Plan Review Details - Permit 08090029
| Plan Review Stops For Permit 08090029 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-10-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-10-09 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-10-09 |
Time |
14:38 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-09-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-09-05 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-09-05 |
Time |
09:26 |
Sent To |
I |
|
| Notes |
| 2008-09-05 10:38:10 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 225.30 NUMBER OF SUPPLIES | | | WHERE MORE THAN ONE BUILDING OR OTHER STRUCTURE IS ON | | | THE SAME PROPERTY AND UNDER SINGLE MANAGEMENT, EACH | | | ADDITIONAL BUILDING OR OTHER STRUCTURE THAT IS SERVED | | | BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF THE | | | SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY | | | ONE FEEDER OR BRANCH CIRCUIT UNLESS PERMITTED IN | | | 225.30(A) THROUGH (E). FOR THE PURPOSE OF THIS SECTION, | | | A MULTIWIRE BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE | | | CIRCUIT.*** THIS ARTICLE REQUIRES A DISCONNECTING MEANS | | | AT THE PAVILION. SEE 225.31 AND 225.32 FOR LOCATION, | | | 250.32 FOR GROUNDING REQUIREMENTS. LOCATE THIS | | | EQUIPMENT ON THE PLAN, SHOW FEEDER INFORMATION ON A | | | DIAGRAM PER 215.5. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-10-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-07 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-07 |
Time |
14:09 |
Sent To |
E |
|
| Notes |
| 2008-10-07 14:10:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-09-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-09-05 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-09-03 |
Time |
16:31 |
Sent To |
PC |
|
| Notes |
| 2008-09-03 16:31:12 | TO "E" BOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy