 |
Plan Review Details - Permit 08090055
| Plan Review Stops For Permit 08090055 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-12-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-12-05 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-12-05 |
Time |
08:29 |
Sent To |
|
|
| Notes |
| 2008-12-05 09:23:04 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- PROVIDE COMPLETE ENGINEERING PACKAGE FOR PROPOSED | | | GUARDRAIL SYSTEM. PLEASE PROVIDE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS OR DELAYS. | | | 2- FLUE CALCULATIONS NEED TO HAVE THE NAME AND | | | SIGNATURE OF PERSON RESPONSIBLE FOR THE CALCULATIONS. | | | PLEASE RESUBMIT WITH THIS INFORMATION. | | | 3- ELEVATION CERTIFICATE TO BE HANDLED TO THE BUILDING | | | INSPECTOR. | | | ***NOTE: MINIMUM FINISH FLOOR ELEVATION FOR FLOOD ZONE | | | A5 IS 7.5'. | | | 4- REVISE ENERGY CALCULATIONS FOR GARAGE/GUEST ROOM | | | BUILDING. ADJACENT WALLS TO HAVE R-11 MIN. AS REQUIRED | | | BY SEC. 13-602.1.C.1.1 FBC 2004. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-10-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-10-28 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-10-28 |
Time |
14:26 |
Sent To |
ENG |
|
| Notes |
| 2008-10-28 17:20:28 | RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW SECOND | | | CHECKLIST. | | | REVIEW UNDER 2004 FBC RESIDENTIAL WITH 2007 REVISIONS. | | | | | | 1- ENERGY CALCULATIONS: | | | A) ENGINEER WHO SIGNED AND SEALED ENERGY CALCULATIONS | | | NEED TO PROVIDE HIS INFORMATION AS REQUIRED BY CHAPTER | | | 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA | | | ADMINISTRATIVE CODE. | | | | | | B) ENERGY CALCULATIONS FOR GARAGE/LIVING AREA STRUCTURE | | | ARE NOT SIGNED AND SEALED AND THEY HAVE THE COPY OF THE | | | ENGINEER SIGNATURE. THESE CALCULATIONS NEED TO HAVE | | | ORIGINAL SIGNATURE-AND SEAL. AND PROVIDE ENGINEER'S | | | INFORMATION AS REQUIRED BY SEC. 61G15-23.002 FLORIDA | | | ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. | | | | | | C) ENERGY CALCULATIONS FOR GARAGE/LIVING AREA STRUCTURE | | | IS MISSING THE INFORMATION FOR GARAGE ADJACENT WALL | | | AREA AND GARAGE ADJACENT CEILING AREA. PROVIDE COMPLETE | | | INFORMATION AS REQUIRED. | | | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ALL PRODUCT APPROVALS (TWO SETS. ONLY ONE SET WAS | | | APPROVED AND STAMPED) AS REQUIRED BY SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 3- GUARDRAIL SYSTEM: | | | A) DETAILS AND SPECIFICATIONS FOR ENGINEERED GUARDRAIL | | | SYSTEM NEED TO HAVE ENGINEER'S ORIGINAL SEAL, SIGNATURE | | | AND DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE AND | | | SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. | | | | | | B) ENGINEER TO DESIGN THIS SYSTEM PER FBC 2004, WHICH | | | IS THE CODE IN EFFECT. SPECIFY FBC 2004 WITH 2007 | | | REVISIONS ON BUILDING CODE DESIGN INFORMATION. | | | | | | C) ENGINEER TO IDENTIFY PROJECT ADDRESS. | | | | | | D) ENGINEER TO CLEARLY IDENTIFY ALL DESIGN INFORMATION | | | INFORMATION THAT IS SPECIFIC TO THIS PROJECT. EG: GLASS | | | THICKNESS, RAILING HEIGHT, WIND EXPOSURE, ETC. SEC. | | | 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY | | | COMPLIANCE WITH SECTIONS . R301, R311.5 AND R312 OF | | | 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 4- CHIMNEY FLUE: | | | A) REVISED DRAWING SHOWS THREE FLUES. THERE IS ONLY ONE | | | APPLIANCE. COMPLY WITH SEC. R1001.10 OF 2004 FLORIDA | | | RESIDENTIAL CODE. THIS SECTION ONLY ALLOWS TWO FLUES | | | PER APPLIANCE. | | | | | | B) REVISE SIZE OF FLUE. SEE SEC. R1001.12.2. SIZE SHOWN | | | ON DRAWINGS DON'T COMPLY. ALSO, PROVIDE CALCULATIONS | | | SHOWING HOW FLUE SIZE WAS OBTAINED. INCLUDE FLUE HEIGHT | | | MEASURED FROM FLOOR OF COMBUSTION CHAMBER TO TOP OF | | | FLUE. SEE FIGURE R1001.12.2 OF 2004 FLORIDA RESIDENTIAL | | | CODE. | | | | | | C) REVIEW ISOKERN SPECIFICATIONS FOR FLUE LINING | | | SUBMITTED. THEY DON'T PROVIDE INFORMATION FOR FLUE TO | | | BE SPLIT INTO TWO (OR THREE AS SHOWN ON DRAWINGS). | | | REVISE AS REQUIRED TO MATCH. | | | | | | 5- NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS OF | | | BEING RECORDED IF WORK IS NOT STARTED. SEC. 713.13 | | | FLORIDA STATUTE. PROVIDE RE-RECORDED NOTICE OF | | | COMMENCEMENT. | | | ***NOTE: THIS MAY BE PROVIDED LATER AT TIME OF PERMIT | | | PICK UP TO AVOID EXPIRATION OF IT. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-09-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-09-16 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-09-16 |
Time |
11:44 |
Sent To |
ENG |
|
| Notes |
| 2008-09-16 17:02:56 | RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE AND 2004 FBC | | | WITH 2007 REVISIONS. | | | | | | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N JOG RD. | | | (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE FOR THE | | | CHANGE OF USE ON THE FIRST FLOOR OF GARAGE BUILDING. | | | BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF | | | FEES ARE DUE. | | | | | | 2- HOUSE IS LOCATED IN FLOOD ZONE A5 WITH BASE FLOOD | | | ELEVATION OF 7.0'. NEED TO ELEVATE FINISH FLOOR | | | BUILDING ON BOTH BUILDINGS UP TO 7.5' MINIMUM AS | | | REQUIRED BY CITY ORDINANCE SEC. 94-546(B)(1). SURVEY | | | SUBMITTED STATES FINISH FLOOR ELEVATION OF 6.89' FOR | | | GARAGE BUILDING AND 7.42' FOR MAIN HOUSE. THESE FINISH | | | FLOOR ELEVATIONS NEED TO BE RAISED. | | | ***NOTE: ELEVATION CERTIFICATE WILL BE REQUIRED TO | | | VERIFY FINISH FLOOR ELEVATION. | | | | | | 3- PROVIDE COMPLETE SPECIFICATIONS FOR OUTDOOR | | | FIREPLACE AND PROVIDE DOCUMENTATION TO CLARIFY WHY | | | CHIMNEY IS NOT REQUIRED FOR THIS TYPE OF FIREPLACE. | | | | | | 4- WINDERS IN GARAGE STAIRS NEED TO COMPLY WITH SEC. | | | R311.5.3.2 OF 2004 FLORIDA RESIDENTIAL CODE. COMPLY | | | WITH THE MIN. 6" WINDERS AT NARROWER END. SEE ATTACHED | | | PICTURE FROM COMMENTARY CODE. | | | | | | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR: | | | A) INSWING ENTRY DOORS WITH SIZE AS SHOWN ON PLANS. | | | | | | B) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS. | | | ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL | | | COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED | | | TO SUBMIT COMPLETE REPORT. | | | | | | C) CLARIFY WHERE IS DOOR WITH FLORIDA PRODUCT APPROVAL | | | FL3030-R2 GOING TO BE INSTALLED. AND, CHECK DESIGN | | | PRESSURES WITH THOSE CALCULATED BY THE ENGINEER OF | | | RECORD TO MAKE SURE THEY WILL BE OK FOR THIS PROJECT. | | | | | | D) CLARIFY WHERE IS DOOR WITH FLORIDA PRODUCT APPROVAL | | | FL4940 GOING TO BE INSTALLED. IF IT'S FOR GARAGE SIDE | | | DOOR, THEN NEED TO PROVIDE ANOTHER PRODUCT APPROVAL | | | BECAUSE THIS ONE DOESN'T MEET THE DESIGN PRESSURES | | | CALCULATED BY THE ENGINEER. | | | | | | E) GARAGE OVERHEAD DOORS: FLORIDA PRODUCT APPROVAL | | | FL1652 SUBMITTED DOESN'T RESIST THE CALCULATED DESIGN | | | PRESSURES. | | | | | | 6- ROLLADEN ROLL SHUTTERS: | | | A) PROVIDE COMPLETE INSTALLATION SCHEDULE AS REQUIRED | | | BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS | | | IMPACT PROTECTION. SEE ATTACHED COPY. | | | B) COMPLETE INFORMATION ON SHEET 21 OF 21 OF NOA | | | 08-0313.07 SUBMITTED. | | | C) CLEARLY MARK ON SHUTTER DRAWINGS SPECIFIC CHARTS TO | | | BE USED TO VERIFY COMPLIANCE WITH PRODUCT APPROVAL AND | | | PROPOSED INSTALLATION. | | | | | | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 8- ENERGY CALCULATIONS: | | | A) COMPLETE INFORMATION ON TOP. INCLUDING BUILDER | | | INFORMATION. | | | B) THIS IS NOT NEW CONSTRUCTION OR ADDITION, BUT | | | EXISTING. ENERGY CALCULATIONS FOR MAIN HOUSE AND GARAGE | | | BUILDING NEED TO BE REVISED ACCORDINGLY. | | | C) CLARIFY WHY THE WALL R-VALUE IS R=2.0 FOR GARAGE | | | BUILDING. | | | | | | 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW | | | HANDRAILS AND FOR NEW BALCONY GLASS GUARDRAILS TO | | | VERIFY COMPLIANCE WITH TABLE R301.5, SEC. R311.5 AND | | | SEC. R312 OF 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 10- PROVIDE COMPLETE DOCUMENTATION SHOWING HOW CHIMNEY | | | FLUE COMPLIES WITH FIGURE R1001.12.2 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 11- SPECIFY HOW IS THE ROOF TILE GOING TO BE FASTENED | | | AS REQUIRED BY SEC. 106.1.1.2 OF CITY AMENDMENTS TO FBC | | | 2004. CHECK PRODUCT APPROVAL FOR PROPER PRODUCT TO BE | | | USED TO RESIST THE CALCULATED UPLIFT LOADS. IF USING | | | ANY TYPE OF ADHESIVE THEN PROVIDE SUCH PRODUCT | | | APPROVAL. IF USING SCREWS, THEN SPECIFY SIZE AND NUMBER | | | OF THEM. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2009-11-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-11-23 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-11-23 |
Time |
10:04 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-06-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-06-04 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-06-04 |
Time |
08:11 |
Sent To |
PC |
|
| Notes |
| 2009-06-04 08:12:50 | STAMPED, LOW VOLTAGE IS REQUIRED OT BE UNDER SEPARATE | | | PERMITS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-12-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-04 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-04 |
Time |
08:49 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-22 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-22 |
Time |
14:01 |
Sent To |
PC |
|
| Notes |
| 2008-10-22 14:01:24 | ** DENIED REVIEW** | | | | | | 1) NOTE: THERE IS ONE MINOR COMMENT HOWEVER PLANS ARE | | | COMING BACK FOR COMMENTS FROM OTHER TRADES. AS A NEW | | | GUTTER IS BEING INSTALLED FROM THE METER TO THE TWO | | | EXISTING MAINS, PLEASE PROVIDE THE SIZE OF THE | | | CONDUCTOR WHICH WILL BE NEW INSTALLED FROM METER TO | | | GUTTER AND FROM GUTTER TO EACH MAIN. | | | 240.4,310.16,230.70. | | | | | | ** A CALL WAS PLACED TO TEELE AND ASSOCIATES AND LEFT | | | MESSAGE ON DAN'S VOICEMAIL. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-09-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-11 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-11 |
Time |
16:29 |
Sent To |
P |
|
| Notes |
| 2008-09-11 16:30:13 | | | | | | | | | | | | | ** DENIED REVIEW ** | | | | | | | | | | | | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED | | | ON ELECTRICAL PLANS. | | | 2004 FBC W/ 2007 REVISIONS | | | 2004 RESIDENTIAL CODE | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | 2) NOTE: PLEASE VERIFY THE SMOKE DETECTION DEVICES. THE | | | PLANS CALL FOR *SMOKE DETECTORS* WHICH BY DEFINITION IN | | | NFPA-72 ARE DEVICES WHICH WILL DETECT HOWEVER NOT SOUND | | | AN ALARM. SMOKE ALARM (SA)DEVICES ARE DEVICES WHICH | | | DETECT AND SOUND AN ALARM. PLEASE SEE FBC 907, | | | RESIDENTIAL CODE R313 AND NFPA-72 11.5.1.1, 11.8.3. | | | IF THESE DEVICES ARE INDEED SMOKE DETECTORS PLEASE | | | COMPLETE WITH FIRE ALARM PANEL, HORNS/SOUNDING DEVICES | | | ETC. | | | | | | 3) NOTE: PLEASE SEE THE HALLWAY UPSTAIRS AND DOWN | | | STAIRS WILL REQUIRE SOME SORT OF LIGHTING FIXTURES FOR | | | EGRESS. | | | THIS IS ALSO FOR ROOMS 210 AND 201. EITHER HALF SWITCH | | | RECEPTACLE OR SOME SORT OF LISTED LIGHT FIXTURE. | | | 210.70, LS 101 7.8 | | | | | | 4) NOTE: PLEASE PLACE NOTE ON FIXTURE LEGEND FOR THE | | | TYPE OF RECESSED LIGHTS TO MEET FBC 13-606.1.ABC.1.2.4 | | | | | | 5) NOTE: PLEASE CLARIFY THE DINING AREA/BREAKFAST AREA | | | IF ANY ON PLANS. PLEASE SEE 210.52B1, 210.11C1 AND | | | 220.52 FOR CIRCUITING AND LOADS TO BE FIGURED FOR THE | | | RECEPTACLES CIRCUITS IN THESE AREAS. | | | | | | 6) NOTE: PLEASE CLARIFY THE 125AMP 42 MLO. PLEASE | | | VERIFY THAT THIS PANEL IS 42CIRCUITS AT 125AMP RATED. | | | 110.3, 90.7. | | | | | | 7) NOTE: PLEASE COORDINATE INFORMATION ON PANEL | | | SCHEDULE *A* FOR PANEL *B*. PLEASE SEE PANEL *B* | | | SCHEDULE AS THIS INDICATES THE FEEDERS AS #3'S YET THE | | | PANEL SCHEDULE ON PANEL *A* INDICATES #6 ON A 100AMP | | | RATED BREAKER. | | | 240.4,310.16, 215.5 ETC | | | FBC 106.1.1 FOR CLARITY AND COORDINATION. | | | | | | 8) NOTE: PLEASE COORDINATE RISER AND FEEDERS FOR PANEL | | | *G1* AS THE RISER INDICATES #3'S IN AN 1 1/4 INCH | | | CONDUIT YET THE PANEL *G1* NOTES FEEDERS AS #1'S AND 1 | | | 1/2 INCH CONDUIT. | | | 240.4, 310.16, 215.5 | | | FBC 106.1.1 FOR CLARITY AND COORDINATION. | | | | | | 9) NOTE: PLEASE LIST ALL OF THE REQUIRED ARC FAULT | | | PROTECTED CIRCUITS. THE PANEL SCHEDULE(S) LIST AFCI | | | PROTECTION FOR RECEPTACLES HOWEVER BASED ON THE 2002 | | | NEC AND 2005 NEC 210.12 REQUIRES PROTECTION ON ALL | | | OUTLETS IN THESE AREAS. THIS INCLUDES RECEPTACLES, | | | LIGHTS FANS , SMOKE ALARMS (120V) ETC. ALL OUTLETS. | | | | | | 10) NOTE: PLEASE ADJUST PANEL SCHEDULES SO THE | | | CIRCUITING IS SPECIFIC TO ROOMS AND AREAS IN WHICH THEY | | | FEED. THE USE OF *GENERAL RECEPTACLES* GENERAL | | | LIGHTING* IS NOT ACCEPTABLE. PLEASE SEE THIS WAS A | | | CHANGE IN THE 2005 NEC WHICH REQUIRES SPECIFIC. THE | | | FOLLOWING IS TEXT TAKEN DIRECTLY FROM THE NEC. | | | | | | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | | SECTION.* | | | 408.4, 310.16, 240.4 ETC | | | FBC 106.3.5.4 | | | | | | 11) NOTE: PLEASE SEE 210.70 FOR AREAS IN WHICH AIR | | | HANDLER UNITS ARE LOCATED WHICH APPEAR TO ABOVE | | | CEILING(S) IN ATTIC AREAS WHICH REQUIRED SERVICE | | | LIGHTS. | | | AN EXAMPLE WOULD BE AHU #2. | | | | | | 12) NOTE: PLEASE SEE 410.8 FOR ASSUMED SHELVING AREAS | | | IN CLOSETS AND MINIMUM REQUIRED CLEARANCES FOR FIXTURES | | | FROM COMBUSTIBLES. PLEASE SEE LINEN CLOSET 212 FOR | | | EXAMPLE AS BASED ON THE SIZE OF THE CLOSET AND THE | | | ASSUMED DISTANCE FOR SHELVING IN THE NEC, THIS FIXTURE | | | ABOVE THE DOOR APPEARS IT MAY BE TOO CLOSE. PLEASE | | | VERIFY THIS AND PROVIDE INFORMATION. | | | IF THIS HAD BEEN THE ONLY COMMENT IT WOULD HAVE BEEN | | | REDLINED AND VIF. | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2008-12-05 |
|
|
Cont ID |
|
| Sent By |
dlauderm |
Date |
2008-12-05 |
Time |
06:56 |
Rev Time |
0.00 |
| Received By |
dlauderm |
Date |
2008-12-05 |
Time |
06:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2008-12-01 |
|
|
Cont ID |
|
| Sent By |
dlauderm |
Date |
2008-12-01 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
dlauderm |
Date |
2008-12-01 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2008-10-30 13:13:59 | PASSED, PER REVIEW BY ENGINEERING STORMWATER ENGINEER, | | | JEFF RENAULT. | | | EMAIL SENT TO DEAN LAUDERMILK ON 10-01-08: "I HAVE | | | REVIEWED THE PROPOSED GRADING AND DRAINAGE PLANS AND | | | THE DRAINAGE CALCULATIONS FOR THE ABOVE PROJECT. THE | | | PROJECT INVOLVES THE RENOVATION OF AN EXISTING SINGLE | | | FAMILY RESIDENCE. THE EXISTING FINISH FLOOR ELEVATIONS | | | ARE MORE THAN 1' ABOVE THE ROADWAY CROWN ELEVATION OF N | | | FLAGLER DRIVE. WATER QUALITY FOR THE SITE IS BEING | | | PROVIDED BY YARD DRAINS , PIPING , SEDIMENT TRAPS AND | | | EXFILTRATION TRENCH. I RECOMMEND APPROVAL OF THE | | | STORMWATER FEATURES OF THIS PROJECT AS PRESENTED IN THE | | | SUBMITTAL. SHOULD YOU HAVE ANY QUESTIONS , PLEASE | | | CONTACT ME." |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2008-09-17 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-09-17 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-09-17 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2008-09-17 15:52:21 | FAILED FOR FOLLOWING REASONS: | | | | | | 1. PLEASE SHOW ON DRAWINGS THE TURBIDITY BARRIER | | | DETAILS OF POLLUTION PREVENTION . PLEASE SHOW ON | | | DRAWINGS THE TURBIDITY BARRIER AROUND CATCH BASINS, ANY | | | OUT FALLS OR LAKES IF YOU HAVE ETC DURING CONSTRUCTION | | | AND ALL DEMOLITION PHASE. HEIGHT OF BARRIER SHOULD BE | | | HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES. | | | | | | 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO. | | | 4060-07: | | | | | | ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH | | | EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY | | | APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE | | | FOLLOWING: | | | | | | 1. EROSION CONTROL, AND | | | 2. LAND STABILIZATION | | | | | | THE AMOUNT OF THE EROSION CONTROL AND LAND | | | STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER | | | OF RECORD USING THE CURRENT CITY COST SCHEDULE AND | | | VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT. | | | PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION | | | SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION. | | | | | | UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN | | | FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL | | | TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE | | | MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS. | | | | | | A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM | | | THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR. | | | | | | 3. PLEASE SHOW ON DRAWINGS DUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, & LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | | | | 4. PLEASE SHOW ON STORM WATER QUALITY CALCULATION THAT | | | YOU HAVE CONSIDERED FLOOD ZONE AREA, & 5,10, 25, 50, | | | 100 YEAR FLOOD CRITERIA AND CROWN OF THE ROAD WHEN YOU | | | DETERMINE THE FIRST FLOOR ELEVATION. FIRST FLOOR | | | ELEVATION SHOULD BE ATLEAST 1 FOOT HIGHER THAN HIGHEST | | | CROWN OF THE ROAD. | | | | | | 5. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE | | | SO, WE CAN SEE THE LAYOUT OF STORM WATER PIPES FROM ALL | | | OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE | | | CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR | | | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET | | | DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL | | | THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL | | | ENVRONMENTAL REPORT. | | | | | | 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST, AROUND | | | YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET | | | FLOODED AND HAVE ENOUGH DRAINS. | | | | | | 7. PLEASE PROVIDE A COPY OF GEO-TECH REPORT & STORM | | | WATER QUALITY CALCULATIONS TO 1000 45TH STREET FOR | | | THEIR APPROVAL BEFORE WE ISSUE A PERMIT. | | | | | | 8. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G. | | | OF 1000 45TH STREET BEFORE WE ISSUE A PERMIT. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI 805-6723 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2008-12-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-04 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-04 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2008-12-04 12:23:27 | | | | | | | PASSED/PROVISO | | | | | | GAS PIPE TO WATER HEATER REQUIRED TO BE 1-1/4" BUT | | | SHOWN AS 3/4" REVISION REQUIRED FOR GAS RISER DIAGRAM. | | | TABLE 402.4(2) | | | | | | | | | | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2008-10-24 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-10-24 |
Time |
11:06 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2008-10-24 |
Time |
11:06 |
Sent To |
B |
|
| Notes |
| 2008-10-24 11:11:10 | GAS PLAN REVIEW: | | | DENIED **2ND TIME: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND | | | WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE | | | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW | | | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW | | | COMMENTS. | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE SECTION 401.1 SCOPE. | | | NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE | | | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. | | | REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS WITH NO | | | CORRESPONDING LENGTHS INDICATED AND COMPLY ON THE | | | RESUBMITTAL. | | | | | | **RESPONSE NOTED, HOWEVER THE RESUBMITTED PLANS STILL | | | HAVE CUT SECTIONS OF PIPE WITH NO CORRESPONDING LENGTHS | | | BEING INDICATED FOR THEM. IF THERE IS A CUT SECTION OF | | | PIPE THERE SHOULD BE A CORRESPONDING LENGTH INDICATED | | | FOR IT. PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT | | | SECTIONS WITH NO CORRESPONDING LENGTHS INDICATED AND | | | COMPLY ON THE RESUBMITTAL. | | | | | | 2. "OK" COMMENT ADDRESSED. | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | NOTE: REFERENCE COMMENT #1 AND COMPLY. | | | | | | **RESPONSE NOTED, HOWEVER UNTIL COMMENT #1 IS ADDRESSED | | | AND THE WRITTEN DISTANCES ARE CORRELATED WITH THE | | | CORRESPONDING LENGTHS FOR EACH CUT SECTIONS OF PIPE | | | THIS COMMENT WILL REMAIN. | | | | | | 4. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE LIVING | | | ROOM (ROOM #108) GAS FIRE PLACE PER FBC-2004 FUEL GAS | | | CODE SECTION 304. | | | | | | **RESPONSE NOTED, HOWEVER THE CALCULATIONS PROVIDED IN | | | THE RESPONSE LETTER SHOULD BE CLEARLY INDICATED ON PLAN | | | SHEET P202. | | | | | | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | NOTE: THE MP REGULATORS MANUFACTURER SHEETS SHALL | | | CLEARLY INDICATE THE MAKE, MODEL NUMBER, BTU LOAD | | | CAPACITY AND A LISTING FROM A RECOGNIZED TESTING | | | LABORATORY (LISTING EXAMPLES= CSA, AGA OR UL). THE | | | SUBMITTED REAL-FYRE GAS LOG MANUFACTURE SHEETS DO NOT | | | COMPLY WITH THE FOLLOWING. LOG LIGHTERS SHALL BE TESTED | | | IN ACCORDANCE WITH CSA 8. PER FBC-2004 FUEL GAS CODE | | | SECTION 603.1 GENERAL. | | | | | | **NO COMMENT RESPONSE AND THIS COMMENT WAS PARTIALLY | | | ADDRESSED. MANUFACTURE SHEETS FOR THE MP REGULATOR WERE | | | NOT IN THE RESUBMITTAL. | | | | | | **THE FOLLOWING IS A NEW COMMENT. | | | | | | 6. SHEET P202: THE FOLLOWING NOTE WAS ON THE | | | RESUBMITTED GAS RISER "ALL CSST PIPING SHALL BE OMEGA | | | TRACPIPE. SIZING BASED ON MANUFACTURE'S DESIGN | | | STANDARDS AND ALLOWED BY 402.3(2)". PLEASE KNOW THAT | | | THE OMEGAFLEX TRACPIPE TABLES DO NOT HAVE A EHD 30 | | | LISTED IN THEIR TABLES NOR DO THEY HAVE AN APPROVED | | | TABLE TO REVIEW TO. PLEASE KNOW THAT FOR 0.5 PSI | | | NAT/GAS TABLE 402.4(14) FROM THE FBC-2004 FUEL GAS CODE | | | WILL BE USED FOR PLAN REVIEW. PLEASE DELETE THE OMEGA | | | TRACPIPE NOTE FROM THE PLANS. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | *IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-09-15 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-09-15 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-09-15 |
Time |
10:20 |
Sent To |
B |
|
| Notes |
| 2008-09-15 11:04:24 | GAS PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | NOTE: ALL COMMENTS ARE PER THE MAIN HOUSE GAS RISER | | | DIAGRAM LOCATED ON SHEET P201. | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE SECTION 401.1 SCOPE. | | | NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE | | | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. | | | REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS WITH NO | | | CORRESPONDING LENGTHS INDICATED AND COMPLY ON THE | | | RESUBMITTAL. | | | | | | 2. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL) | | | BEING USED ON THE RESUBMITTAL. PER FBC-2004 FUEL GAS | | | SECTION 401.1 SCOPE. | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | NOTE: REFERENCE COMMENT #1 AND COMPLY. | | | | | | 4. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE LIVING | | | ROOM (ROOM #108) GAS FIRE PLACE PER FBC-2004 FUEL GAS | | | CODE SECTION 304. | | | | | | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | NOTE: THE MP REGULATORS MANUFACTURER SHEETS SHALL | | | CLEARLY INDICATE THE MAKE, MODEL NUMBER, BTU LOAD | | | CAPACITY AND A LISTING FROM A RECOGNIZED TESTING | | | LABORATORY (LISTING EXAMPLES= CSA, AGA OR UL). THE | | | SUBMITTED REAL-FYRE GAS LOG MANUFACTURE SHEETS DO NOT | | | COMPLY WITH THE FOLLOWING. LOG LIGHTERS SHALL BE TESTED | | | IN ACCORDANCE WITH CSA 8. PER FBC-2004 FUEL GAS CODE | | | SECTION 603.1 GENERAL. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2009-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-10-19 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-10-19 |
Time |
14:18 |
Sent To |
B |
|
| Notes |
| 2009-10-19 14:19:00 | TO JG'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
|
Date |
2009-10-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-14 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-10-13 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2009-10-14 09:51:28 | LANDSCAPE REVISION TO ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2009-06-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-06-03 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-06-03 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2009-06-03 16:05:55 | TO RON REGUEIRO'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-05-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-27 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-27 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2009-05-27 10:21:05 | SENT TO RON R'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-05-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-27 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-27 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2009-05-27 10:03:52 | SENT TO DEWEY P'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-11-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-18 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-18 |
Time |
08:32 |
Sent To |
Z |
|
| Notes |
| 2008-11-18 08:32:43 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-10-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-14 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-14 |
Time |
14:26 |
Sent To |
Z |
|
| Notes |
| 2008-10-14 14:27:17 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-09-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-10 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-10 |
Time |
09:06 |
Sent To |
E |
|
| Notes |
| 2008-09-10 09:06:33 | TO "SFR" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-09-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-09-17 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-09-04 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2008-09-04 10:40:19 | TO "SFR" "Z" |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
2009-10-16 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-10-16 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-10-16 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
P |
Date |
2008-12-03 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-12-03 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2008-12-03 |
Time |
14:16 |
Sent To |
PC |
|
| Notes |
| 2008-12-03 14:18:37 | ***LANDSCAPE REVIEW PASSED*** | | | | | | PLEASE SEE NOTES CONCERNING THE PAVING MATERIAL AND | | | RIGHT-OF-WAY REQUIREMENTS ON SHEET C-1. | | | | | | RAK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2009-06-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-06-09 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-06-09 |
Time |
11:12 |
Sent To |
PC |
|
| Notes |
| 2009-06-09 11:13:29 | SEE REDLINED NOTE ON PLANS: | | | | | | RETURN AIR PROHIBITED FROM CLOSETS PER FBC-R | | | M1602.2(4). | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-05-29 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-05-29 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-05-29 |
Time |
16:27 |
Sent To |
PC |
|
| Notes |
| 2009-05-29 16:28:35 | M100, M101 REVISION 5 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-10-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-10-22 |
Time |
15:53 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-10-22 |
Time |
15:53 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2008-09-10 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-09-10 |
Time |
13:33 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2008-09-10 |
Time |
13:33 |
Sent To |
E |
|
| Notes |
| 2008-09-10 13:37:13 | *** PROVISO *** | | | 1) ATTIC ACCESS OPENING MUST BE WITHIN 6 FEET OF AIR | | | HANDLERS IN ATTIC, PER 2004 FBC/R 1305.1.3. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-12-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-04 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-04 |
Time |
13:40 |
Sent To |
M |
|
| Notes |
| 2008-12-04 13:41:43 | | | | | | | ************PASSED/PROVISO*********** | | | | | | ALL FIXTURES AND VALVES SHALL COMPLY WITH CHAPTER 13 OF | | | THE PLUMBING CODE | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-10-24 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-10-24 |
Time |
10:25 |
Rev Time |
1.30 |
| Received By |
mperson |
Date |
2008-10-24 |
Time |
10:25 |
Sent To |
G |
|
| Notes |
| 2008-10-24 10:30:59 | PLUMBING PLAN REVIEW: | | | DENIED **2ND TIME: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND | | | WITH THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS | | | THE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. "OK" COMMENT ADDRESSED. | | | | | | 2. "OK" COMMENT ADDRESSED. | | | | | | 3. SHEET A400 PLUMBING FIXTURE SCHEDULE: PLEASE KNOW | | | THAT THE FIXTURES IN THE SCHEDULE REQUIRE THIRD-PARTY | | | TESTING AND CERTIFICATION. PLEASE KNOW THAT FIXTURES | | | LISTED IN THE SCHEDULE ARE NOT COMMONLY USED FIXTURES | | | SUCH AS KOHLER OR AMERICAN STANDARD AND AN ONLINE | | | SEARCH BY THIS PLANS EXAMINER FAILED TO COME UP WITH | | | THE REQUIRED THIRD PARTY TESTING AND CERTIFICATIONS. | | | PROVIDE MANUFACTURE SPECIFICATION SHEETS WITH THIS | | | INFORMATION. PER FBC-2004 PLUMBING SECTION 303.4 | | | THIRD-PARTY TESTING AND CERTIFICATION. | | | NOTE: THE FOLLOWING IS A LIST OF FIXTURES AND COMPLIANT | | | THIRD-PARTY TESING AND CERTIFICATION STANDARDS | | | MANUFACTURE SHEETS MUST INDICATE PER THE FBC-2004 | | | PLUMBING CODE SECTIONS. | | | | | | A} BATHTUBS= SECTION 407.1 APPROVAL. BATHTUBS SHALL | | | CONFORM TO ANSI Z124.1, ASME A112.19.1M, ASME | | | A112.19.4M, ASME A112.19.9M, CSA B45.2, CSA B45.3 OR | | | CSA B45.5. | | | | | | B} LAVATORIES= SECTION 416.1 APPROVAL. LAVATORIES SHALL | | | CONFORM TO ANSI Z124.3, ASME A112.19.1M, ASME | | | A112.19.2M, ASME A112.19.3M, ASME A112.19.4M, ASME | | | A112.19.9M, CSA B45.1, CSA B45.2, CSA B45.3 OR CSA | | | B45.4. GROUP WASH-UP EQUIPMENT SHALL CONFORM TO THE | | | REQUIREMENTS OF SECTION 402 . EVERY 20 INCHES (508 MM) | | | OF RIM SPACE SHALL BE CONSIDERED AS ONE LAVATORY. | | | SECTION 416.2 CULTURED MARBLE LAVATORIES. CULTURED | | | MARBLE VANITY TOPS WITH AN INTEGRAL LAVATORY SHALL | | | CONFORM TO ANSI Z124.3 OR CSA B45.5. | | | | | | C} SHOWER= SECTION 417.1 APPROVAL. PREFABRICATED | | | SHOWERS AND SHOWER COMPARTMENTS SHALL CONFORM TO ANSI | | | Z124.2, ASME A112.19.9M OR CSA B45.5. SHOWER VALVES FOR | | | INDIVIDUAL SHOWERS SHALL CONFORM TO THE REQUIREMENTS OF | | | SECTION 424.4 . | | | | | | D} WATER CLOSET= SECTION 420.1 APPROVAL. WATER CLOSETS | | | SHALL CONFORM TO THE WATER CONSUMPTION REQUIREMENTS OF | | | SECTION 604.4 AND SHALL CONFORM TO ANSI Z124.4, ASME | | | A112.19.2M, CSA B45.1, CSA B45.4 OR CSA B45.5. WATER | | | CLOSETS SHALL CONFORM TO THE HYDRAULIC PERFORMANCE | | | REQUIREMENTS OF ASME A112.19.6. WATER CLOSET TANKS | | | SHALL CONFORM TO ANSI Z124.4, ASME A112.19.2, ASME | | | A112.19.9M, CSA B45.1, CSA B45.4 OR CSA B45.5. | | | ELECTRO-HYDRAULIC WATER CLOSETS SHALL COMPLY WITH ASME | | | A112.19.13. | | | | | | E} FAUCETS AND OTHER FIXTURE FITTINGS SECTION 424.1 | | | APPROVAL. FAUCETS AND FIXTURE FITTINGS SHALL CONFORM TO | | | ASME A112.18.1 OR CSA B125. FAUCETS AND FIXTURE | | | FITTINGS THAT SUPPLY DRINKING WATER FOR HUMAN INGESTION | | | SHALL CONFORM TO THE REQUIREMENTS OF NSF 61, SECTION 9. | | | FLEXIBLE WATER CONNECTORS EXPOSED TO CONTINUOUS | | | PRESSURE SHALL CONFORM TO THE REQUIREMENTS OF SECTION | | | 605.6 . | | | | | | F} SECTION 424.1.1 FAUCETS AND SUPPLY FITTINGS. FAUCETS | | | AND SUPPLY FITTINGS SHALL CONFORM TO THE WATER | | | CONSUMPTION REQUIREMENTS OF SECTION 604.4 . | | | | | | G} SECTION 424.1.2 WASTE FITTINGS. WASTE FITTINGS SHALL | | | CONFORM TO ONE OF THE STANDARDS LISTED IN TABLES 702.1 | | | AND 702.4 FOR ABOVE-GROUND DRAINAGE AND VENT PIPE AND | | | FITTINGS, OR THE WASTE FITTINGS SHALL BE CONSTRUCTED OF | | | TUBULAR STAINLESS STEEL WITH A MINIMUM WALL THICKNESS | | | OF 0.012 INCH (0.30 MM), TUBULAR COPPER ALLOY HAVING A | | | MINIMUM WALL THICKNESS OF 0.027 INCH (0.69 MM) OR | | | TUBULAR PLASTIC COMPLYING WITH ASTM F 409. | | | | | | H} SECTION 424.2 HAND SHOWERS. HAND-HELD SHOWERS SHALL | | | CONFORM TO ASSE 1014 OR CSA B125. | | | | | | I} SECTION 424.3 SHOWER VALVES. SHOWER AND TUB-SHOWER | | | COMBINATION VALVES SHALL BE BALANCED PRESSURE, | | | THERMOSTATIC OR COMBINATION | | | BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO | | | THE REQUIREMENTS OF ASSE 1016 OR CSA B125. SHOWER AND | | | TUB-SHOWER COMBINATION VALVES AND MASTER THERMOSTATIC | | | MIXING VALVES REQUIRED BY THIS SECTION SHALL BE | | | EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF | | | THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD | | | ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S | | | INSTRUCTIONS. | | | | | | J} SECTION 424.4 HOSE-CONNECTED OUTLETS. FAUCETS AND | | | FIXTURE FITTINGS WITH HOSE-CONNECTED OUTLETS SHALL | | | CONFORM TO ASME A112.18.3M. | | | | | | K} SECTION 424.5 TEMPERATURE-ACTUATED, FLOW REDUCTION | | | VALVES FOR INDIVIDUAL FIXTURE FITTINGS. | | | TEMPERATURE-ACTUATED, FLOW REDUCTION DEVICES, WHERE | | | INSTALLED FOR INDIVIDUAL FIXTURE FITTINGS, SHALL | | | CONFORM TO ASSE 1062. SUCH VALVES SHALL NOT BE USED | | | ALONE AS A SUBSTITUTE FOR THE BALANCED PRESSURE, | | | THERMOSTATIC OR COMBINATION SHOWER VALVES REQUIRED IN | | | SECTION 424.3 . | | | | | | L} SECTION 424.6 TRANSFER VALVES. DECK-MOUNTED | | | BATH/SHOWER TRANSFER VALVES CONTAINING AN INTEGRAL | | | ATMOSPHERIC VACUUM BREAKER SHALL CONFORM TO THE | | | REQUIREMENTS OF ASME A112.18.7. | | | | | | **RESPONSE NOTED, HOWEVER THE FOLLOWING ITEMS LISTED ON | | | THE "PUMBING FIXTURE SCHDULE" ON SHEET NO. A400 WERE | | | NOT LISTED IN THE REQUESTED MANUFACTURE SHEETS. PLEASE | | | PROVIDE THE MANUFACTURE SHEETS AS REQUESTED OR REVISE | | | THE PLUMBING FIXTURE SCHDULE. PLEASE KNOW THAT CLEARLY | | | MARKED MANUFACTURE SHEETS WITH THE MODEL NUMBER OF THE | | | FIXTURES BEING USED WOULD GREATLY HELP IN PLAN REVIEW | | | TIME. PLEASE KNOW THAT ALL ITEMS WILL REMAIN ON THIS | | | COMMENT AS SOME ITEMS ARE LISTED AS SPAREPARTS WITH NO | | | EXPLANATION AS TO WHAT THEY ARE. | | | | | | **DORNBRACHT, 28011979-00, TARA HANDSHOWER SET. | | | **DORNBRACHT, 09110311-00, TARA SPAREPARTS. | | | **DORNBRACHT, 09.14.10.026.90, TARA SPAREPARTS-SEAL. | | | **DORNBRACHT, 092722003-00, TARA SPAREPARTS. **LACAVA, | | | 5057-001, TWIN UNDERMOUNT SINK. **LACAVA, 7100-11-CR, | | | POLISHED CHROME P-TRAP. **TOTO MS854114SL, WH ULTRAMAX | | | TOILET ADA. | | | | | | 4. "OK" COMMENT ADDRESSED. | | | | | | 5. "OK" COMMENT ADDRESSED. | | | | | | 6. "OK" COMMENT ADDRESSED. | | | | | | 7. "OK" COMMENT ADDRESSED. | | | | | | 8. "OK" COMMENT ADDRESSED. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | **PLEASE CALL IF THERE ARE ANY QUESTIONS. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-09-12 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-09-15 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-09-12 |
