Plan Review Details - Permit 08090075
Plan Review Stops For Permit 08090075
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-03 Cont ID  
Sent By shill Date 2008-10-03 Time 09:02 Rev Time 0.00
Received By shill Date 2008-10-03 Time 09:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-23 Cont ID  
Sent By shill Date 2008-09-23 Time 13:55 Rev Time 0.00
Received By shill Date 2008-09-23 Time 13:55 Sent To  
Notes
2008-09-23 14:12:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. N/A.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE.
 USE OF REMOVABLE SHUTTERS MUST BE APPROVED BY THE
 BUILDING OFFICIAL, SEE OTHER COMMENTS.
  
 3. USE OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS
 MUST BE APPROVED BY THE BUILDING OFFICIAL THROUGH
 SUBMITTAL OF A PRESTORM PREPARATION PLAN. SEE ATTACHED,
 ITEM 13. THIS PLAN CAN BE SUBMITTED VIA EMAIL OR AT THE
 FRONT COUNTER PRIOR TO RESUBMITTAL OF THE PERMIT
 APPLICATION.
  
 4. AS SCANNING IS DONE IN BLACK AND WHITE, PLEASE
 REVISE PLAN TO CLEARLY SHOW SCOPE OF WORK WITHOUT USE
 OF COLOR CODING.
  
 5. "DOUBLE WINDOWS" REQUIRES USE OF A MULLION. PLEASE
 SUBMIT MULLION PRODUCT APPROVAL, TWO SETS.
 WWW.FLORIDABUILDING.ORG
  
 6. TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS
 REQUIRED FOR PERMIT ISSUANCE. FBC*106.
  
 7. THE APPLICATION STATES THAT FIVE DOORS AND ONE SASH
 IS TO BE REPLACED. THE PLAN SHOWS ONLY FOUR DOORS TO BE
 REPLACED. IT IS NOT CLEAR WHAT "SASH" IS TO BE
 REPLACED; NOTHING NOTED ON THE PLAN, AND THE PRODUCT
 APPROVALS ARE FOR WINDOW REPLACEMENT. A PORTION OF A
 WINDOW SHOULD NOT BE REPLACED. GLAZING REPLACEMENT DOES
 NOT REQUIRE A PERMIT, BUT IF THE FRAME IS TO BE
 REPLACED, THE ENTIRE WINDOW UNIT SHOULD BE REPLACED,
 NOT THE SASH ONLY. PLEASE CLARIFY SCOPE OF WORK; SHOW
 ALL PROPOSED WORK ON THE PLAN AND REVISE THE PERMIT
 APPLICATION.
  
 8. PROVIDE A REASONABLE VALUE FOR THIS JOB.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-23 Cont ID  
Sent By shill Date 2008-09-23 Time 14:12 Rev Time 0.00
Received By shill Date 2008-09-23 Time 12:20 Sent To  
Notes
2008-09-23 12:20:59TO "SHILL" DESK/PER "RBROWN"