Plan Review Details - Permit 08090067
Plan Review Stops For Permit 08090067
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-03-02 Cont ID  
Sent By jgomez Date 2009-03-02 Time 15:53 Rev Time 0.00
Received By jgomez Date 2009-03-02 Time 15:52 Sent To PC
Notes
2009-03-02 16:01:24BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- NEED TO COMPLY WITH THE RESIDENTIAL SWIMMING BARRIER
 REQUIREMENTS OF SEC. R4101.17 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR FINAL INSPECTION. NEED BARRIER
 REQUIREMENTS FROM THE HOUSE TO THE POOL. BARRIER
 REQUIREMENTS FROM OUTSIDE TO THE POOL WAS ADDRESSED
 WITH FENCE PERMIT 09020064. NEED TO COMPLY WITH THE
 BARRIER REQUIREMENTS FROM THE HOUSE TO THE POOL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-14 Cont ID  
Sent By jgomez Date 2009-01-14 Time 09:32 Rev Time 0.00
Received By jgomez Date 2009-01-14 Time 08:12 Sent To PC
Notes
2009-01-14 09:34:30RESIDENTIAL (R3) POOL/SPA BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 ***NOTE: COMMENTS FROM FIRST CHECKLIST WERE NOT
 ADDRESSED.
  
 1- CLEARLY SPECIFY HOW COMPLYING WITH THE RESIDENTIAL
 SWIMMING BARRIER REQUIREMENTS OF SEC. R4101.17 OF 2004
 FLORIDA RESIDENTIAL CODE. NEED TO SPECIFY HOW TO
 PREVENT ACCESS TO THE POOL FROM THE HOUSE AND ACCESS TO
 THE POOL FROM OUTSIDE. PLANS SUBMITTED DON'T SPECIFY IF
 THERE IS A FENCE AROUND PERIMETER OF PROPERTY AND IF
 HOUSE DOORS AND WINDOWS THAT HAVE ACCESS TO THE POOL
 HAVE EXIT ALARMS. PROVIDE COMPLETE INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-24 Cont ID  
Sent By jgomez Date 2008-09-24 Time 14:03 Rev Time 0.00
Received By jgomez Date 2008-09-24 Time 13:56 Sent To Z
Notes
2008-09-24 14:13:22RESIDENTIAL (R3) POOL/SPA BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- CLEARLY SPECIFY HOW COMPLYING WITH THE RESIDENTIAL
 SWIMMING BARRIER REQUIREMENTS OF SEC. R4101.17 OF 2004
 FLORIDA RESIDENTIAL CODE. NEED TO SPECIFY HOW TO
 PREVENT ACCESS TO THE POOL FROM THE HOUSE AND ACCESS TO
 THE POOL FROM OUTSIDE. PLANS SUBMITTED DON'T SPECIFY IF
 THERE IS A FENCE AROUND PERIMETER OF PROPERTY AND IF
 HOUSE DOORS AND WINDOWS THAT HAVE ACCESS TO THE POOL
 HAVE EXIT ALARMS. PROVIDE COMPLETE INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-27 Cont ID  
Sent By btrobaug Date 2009-10-27 Time 12:47 Rev Time 0.00
Received By btrobaug Date 2009-10-27 Time 12:46 Sent To  
Notes
2009-10-27 12:47:35 
  
  
 RELOCATE POOL EQUIPMENT./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-23 Cont ID  
Sent By btrobaug Date 2009-02-23 Time 12:18 Rev Time 0.00
Received By btrobaug Date 2009-02-23 Time 11:56 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-29 Cont ID  
Sent By btrobaug Date 2008-12-29 Time 10:09 Rev Time 0.00
Received By btrobaug Date 2008-12-29 Time 09:41 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-09-18 Cont ID  
Sent By btrobaug Date 2008-09-18 Time 16:49 Rev Time 0.00
Received By btrobaug Date 2008-09-18 Time 16:17 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-09-19 Cont ID  
Sent By mperson Date 2008-09-19 Time 11:57 Rev Time 0.00
Received By mperson Date 2008-09-19 Time 11:57 Sent To B
Notes
2008-09-19 12:00:25NOTE: AUX. POOL HAS A GAS HEATER AND A GAS PERMIT
 #08090073 HAS BEEN APPLIED FOR.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-10-20 Cont ID  
Sent By btrobaug Date 2009-10-20 Time 14:42 Rev Time 0.00
Received By btrobaug Date 2009-10-20 Time 14:42 Sent To Z
Notes
2009-10-20 14:48:32TO R11./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-03-10 Cont ID  
Sent By adarroug Date 2009-03-10 Time 10:09 Rev Time 0.00
Received By adarroug Date 2009-03-10 Time 10:09 Sent To Z
Notes
2009-03-10 10:09:53TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 11:55 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 11:55 Sent To Z
Notes
2009-02-09 11:55:29TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-16 Cont ID  
Sent By adarroug Date 2008-12-16 Time 10:44 Rev Time 0.00
Received By adarroug Date 2008-12-16 Time 10:44 Sent To Z
Notes
2008-12-16 10:44:53TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 08:50 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 08:50 Sent To E
Notes
2008-09-10 08:52:04TO "E" BOX--OTHER TRADES TO REVIEW BEFORE ZONING, PER
 MAGGIE CRUZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-16 Cont ID  
Sent By adarroug Date 2008-12-16 Time 10:35 Rev Time 0.00
Received By adarroug Date 2008-09-04 Time 09:52 Sent To  
Notes
2008-09-04 09:52:34TO "Z" BOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-10-21 Cont ID  
Sent By kstevens Date 2009-10-21 Time 16:44 Rev Time 0.00
Received By kstevens Date 2009-10-21 Time 16:44 Sent To  
Notes
2009-10-21 16:44:52REVISION OK -- CHANGED POOL EQUIPMENT & PIPING FROM
 NORTH SIDE TO SOUTH SIDE OF HOUSE.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-02-27 Cont ID  
Sent By kstevens Date 2009-02-27 Time 10:19 Rev Time 0.00
Received By kstevens Date 2009-02-27 Time 10:19 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-01-13 Cont ID  
Sent By kstevens Date 2009-01-13 Time 14:24 Rev Time 0.00
Received By kstevens Date 2009-01-13 Time 14:24 Sent To B1
Notes
2009-01-13 14:28:30DENIED
 REFERENCE:
 FBC-2004 BUILDING
  