Time |
15:58 |
Sent To |
G |
|
| Notes |
| 2008-09-12 16:54:54 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET A102 BATH ROOM NUMBER 208 AND 214 INDICATE THE | | | WATER CLOSET 1'-4" FROM THE SHOWER WALL TO THE | | | CENTERLINE OF THE WATER CLOSETS IN A 30" MIN. SPACE | | | PROVIDED FOR THE WATER CLOSET. THIS LEAVES 14" FROM | | | CENTERLINE OF THE WATER CLOSET TO THE EDGE OF THE | | | LAVATORY. PER CODE A MINIMUM OF 15" IS REQUIRED. WHY | | | ISN'T THE WATER CLOSET CENTERED IN THE 30" SPACE AT | | | 1'-3" TO BE COMPLIANT? PER FBC-2004 PLUMBING SECTION | | | 405.3.1 WATER CLOSETS, URINALS, LAVATORIES AND BIDETS. | | | | | | 2. SHEET A103 EXISTING GARAGE-PROPOSED SECOND FLOOR | | | PLAN ROOM NUMBER 203 DOES NOT INDICATE THE PROPOSED BAR | | | SINK THAT IS BEING INDICATED ON SHEET P201 GUEST HOUSE | | | SANITARY RISER. PLEASE CORRELATE PLAN SHEET TO REFLECT | | | THE PROPOSED BAR SINK. PER (W.P.B. AS AMENDED) SECTION | | | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 3. SHEET A400 PLUMBING FIXTURE SCHEDULE: PLEASE KNOW | | | THAT THE FIXTURES IN THE SCHEDULE REQUIRE THIRD-PARTY | | | TESTING AND CERTIFICATION. PLEASE KNOW THAT FIXTURES | | | LISTED IN THE SCHEDULE ARE NOT COMMONLY USED FIXTURES | | | SUCH AS KOHLER OR AMERICAN STANDARD AND AN ONLINE | | | SEARCH BY THIS PLANS EXAMINER FAILED TO COME UP WITH | | | THE REQUIRED THIRD PARTY TESTING AND CERTIFICATIONS. | | | PROVIDE MANUFACTURE SPECIFICATION SHEETS WITH THIS | | | INFORMATION. PER FBC-2004 PLUMBING SECTION 303.4 | | | THIRD-PARTY TESTING AND CERTIFICATION. | | | NOTE: THE FOLLOWING IS A LIST OF FIXTURES AND COMPLIANT | | | THIRD-PARTY TESING AND CERTIFICATION STANDARDS | | | MANUFACTURE SHEETS MUST INDICATE PER THE FBC-2004 | | | PLUMBING CODE SECTIONS. | | | | | | A} BATHTUBS= SECTION 407.1 APPROVAL. BATHTUBS SHALL | | | CONFORM TO ANSI Z124.1, ASME A112.19.1M, ASME | | | A112.19.4M, ASME A112.19.9M, CSA B45.2, CSA B45.3 OR | | | CSA B45.5. | | | | | | B} LAVATORIES= SECTION 416.1 APPROVAL. LAVATORIES SHALL | | | CONFORM TO ANSI Z124.3, ASME A112.19.1M, ASME | | | A112.19.2M, ASME A112.19.3M, ASME A112.19.4M, ASME | | | A112.19.9M, CSA B45.1, CSA B45.2, CSA B45.3 OR CSA | | | B45.4. GROUP WASH-UP EQUIPMENT SHALL CONFORM TO THE | | | REQUIREMENTS OF SECTION 402 . EVERY 20 INCHES (508 MM) | | | OF RIM SPACE SHALL BE CONSIDERED AS ONE LAVATORY. | | | SECTION 416.2 CULTURED MARBLE LAVATORIES. CULTURED | | | MARBLE VANITY TOPS WITH AN INTEGRAL LAVATORY SHALL | | | CONFORM TO ANSI Z124.3 OR CSA B45.5. | | | | | | C} SHOWER= SECTION 417.1 APPROVAL. PREFABRICATED | | | SHOWERS AND SHOWER COMPARTMENTS SHALL CONFORM TO ANSI | | | Z124.2, ASME A112.19.9M OR CSA B45.5. SHOWER VALVES FOR | | | INDIVIDUAL SHOWERS SHALL CONFORM TO THE REQUIREMENTS OF | | | SECTION 424.4 . | | | | | | D} WATER CLOSET= SECTION 420.1 APPROVAL. WATER CLOSETS | | | SHALL CONFORM TO THE WATER CONSUMPTION REQUIREMENTS OF | | | SECTION 604.4 AND SHALL CONFORM TO ANSI Z124.4, ASME | | | A112.19.2M, CSA B45.1, CSA B45.4 OR CSA B45.5. WATER | | | CLOSETS SHALL CONFORM TO THE HYDRAULIC PERFORMANCE | | | REQUIREMENTS OF ASME A112.19.6. WATER CLOSET TANKS | | | SHALL CONFORM TO ANSI Z124.4, ASME A112.19.2, ASME | | | A112.19.9M, CSA B45.1, CSA B45.4 OR CSA B45.5. | | | ELECTRO-HYDRAULIC WATER CLOSETS SHALL COMPLY WITH ASME | | | A112.19.13. | | | | | | E} FAUCETS AND OTHER FIXTURE FITTINGS SECTION 424.1 | | | APPROVAL. FAUCETS AND FIXTURE FITTINGS SHALL CONFORM TO | | | ASME A112.18.1 OR CSA B125. FAUCETS AND FIXTURE | | | FITTINGS THAT SUPPLY DRINKING WATER FOR HUMAN INGESTION | | | SHALL CONFORM TO THE REQUIREMENTS OF NSF 61, SECTION 9. | | | FLEXIBLE WATER CONNECTORS EXPOSED TO CONTINUOUS | | | PRESSURE SHALL CONFORM TO THE REQUIREMENTS OF SECTION | | | 605.6 . | | | | | | F} SECTION 424.1.1 FAUCETS AND SUPPLY FITTINGS. FAUCETS | | | AND SUPPLY FITTINGS SHALL CONFORM TO THE WATER | | | CONSUMPTION REQUIREMENTS OF SECTION 604.4 . | | | | | | G} SECTION 424.1.2 WASTE FITTINGS. WASTE FITTINGS SHALL | | | CONFORM TO ONE OF THE STANDARDS LISTED IN TABLES 702.1 | | | AND 702.4 FOR ABOVE-GROUND DRAINAGE AND VENT PIPE AND | | | FITTINGS, OR THE WASTE FITTINGS SHALL BE CONSTRUCTED OF | | | TUBULAR STAINLESS STEEL WITH A MINIMUM WALL THICKNESS | | | OF 0.012 INCH (0.30 MM), TUBULAR COPPER ALLOY HAVING A | | | MINIMUM WALL THICKNESS OF 0.027 INCH (0.69 MM) OR | | | TUBULAR PLASTIC COMPLYING WITH ASTM F 409. | | | | | | H} SECTION 424.2 HAND SHOWERS. HAND-HELD SHOWERS SHALL | | | CONFORM TO ASSE 1014 OR CSA B125. | | | | | | I} SECTION 424.3 SHOWER VALVES. SHOWER AND TUB-SHOWER | | | COMBINATION VALVES SHALL BE BALANCED PRESSURE, | | | THERMOSTATIC OR COMBINATION | | | BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO | | | THE REQUIREMENTS OF ASSE 1016 OR CSA B125. SHOWER AND | | | TUB-SHOWER COMBINATION VALVES AND MASTER THERMOSTATIC | | | MIXING VALVES REQUIRED BY THIS SECTION SHALL BE | | | EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF | | | THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD | | | ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S | | | INSTRUCTIONS. | | | | | | J} SECTION 424.4 HOSE-CONNECTED OUTLETS. FAUCETS AND | | | FIXTURE FITTINGS WITH HOSE-CONNECTED OUTLETS SHALL | | | CONFORM TO ASME A112.18.3M. | | | | | | K} SECTION 424.5 TEMPERATURE-ACTUATED, FLOW REDUCTION | | | VALVES FOR INDIVIDUAL FIXTURE FITTINGS. | | | TEMPERATURE-ACTUATED, FLOW REDUCTION DEVICES, WHERE | | | INSTALLED FOR INDIVIDUAL FIXTURE FITTINGS, SHALL | | | CONFORM TO ASSE 1062. SUCH VALVES SHALL NOT BE USED | | | ALONE AS A SUBSTITUTE FOR THE BALANCED PRESSURE, | | | THERMOSTATIC OR COMBINATION SHOWER VALVES REQUIRED IN | | | SECTION 424.3 . | | | | | | L} SECTION 424.6 TRANSFER