| 2008-09-17 17:04:29 | |
| | ** DENIED REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE INCORRECT NFPA-70 IS STATED ON |
| | PLANS. IN FACT PLANS STATE A 2004 EDITION WHICH HAS |
| | NEVER EXISTED. PLEASE BE SURE THE FOLLOWING IS STATED |
| | ON ELECTRICAL PLANS AND COORDINATION ON ARCHITECTURAL |
| | IS DONE AT A MINIMUM. |
| | 2002 NFPA-72 |
| | 2005 NPFA-70 |
| | 2003 NFPA-101 |
| | 2004 FBC W/ 2007 REVISIONS. |
| | |
| | FS 553.73 |
| | FBC 106.1.1 FOR CLARITY AND ADDITIONAL INFORMATION. |
| | |
| | ** SOME OF THESE ARE ALREADY NOTED AND CORRECT ONE |
| | ELECTRICAL PLANS, HOWEVER PLEASE COORDINATE BETWEEN |
| | ELECTRICAL AND ARCHITECTURAL PLANS. |
| | |
| | 2) NOTE: PLEASE INCLUDE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2.ABC.1.1,.1.2. |
| | ** PLEASE KNOW ANY NEW FIXTURES BEING INSTALLED SHALL |
| | MEET PRESCRIPTIVE REQUIREMENTS. IF NO NEW FIXTURES WILL |
| | BE INSTALLED AT ALL, THEN PLEASE PLACE NOTES ON PLANS |
| | WHICH STATE NO NEW FIXTURES PERMITTED. PLANS DO CONTAIN |
| | SOME NOTES ABOUT RELOCATING FIXTURES HOWEVER NEED TO BE |
| | EXPANDED AS THIS OFFICE HAS SEEN MANY PROJECTS WHICH |
| | FIXTURES ARE REPLACED WITH NEW AND THE LIGHTING |
| | ALLOWANCES ARE OVER THE ENERGY EFFICIENCY CODE. |
| | |
| | 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | COORDINATE WITH PANEL SCHEDULES. |
| | ** PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING OF EXIT |
| | AND EMERGENCY FIXTURES. SOME AREAS AS SHOWN WITHOUT |
| | CIRCUITING DO NOT MEET THE EXCEPTIONS IN SECTION AS |
| | NOTED. |
| | |
| | 4) NOTE: PLEASE SEE 11-4.28.1,.2,.3 OF THE FBC. PLEASE |
| | INDICATE DEVICES, LOCATIONS, HEIGHTS, LEVELS ETC FOR |
| | MINIMUM COMPLIANCE FOR ADA. |
| | |
| | 5) NOTE: IS THE SERVER ROOM AN IT ROOM PER NEC 645.2, |
| | NFPA-75? IF THIS ROOM IS NOT AN IT ROOM PLEASE PLACE |
| | NOTE ON PLANS WHICH STATES **** NO WIRING METHODS IN |
| | NEC 645 IS PERMITTED **** OR WORDS TO THAT AFFECT. |
| | |
| | 6) NOTE: PLEASE SEE 250.20,250.50,250.66,250.30 AS NO |
| | GROUNDING ELECTRODE SYSTEM, CONDUCTORS ETC ARE SHOWN ON |
| | RISER FOR NEW TRANSFORMER. |
| | |
| | 7) NOTE: PLEASE SEE 450.3 AS THE OVER CURRENT |
| | PROTECTION AS SHOWN FOR THE 50KVA TRANSFORMER IS TOO |
| | HIGH. (MAX 125%.) PLEASE ADJUST. |
| | |
| | 8) NOTE: PLEASE SEE THE TAPS ON THE SECONDARY SIDE OF |
| | THE TRANSFORMER ARE TOO FAR AND DO NOT MEET 240.21. |
| | PLEASE ADJUST BY INCLUDING A MAIN ON THE SECONDARY SIDE |
| | OF THE TRANSFORMER WITHIN 10FT (CONDUCTOR LENGTHS). |
| | |
| | 9) NOTE: PLEASE INCLUDE LOADS ON SERVICE. NOTES ON |
| | RISER MENTIONS ** IT IS IMPOSSIBLE* HOWEVER THE CODE |
| | CLEARLY PROVIDES METHODS TO DETERMINE EXISTING LOADS. |
| | PLEASE SEE 220.87 |
| | |
| | 10) NOTE: PLEASE BE SURE TO LIST AND IDENTIFY THE BACK |
| | UP POWER SOURCE AS *OPTIONAL STAND-BY ONLY* THIS IS NOT |
| | AN EMERGENCY/LIFE SAFETY OR LEGALLY REQUIRED SYSTEM. |
| | |
| | 11) NOTE: WHERE ARE THE BATTERY BACK UP EGRESS LIGHTING |
| | REQUIRED PER NFPA-101 7.8.1.3, 7.9.2.1 |
| | |
| | ** PLEASE KNOW AS THERE ARE ITEMS WHICH WILL CHANGE |
| | AND/OR MAY NOT BE ON PLANS AT THIS TIME THERE MAY BE |
| | COMMENTS ON THE NEXT REVIEW WHICH CAN NOT BE MADE AT |
| | THIS TIME. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |