Plan Review Details - Permit 08090018
Plan Review Stops For Permit 08090018
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-25 Cont ID  
Sent By lmartine Date 2009-07-25 Time 13:06 Rev Time 0.00
Received By lmartine Date 2009-07-25 Time 13:06 Sent To  
Notes
2009-07-25 13:08:25APPROVED FOR ACCESSORY USE ONLY, NOT FOR HABITATION.
 LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-05-05 Cont ID  
Sent By lmartine Date 2009-05-05 Time 16:44 Rev Time 0.00
Received By lmartine Date 2009-05-05 Time 16:44 Sent To  
Notes
2009-05-05 16:55:04BUILDING REVIEW COMMENTS
  
  
  
 PLEASE REFERENCE 2004 FBC (RESIDENTIAL) AND ASCE 7-02
 AS THE CODE DESIGN AND ANY GENERAL NOTE SECTIONS. NOTES
 CAN BE ALTERED AND INITIALED BY MR. BUCK ONLY, IN LIEU
 OF DRAWING NEW SHEETS.
  
  
  
 LUIS MARTINEZ
 561-8052-6710
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-20 Cont ID  
Sent By amorse Date 2008-09-20 Time 08:34 Rev Time 0.00
Received By amorse Date 2008-09-20 Time 08:34 Sent To PC
Notes
2008-09-20 09:06:37 
  
 DENIED
  
 1) PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS
  
 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION,NATURE, AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1 FBC*
  
 3) PROVIDE WIND DESIGN DATA ON DRAWINGS PER 1603.1.4
 FBC. PLEASE NOTE THE 2006 AMENDMENTS TO THE 2004 FBC
 REQUIRE BUILDINGS LOCATED WITHIN EXP B TYPE TERRAIN
 THAT IS DIRECTLY ADJACENT TO EXP C TYPE TERRAIN SUCH AS
 OPEN GOLF COURSES AND BODIES OF WATER FOR A DISTANCE OF
 600 FEET OR MORE IN ANY QUADRANT TO BE IN AN EXP C
 CATEGORY. PLEASE ADJUST THE DESIGN PARAMETERS AND WIND
 PRESSURES ACCORDINGLY
  
 2) PER R301 FBC RES. THE FOLLOWING DESIGN CRITERIA IS
 REQUIRED ON THE CONSTRUCTION DOCUMENTS SUBMITTED FOR
 PERMIT, BUILDINGS AND STRUCTURES, AND ALL PARTS
 THEREOF, SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL
 LOADS, INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS,
 FLOOD LOADS AND WIND LOADS AS PRESCRIBED BY THIS CODE.
 THE CONSTRUCTION OF BUILDINGS AND STRUCTURES SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 CAPABLE OF TRANSFERRING ALL LOADS FROM THEIR POINT OF
 ORIGIN THROUGH THE LOAD-RESISTING ELEMENTS TO THE
 FOUNDATION.
  
 3) THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THIS
 SHALL INCLUDE ROOFING MATERIALS, DOORS,WINDOWS,
 STRAPS/CONNECTOR, ETC.
  
 4) PER SECTION 1609.1.4 FBC OPENING PROTECTION IS
 REQUIRED, ALL GLAZED OPENING SHALL MEET LARGE MISSILE
 IMPACT TEST
  
 5) ADDITIONAL PERMITS WILL BE REQUIRED FOR ELECTRICAL
 AND ROOFING
  
 6) PROVIDE ROOF FRAMING INFORMATION AND LAYOUT, IS THIS
 ROOF FRAMED OF TRUSS,IF TRUSSES ARE USED SUBMIT 2
 COPIES OF ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH
 R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE
 INSTALLATION.
  
 7) PROVIDE MIN ROOF SHEATHING ATTACHMENT
 PER R803.2.3.1 FBC RES.
  
 8) DRAWINGS INCOMPLETE, ELEVATIONS AND PLAN VIEWS DO
 NOT RELATE NO BAY WINDOWS SHOWN ON PLAN. NO PORCH ROOF,
 PROVIDE WINDOW AND DOOR SIZES, OVERALL DIMENSIONS. MEAN
 ROOF HEIGHT, ETC.
  
 9) WHEN COMPLETE DRAWINGS AND PRODUCT APPROVALS ARE
 SUBMITTED FURTHER COMMENTS MAY ARISE
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006&2007
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE RESIDENTIAL 2004
 W/2006&2007 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2009-08-07 Cont ID  
Sent By dpalmer Date 2009-08-07 Time 09:41 Rev Time 0.00
Received By dpalmer Date 2009-08-07 Time 09:41 Sent To  
Notes
2009-08-07 09:42:22AT THE OWNER'S REQUEST.
 ALL ELECTRICAL TO BE SUBMITTED UNDER SEPARATE PLANS,
 PERMIT APPLICAITON AND FEE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-06-10 Cont ID  
Sent By dpalmer Date 2009-06-10 Time 16:18 Rev Time 0.00
Received By dpalmer Date 2009-06-10 Time 16:18 Sent To  
Notes
2009-06-10 16:19:07** DENIED 3RD REVIEW**
  
  
 ** ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE.
 MINIMUM CODE COMPLIANCE IS NOT BEING MET WITH REPEATED
 COMMENTS. FS 553.80(2)(B) MAY BE ASSESSED ON THE
 FOLLOWING REVIEW TO DESIGNER OF RECORD.
  
 ** PLANS ARE REVISED SHOWING A COMPLETELY DIFFERENT
 SERVICE FROM PREVIOUS SUBMITTED PLANS. SEE NOTES BELOW
 AS *MINIMUM* CODE COMPLIANCE IS NOT MET.
 IF PLANS ARE REVISED AND ARE NOT THE SAME AS PREVIOUSLY
 SUBMITTED THEN SOMETIMES THAT CAN CREATE NEW COMMENTS
 ** THIS REVIEWER HAS STATED ON BOTH PREVIOUS REVIEWS
 THAT IF THERE WERE QUESTIONS TO PLEASE CALL TO GO OVER
 COMMENTS. TO DATE NO CONTACT HAS BEEN MADE TO THIS
 OFFICE TO GO OVER COMMENTS.
 SEE ALL OF THE FOLLOWING NOTES.
  
 1) NOTE: NEW RISER NOW SHOWS EXISTING 200AMP METER WITH
 NEW 4/0 ON RISER YET THE CONDUCTORS TO MAIN ARE 2/0.
 WHICH IS IT? 310.16, 310.15B6
  
 2) NOTE: THE RISER NOW SHOWS A NEW SERVICE MAIN WITH A
 200AMP DISCONNECT AND A NEW 60 AMP DISCONNECT. AS SHOWN
 THIS IS A 260AMP SERVICE. CONDUCTORS AND METER ARE NOT
 RATED FOR MORE THAN 200AMPS. IS THIS A MAIN BREAKER
 PANEL WITH A SUB 60AMP BREAKER?
  
 3) NOTE: PLEASE INDICATE AIC RATINGS FOR NEW MAIN PER
 110.9
  
 4) NOTE: THE RISER NOW SHOWS NEW #1AWG CONDUCTORS FROM
 60AMP BREAKER AS NEW FEEDERS TO SUB PANEL AT PLAYHOUSE.
 THIS IS NOT POSSIBLE. 110.14,110.3
  
 5) NOTE: THE RISER NOW SHOWS A NEW 60AMP SUB PANEL AT
 THE PLAYHOUSE YET THE EXISTING 200AMP PANEL STILL SHOWS
 TWO CIRCUITS TO THE NEW PLAYHOUSE. WHICH IS IT?
 IN EITHER CASE THE MEANS OF DISCONNECT REQUIRED PER
 225.31-225.39 IS NOT SHOWN AS PREVIOUSLY REQUESTED ON
 BOTH PREVIOUS REVIEWS.
  
 6) NOTE: THE GROUNDING ELECTRODE SYSTEM BASED ON
 250.32, 250.50, 250.66 IS STILL NOT SHOWN. IF THERE IS
 A NEW PANEL PLEASE SHOW THE MINIMUM. IF THERE NEW
 CIRCUITS FROM EXISTING PANEL THEN PLEASE SHOW
 COMPLIANCE. FOR NOTES #5 AND #6.
  
 7) NOTE: IF THERE IS GOING TO BE A NEW SUB PANEL INSIDE
 THE NEW PLAYHOUSE PLEASE SUBMIT THE PANEL SCHEDULE
 SHOWING MINIMUM CODE COMPLIANCE FOR CONDUCTOR SIZES,
 OVER CURRENT PROTECTION AND PANEL SCHEDULE.
 240.4,408.4, 310.16 ETC
  
  
  
  
  
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-03-24 Cont ID  
Sent By dpalmer Date 2009-03-24 Time 09:04 Rev Time 0.00
Received By dpalmer Date 2009-03-24 Time 09:04 Sent To B
Notes
2009-03-24 09:05:13** PLANS DENIED **
  
 THE ELECTRICAL PLANS DO NOT MEET THE MINIMUM NATIONAL
 ELECTRICAL CODE. PLEASE SEE THE FOLLOWING COMMENTS.
 THESE COMMENTS ARE BASED ON THE 2005 NFPA-70
  
 1) NOTE: THE ELECTRICAL RISER SUBMITTED DOES NOT MEET
 MINIMUM CODE. THE RISER INDICATES A 200AMP DISCONNECT
 FEEDING CONDUCTORS ONLY RATED FOR 150AMPS PER 310.15B6.
 THIS RISER ALSO INDICATES A SECONDARY FEEDER FROM THE
 MAIN TO THE PANEL. WHICH IS CORRECT?
  
 2) NOTE: PLEASE SEE NEC 225.31-225.39 REQUIRED
 DISCONNECTING MEANS NOT SHOWN. REQUIRED GROUPING ETC.
  
 3) NOTE: PLEASE SEE 250.32, 250.50 AS THE REQUIRED
 IDENTIFICATION OF THE GROUNDING ELECTRODE SYSTEM IS NOT
 SHOWN.
  
 4) NOTE: PLEASE BE SURE TO STATE THE ADOPTED MINMUM
 CODE EDITIONS ON PLANS AS REQUIRED PER FS 553.73.
 2004 FBC (RESIDENTIAL AND 2005 NFPA-70
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-12 Cont ID  
Sent By dpalmer Date 2008-09-12 Time 16:06 Rev Time 0.00
Received By dpalmer Date 2008-09-12 Time 16:06 Sent To  
Notes
2008-09-12 16:06:44 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT PLANS WITH MINIMUM CLARITY AND
 INFORMATION IN DRAFTSMAN QUALITY. THE PLANS NEED TO
 SHOW ALL ASPECTS OF CONSTRUCTION TO CONFORM TO THE
 MINIMUM BUILDING CODE ALONG WITH OTHER ADOPTED CODES BY
 FLORIDA STATUES 553.73
 FBC 106.1, 106.1.1, 106.1.2, 106.3.5.4.
  
 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS WHICH WILL
 COORDINATE WITH A SUBMITTED FLOOR PLAN. FOR EXAMPLE THE
 ELECTRICAL LAYOUT AS SUBMITTED DOES NOT COORDINATE WITH
 THE HAND DRAWN ELEVATION PLANS. THE ELEVATION PLANS
 SHOW WALLS AND WINDOWS WHICH ARE NOT THE SAME AS
 ELECTRICAL.
 PLEASE SUBMIT ELECTRICAL PLANS WHICH ARE UNDER THE
 MINIMUM DESIGN OF THE 2005 NATIONAL ELECTRICAL CODE.
 PLEASE SEE SOME OF THE FOLLOWING.
 LOAD CALCULATIONS FOR ADDING LOAD TO EXISTING SERVICE.
 220.87
 GROUNDING ELECTRODE SYSTEM AT DETACHED STRUCTURES PER
 250.32, 250.50.
 DISCONNECTING MEANS AT DETACHED STRUCTURES PER
 225.31-225.39.
 CONDUCTOR SIZES PER 310.16
 PANEL SCHEDULE PER 408.4
 BREAKER SIZE(S). 310.16, 240.4, 210.19, 210.20 ETC
  
  
 *** BASED ON PLANS AT THIS TIME THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-06-03 Cont ID  
Sent By jgomez Date 2009-06-03 Time 14:17 Rev Time 0.00
Received By jgomez Date 2009-06-03 Time 14:17 Sent To  
Notes
2009-06-03 14:18:29SENT TO RESIDENTIAL BOX R13.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-16 Cont ID  
Sent By adarroug Date 2009-03-16 Time 08:26 Rev Time 0.00
Received By adarroug Date 2009-03-16 Time 08:26 Sent To Z
Notes
2009-03-16 08:27:05TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 14:54 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 14:54 Sent To E
Notes
2008-09-10 15:00:05TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-09-20 Time   Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 12:41 Sent To  
Notes
2008-09-03 12:41:53TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2009-03-17 Cont ID  
Sent By jroach Date 2009-03-17 Time 10:03 Rev Time 0.00
Received By jroach Date 2009-03-17 Time 10:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-09 Cont ID  
Sent By jroach Date 2008-09-09 Time 09:26 Rev Time 0.00
Received By jroach Date 2008-09-09 Time 09:26 Sent To  
Notes
2008-09-09 09:30:21***FAILED***
  
 1) OVERALL HEIGHT OF THE STRUCTURE SHALL BE PROVIDED.
 BUILDING HEIGHT SHALL BE MEASURED FROM GRADE TO THE
 MEAN POINT OF THE PITCHED ROOF.
  
 2) A FLOOR PLAN SHALL BE PROVIDED, OR THE DIMENSIONS OF
 THE STRUCTURE SHALL BE PROVIDED ON THE SITE
 PLAN/SURVEY.
  
 3) THE FLOOR PLAN OR REVISED SITE PLAN SHALL MATCH THE
 BUILDING FOOTPRINT THAT IS BEING PROPOSED AND ENSURE
 THAT THE SETBACKS ARE MEASURED FROM THE PROPERTY LINE
 TO THE CLOSEST POINT OF THE STRUCTURE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.