VALVES. DECK-MOUNTED | | | BATH/SHOWER TRANSFER VALVES CONTAINING AN INTEGRAL | | | ATMOSPHERIC VACUUM BREAKER SHALL CONFORM TO THE | | | REQUIREMENTS OF ASME A112.18.7. | | | | | | 4. SHEET P200 E.W.H. PIPING SCHEMATIC: PLEASE KNOW THAT | | | THE "WATTS #288 ATMOSPHERIC VACUUM BREAKER" IS THE | | | WRONG VALVE FOR A BOTTOM FED WATER HEATER. A "WATTS | | | #N36 VACUUM RELIEF VALVE" IS THE CORRECT TYPE OF VALVE | | | FOR A BOTTOM FED WATER HEATER. PER FBC-2004 PLUMBING | | | SECTION 504.2 VACUUM RELIEF. | | | | | | 5. SHEET P200 MAIN HOUSE WATER HEATER DETAIL NOTES #9: | | | A VACUUM RELIEF VALVE IS REQUIRED FOR THE 80 GALLON | | | STORAGE TANK NOT A VACUUM BREAKER. PLEASE CLEARLY | | | INDICATE THIS REQUIRED VALVE ON THE RESUBMITTAL. PER | | | FBC-2004 PLUMBING SECTION 504.2 VACUUM RELIEF. | | | | | | 6. SHEET P200 MAIN HOUSE WATER HEATER DETAIL NOTES #8 | | | THE "AUTO AIR VENT-GRUNDHFUS YGE075T" LOCATION IS | | | MISSING FROM THE DETAIL. CLEARLY INDICATE THE LOCATION | | | OF THIS ITEM. PER FBC-2005 PLUMBING SECTION 501.1 | | | SCOPE. | | | | | | 7. SHEET P201 MASTER BATH ROOM #205: DUE TO THE FIXTURE | | | LAYOUT CHANGES OF THIS ROOM A COMPLETE SANITARY | | | ISOMETRIC RISER DIAGRAM IS REQUIRED OF THE NEW PROPOSED | | | MASTER BATH LAYOUT. PER FBC-2004 PLUMBING SECTION 701.1 | | | SCOPE, SECTION 901.1 SCOPE AND (W.P.B. AS AMENDED) | | | SECTION 106.3.5.4 (9) PLUMBING. | | | | | | 8. SHEET P201 MAIN HOUSE SANITARY RISER: A CLEANOUT IS | | | REQUIRED FOR THE 3 INCH WASHING MACHINE STACK. CLEARLY | | | INDICATE THE REQUIRED 3 INCH CLEANOUT FOR THE WASHING | | | MACHINE STACK TO BE LOCATED A FOUR FEET ABOVE FINNISH | | | FLOOR (4' A.F.F.) PER FBC-2004 PLUMBING SECTION 708.9 | | | ACCESS. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-11-26 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-11-26 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-11-25 |
Time |
10:39 |
Sent To |
L |
|
| Notes |
| 2008-11-26 15:27:20 | PASSED WITH PROVISO: THE CHIMNEY SHALL BE SETBACK A | | | MINIMUM OF SIX (6) FEET FROM THE SOUTHERLY PROPERTY | | | LINE AND MAY NOT PROJECT MORE THAN 18 INCHES INTO THE | | | PROPERTY LINE AS NOTED IN THE DETAIL ON SHEET S100. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-10-21 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-10-21 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-10-21 |
Time |
14:59 |
Sent To |
E |
|
| Notes |
| 2008-10-21 15:05:58 | ***ZONING FAILED*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION | | | 94-441(C)(2): AS THE VALUE OF THE PROPOSED WORK EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT | | | VALUE" WITH THE P.B.C. PROPERTY APPRAISER'S OFFICE), | | | LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. | | | | | | PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | | THE ZLDR. | | | | | | REPEAT COMMENT: | | | | | | 3. THE BOUNDARY SURVEY INCLUDES THE PROPERTY TO THE | | | SOUTH AS PART OF THE SUBJECT SITE. THE PBC PROPERTY | | | APPRAISER'S RECORDS SHOW THAT THESE PARCELS ARE | | | SEPERATE. PLEASE CLARIFY. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-09-09 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-09-09 |
Time |
10:23 |
Sent To |
I |
|
| Notes |
| 2008-09-09 10:33:34 | **ZONING FAILED** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. STATE EXACT SCOPE OF WORK ON BUILDING PERMIT | | | DESCRIPTION, I.E., ANY ADDITIONS (TERRACE/CHIMNEY, IF | | | APPLICABLE), DEMOLITIONS, LAYOUT CHANGE, INCREASING THE | | | HEIGHT OF THE STRUCTURE, ETC. | | | | | | 3. THE BOUNDARY SURVEY THAT WAS SUBMITTED INCLUDES THE | | | PROPERTY NEXT DOOR AS PART OF THE SUBJECT SITE. THE PBC | | | PROPERTY APPRAISERS RECORDS SHOW THAT THESE PARCELS ARE | | | SEPARATE. PLEASE CLARIFY. | | | | | | 4. INDICATE ON SURVEY THE SETBACK DIMENSIONS FROM ANY | | | EXTERIOR IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES. | | | | | | 5. PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE | | | SURFACES (EXISTING AND PROPOSED) LOCATED WITHIN THE | | | FRONT YARD (FROM FRONT PROPERTY LINE TO THE FRONT | | | BUILDING FACADE). | | | | | | INDICATE WHETHER THE PROPOSED DRIVEWAY BRICK PAVERS ARE | | | SEALED OR UNSEALED AND WHETHER THEY ARE SET IN SAND OR | | | OVER CONCRETE. PURSUANT TO THE CITY OF WEST PALM BEACH | | | ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION | | | 94-482: REQUIRED OFF-STREET PARKING SPACES FOR LESS | | | THAN FOUR RESIDENTIAL DWELLING UNITS SHALL BE LOCATED | | | ON THE PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. | | | REQUIRED PARKING MAY BE LOCATED IN A FRONT YARD; | | | HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT | | | OF THE FRONT YARD AREA MUST BE LANDSCAPED. | | | | | | 6. INDICATE THE HEIGHT OF BOTH BUILDINGS ON ELEVATION | | | PLANS. PURSUANT TO THE ZLDR, SECTION 94-72(A)(3): | | | MAXIMUM BUILDING HEIGHT IN SINGLE FAMILY LOW DENSITY | | | (SF7) RESIDENTIAL DISTRICT IS 30 FEET AND PURSUANT TO | | | SECTION 94-304(B)(4), ACCESSORY STRUCTURES SHALL NOT | | | EXCEED 25 FEET. | | | | | | 7. CLARIFY WHETHER THE CHIMNEY IS EXISTING OR PROPOSED. | | | IF PROPOSED, PURSUANT TO THE ZLDR, SECTION 305(B)(10): | | | CHIMNEYS MAY NOT PROJECT NO MORE THAN 18 INCHES INTO | | | ANY SETBACK. | | | | | | SHEET NO.: A203 INDICATES THE TOTAL HEIGHT INCLUDING | | | THE CHIMNEY IS 34 FEET - 6 INCHES. PURSUANT TO THE | | | ZLDR, SECTION 306(A): CHIMNEYS MAY EXCEED DISTRICT | | | HEIGHT REQUIREMENTS BY ONLY TEN (10) PERCENT. | | | | | | 8. IF PROPOSING TO INSTALL OR RELOCATE ANY A/C | | | EQUIPMENT, INDICATE SETBACK DIMENSIONS TO ALL PROPERTY | | | LINES. PURSUANT TO THE ZLDR, SECTION 94-305(B)(4): | | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET | | | INTO A REQUIRED SETBACK. | | | | | | 9. CORRELATE ALL SITE PLAN CHANGES. | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |