Plan Review Details - Permit 08090040
| Plan Review Stops For Permit 08090040 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-11-25 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-11-25 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-11-25 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-11-01 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-11-01 |
Time |
08:29 |
Rev Time |
0.75 |
| Received By |
amorse |
Date |
2008-11-01 |
Time |
08:29 |
Sent To |
PC |
|
| Notes |
| 2008-11-01 08:45:57 | | | | | | | DENIED | | | | | | 1) PER 11-4.8.3 FBC THE MINIMUM CLEAR WIDTH OF RAMPS | | | THAT ARE PART OF THE REQUIRED MEANS OF EGRESS SHALL BE | | | 44". | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-09-06 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-09-06 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2008-09-06 |
Time |
09:33 |
Sent To |
PC |
|
| Notes |
| 2008-09-06 09:41:23 | | | | | | | DENIED | | | | | | 1) A DESIGN PROFESSIONAL THAT IS REGISTERED TO PRACTICE | | | UNDER CHAPTER 481 OR 471 OF THE FLORIDA STATUTES SHALL | | | AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND DATE TO SAID | | | DRAWINGS AND SPECIFICATIONS PER 106.1 FBC 2004. THE | | | EXEMPTION FROM LICENSURE UNDER 481.229 FS DOES NOT | | | EXEMPT THE DESIGNER RESPONSIBLE FOR THE DRAWINGS FROM | | | SIGNING AND DATING SAID DRAWINGS. | | | | | | 2) PER FLORIDA STATUTE 481.229 EXEMPTIONS FROM | | | ARCHITECTURAL LICENSURE FOR WORK ON NON-RESIDENTIAL | | | BUILDINGS UNDER $25,000 - MUST BE PREPARED BY AN | | | ARCHITECT/ENGINEER IF THE BUILDING IS INTENDED FOR | | | PUBLIC USE. | | | | | | 3) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, | | | ADDRESS, AND LICENSE NUMBER ON EACH SHEET THAT BEARS | | | THEIR SEAL PER | | | 61G15-23.002(2) FAC | | | | | | 4) PLEASE PROVIDE ALL RAMP MEASUREMENTS TO DETERMINE | | | CODE COMPLIANCE, WIDTH, LENGTH, ETC. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-09-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-04 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2008-09-04 10:12:18 | TO "MISC" BOX#1 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|