS OPTIONS |
| | TO GET THIS SITUATION RESOLVED. |
| | |
| | 2. PLEASE REVISE THE INSTALLATION SCHEDULE AS FOLLOWS: |
| | |
| | A. THE SHUTTER CONNECTION MOUNTING TYPE SHOULD |
| | CORRELATE WITH ANCHOR CHARTS; FOR INSTANT, WALL MOUNT |
| | A-A (AS SHOWN ON SHEET 3). ALL OF THE MOUNTING TYPES |
| | AND ALL SIX CHARTS WERE HIGHLIGHTED. |
| | |
| | B. PLEASE CLARIFY WHICH ANCHOR YOU ARE USING. THE |
| | INSTALLATION SCHEDULE STATES YOU ARE USING ITW, BUT |
| | BOTH ANCHORS A AND D ARE CIRCLED ON S;HEET 7. USE OF |
| | ANCHOR A, 1/4" TAPCONS, CONNECTION MOUNTING TYPE A-A, |
| | BLOCK SUBSTRATE, REQUIRES USE OF CHART 1 (SEE SHEET 3). |
| | THIS WOULD REQUIRE 6" ANCHOR SPACING, BUT THE |
| | INSTALLATION SCHEDULE SPECIFIES 9"/7". PLEASE REVISE. |