 1. SHTS 1 & 2 OF 4. APPROVED SURFACE SKIMMERS ARE
 REQUIRED AND SHALL BE INSTALLED IN STRICT ACCORDANCE
 WITH THE MANUFACTURES INSTALLATION INSTRUCTIONS.
 SECTION 424.2.12.2.2. NO SKIMMER IS INDICATED ON THE
 SPA POOL LAYOUT OR ON THE SPA PIPING SCHEMATIC. PLEASE
 SHOW THE REQUIRED SKIMMER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-19 Cont ID  
Sent By mperson Date 2008-09-19 Time 11:16 Rev Time 0.00
Received By mperson Date 2008-09-19 Time 11:16 Sent To G
Notes
2008-09-19 11:57:20PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEETS 1, 2 & 4 OF 4, THE POOL AND AUX. POOL ARE NOT
 COMPLIANT WITH FBC-2004 BUILDING CHAPTER 4 (PRIVATE
 SWIMMING POOLS), SECTION 424.2.6.6.4 SUCTION INLETS PER
 PUMP. A MINIMUM OF TWO SUCTION INLETS SHALL BE PROVIDED
 FOR EACH PUMP IN THE SUCTION INLET SYSTEM, SEPARATED BY
 A MINIMUM OF 3 FEET (914 MM) OR LOCATED ON TWO
 DIFFERENT PLANES; I.E., ONE ON THE BOTTOM AND ONE ON
 THE VERTICAL WALL, OR ONE EACH ON TWO SEPARATE VERTICAL
 WALLS. THESE SUCTION INLETS SHALL BE PLUMBED SUCH THAT
 WATER IS DRAWN THROUGH THEM SIMULTANEOUSLY THROUGH A
 COMMON LINE TO THE PUMP. WHEN A SKIMMER IS USED IN
 CONJUNCTION WITH A SINGLE MAIN OUTLET TO MEET THE
 REQUIREMENTS OF THIS SECTION, THE COMMON SUCTION LINE
 MUST BE IN COMPLIANCE WITH SECTION 424.2.6.6.3 SUCH
 THAT A VACUUM CANNOT BE DRAWN ON ANY SINGLE MAIN OUTLET
 OR SKIMMER.
 *NOTE: SHEET 1 OF 4, POOL PLAN ONLY INDICATES ONE 8" X
 32" MAIN DRAIN FOR THE POOL AND AUX. POOL. SHEET 2 OF 4
 MAIN DRAIN DETAIL INDICATES ONE 8" X 32" MAIN DRAIN
 (MIN. TWO REQUIRED SEPERATED A MIN. 3'), HOWEVER THE
 AUX. POOL SECTION IS INDICATING (2) 8" AUX. POOL DRAINS
 W. APPROVED GRATES SECURED W. SCREWS. SHEET 4 OF 4,
 SCHEMATICS FOR THE POOL AND SPA ARE INDICATING
 "MAINDRAINS" AS IF MORE THAN ONE MAIN DRAIN IS BEING
 INSTALLED. PLEASE CORRECT AND CORRELATE PLANS COMPLIANT
 WITH SECTION 424.2.6.6.4.
  
 2. FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (ADD TO NOTES)
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2009-11-12 Cont ID  
Sent By jroach Date 2009-11-12 Time 17:13 Rev Time 0.00
Received By jroach Date 2009-11-12 Time 17:13 Sent To  
Notes
2009-11-12 17:13:30PROVISO
  
 1. POOL EQUIPMENT SHALL BE A MINIMUM OF SIX (6) FEET
 FROM THE SIDE PROPERTY LINE.
  
 2. ALL POOLS SHALL BE COMPLETELY ENCLOSED BY A
 PERMANENT FENCE OF NOT LESS THAN FOUR (4) FEET IN
 HEIGHT PRIOR TO ISSUANCE OF A CERTIFICATE OF COMPLETION
 FOR THE POOL. A ???BABY FENCE??? DOES NOT SATISFY THIS
 REQUIREMENT.
  

Review Stop Z ZONING
Rev No 4 Status P Date 2009-03-17 Cont ID  
Sent By mcruz Date 2009-03-17 Time 19:58 Rev Time 0.00
Received By mcruz Date 2009-03-17 Time 19:52 Sent To I
Notes
2009-03-17 20:54:06PASSED W/PROVISO: AS NOTED ON PLANS: FINAL C.O. SHALL
 NOT BE REC'D UNTIL A DETAIL OF THE SCREENING OF THE
 POOL EQUIPMENT, AS STATED UNDER PERMIT # 08090069, HAS
 BEEN REC'D. PURSUANT TO THE BEAR LAKES ESTATE NORTH
 DECLARATION OF COVENANTS AND RESTRICTIONS, SECTION VII,
 ARCHITECTURAL CONTROLS, SUBSECTION C: .... ALL EXTERIOR
 SERVICE ELEMENTS SUCH AS AIR CONDITIONER COMPRESSORS,
 SHALL BE SHOWN ON THE PLANS AND PLACED IN AN
 INCONSPICUOUS LOCATION. PREFERABLY AT THE REAR OF THE
 RESUDENCE, SCREENED FROM VIEW WITH FENCING AND
 LANDSCAPING. ....
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2009-02-20 Cont ID  
Sent By mcruz Date 2009-02-20 Time 08:50 Rev Time 0.00
Received By mcruz Date 2009-02-20 Time 08:45 Sent To E
Notes
2009-02-20 08:49:43PLANNING AND ZONING DEPT: ***ZONING FAILED - 2ND
 RESUB***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. REPEAT COMMENT: PURSUANT TO THE THE BEAR LAKES
 ESTATES NORTH DECLARATION OF CEVENANTS AND
 RESTRICTIONS, SECTION VII, ARCHITECTURAL CONTROLS,
 SUBSECTION K: POOL AND/OR PATIO ENCLOSURES. POOL AND/OR
 PATIO ENCLOSURE FRAMING AND SCREENING MUST BE DARK IN
 COLOR. THE COLOR AND SPECIFICATIONS FOR THE
 AFOREMENTIONED ENCLOSURE AND SCREENING SHALL REQUIRE
 APPROVAL OF THE ARCHITECTURAL REVIEW BOARD (A.R.B.)
 [SEE ATTACHED, COPY PROVIDED].
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2008-12-22 Cont ID  
Sent By mcruz Date 2008-12-22 Time 12:24 Rev Time 0.00
Received By mcruz Date 2008-12-17 Time 12:48 Sent To E
Notes
2008-12-22 12:24:22PLANNING AND ZONING DEPT: ***ZONING FAILED - 1ST
 RESUB***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. REPEAT COMMENT: PURSUANT TO THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS, SECTION,
 94-304(D)(2)(B)+(C):
 B. EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 NEW COMMENT: PURSUANT TO THE BEAR LAKES ESTATE NORTH
 DECLARATION OF COVENANTS AND RESTRICTIONS, SECTION VII,
 ARCHITECTURAL CONTROLS, SUBSECTION K: POOL AND/OR PATIO
 ENCLOSURES. POOL AND/OR PATIO ENCLOSURE FRAMING AND
 SCREENING MUST BE DARK IN COLOR. THE COLOR AND
 SPECIFICATIONS FOR THE AFOREMENTIONED ENCLOSURE AND
 SCREENING SHALL REQUIRE APPROVAL OF THE ARCHITECTURAL
 REVIEW BOARD (A.R.B.) [SEE ATTACHED, COPY PROVIDED].
  
 NOTE: IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT TO
 OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By mcruz Date 2008-09-26 Time 17:21 Rev Time 0.00
Received By mcruz Date 2008-09-26 Time 17:02 Sent To  
Notes
2008-09-26 17:21:25***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION,
 94-304(D)(2)(B) AND (C):
 B. EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 3. INDICATE HEIGHT AND SETBACK DIMENSIONS OF DECK TO
 ALL ADJACENT PROPERTY LINES. PURSUANT TO THE ZLDR,
 SECTION 94-305(A)7): STEPS, OPEN UNCOVERED PORCHES OR
 STOOPS, AND OPEN TERRACES WHICH ARE THREE FEET OR LESS
 ABOVE GRADE MAY ENCROACH INTO ANY REQUIRED SETBACK AREA
 TO A POINT NOT CLOSER THAN TWO FEET TO THE PROPERTY
 LINE. ANY GRADE DIFFERENTIAL BETWEEN THE ENCROACHING
 STEP, PORCH, STOOP, OR TERRACE AND ADJACENT PROPERTY
 SHALL BE STRUCTURALLY RETAINED AND POSITIVELY DRAINED
 IN A MANNER THAT WILL PREVENT ANY DRAINAGE DISCHARGE TO
 ANY PROPERTY CONTIGUOUS TO THE SIDE OR REAR PROPERTY
 LINES.
  
 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES. AS PER
 SECTION94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO AN REQUIRED
 SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  