Plan Review Details - Permit 08090125
Plan Review Stops For Permit 08090125
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-25 Cont ID  
Sent By jgomez Date 2008-09-25 Time 10:14 Rev Time 0.00
Received By jgomez Date 2008-09-25 Time 10:14 Sent To PC
Notes
2008-09-25 10:15:41ILLUMINATED AWNING BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- CONTRACTOR'S LICENSE ES0000003 IS FOR AN SPECIALTY
 CONTRACTOR FOR SIGN CONTRACTOR, ELECTRICAL. ACCORDING
 TO PALM BEACH COUNTY LICENSING BOARD THE SIGN
 CONTRACTOR, ELECTRICAL LICENSE DOESN'T ALLOW THIS
 CONTRACTOR TO INSTALL THE AWNING. THIS CONTRACTOR CAN
 ONLY DO THE ELECTRICAL PART OF THE JOB UNLESS THIS
 CONTRACTOR HOLDS ANOTHER LICENSE THAT WILL ALLOW AWNING
 INSTALLATION.
  
 2- CONTRACTOR NEEDS TO UPDATE LICENSE WITH PALM BEACH
 COUNTY. CURRENT STATUS SHOWN ON PALM BEACH COUNTY
 WEBSITE IS EXPIRED.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT
 PICK UP.
  
 4- AWNINGS CAN'T EXTEND MORE THAN 2/3 THE DISTANCE FROM
 THE PROPERTY LINE TO THE NEAREST CURB LINE IN FRONT OF
 THE BUILDING NOR SHALL ANY PORTION BE CLOSER THAN 18
 INCHES TO THE CURB LINE. PROVIDE DRAWING SHOWING
 COMPLIANCE WITH CODE SECTION 3105.1.1.2 OF 2004 FBC.
  
 5- PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH SEC. 3105.4.2.1 OF 2004 FBC REGARDING
 THE AWNING QUICK RELEASE. PER BUILDING OFFICIAL THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS
 WHICH WILL BE APPROVED BY THE BUILDING OFFICIAL.
  
 6- PROVIDE AWNING SPECIFICATIONS TO SHOW COMPLIANCE
 WITH THE FLAME RESISTANCE REQUIREMENTS OF SEC. 3105.3.1
 OF 2004 FBC. SHOW COMPLIANCE WITH NFPA 701.
  
 7- PER BUILDING OFFICIAL, NEED TO PROVIDE A LETTER
 SIGNED BY THE OWNER OF THE BUILDING (NOT THE TENANT) TO
 ACKNOWLEDGE HIS/HER RESPONSIBILITY TO HAVE THE AWNING
 COVER REMOVED PRIOR TO ANY WIND EVENT WITH PROJECTED
 WIND SPEEDS OF 75 MPH OR GREATER.
  
 8- UPDATE DRAWINGS. CURRENT REVISIONS ARE 2007 REVISONS
 OF 2004 FBC, NOT 2006. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-19 Cont ID  
Sent By btrobaug Date 2008-09-19 Time 10:07 Rev Time 0.00
Received By btrobaug Date 2008-09-19 Time 10:06 Sent To B
Notes
2008-09-19 10:06:59 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} A DISCONNECTING MEANS PER 600.6 FOR THE CIRCUITS
 REQUIRED BY 600.5 SHOULD BE LOCATED ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 16:19 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 16:19 Sent To E
Notes
2008-09-10 16:20:11TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-25 Cont ID  
Sent By jgomez Date 2008-09-25 Time 10:15 Rev Time 0.00
Received By jgomez Date 2008-09-05 Time 09:18 Sent To  
Notes
2008-09-05 09:18:24TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-10 Cont ID  
Sent By mflis Date 2008-09-10 Time 13:24 Rev Time 0.00
Received By mflis Date 2008-09-10 Time 13:24 Sent To  
Notes
2008-09-10 13:24:49ZONING REVIEW: FAILED
  
 ** PERMIT SHOULD INCLUDE PROPERTY SURVEY OR SEALED SITE
 PLAN INDICATING TO-SCALE, LOCATIONS AND DIMENSION OF
 AWNINGS.
 ** AWNINGS SHOULD BE FULLY DIMENSIONED, INCLUDING
 HEIGHT OF GROUND
  
 MATT FLIS - 822-1445