Plan Review Details - Permit 08080664
Plan Review Stops For Permit 08080664
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-01-26 Cont ID  
Sent By jwitmer Date 2009-01-26 Time 11:12 Rev Time 2.22
Received By jwitmer Date 2009-01-26 Time 11:12 Sent To B
Notes
2009-01-26 12:44:36BUILDING PLAN REVIEW
 PERMIT: 08080664
 ADD: 1801 N FLAGLER DR
 CONT: SEACREST SERVICES
 TEL: (561)346-8449
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 JAN.26/ 2009
 3RD REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) 2ND REQUEST, PLEASE SUBMIT 3 OF ALL SURVEYS, PLANS,
 REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL
 REQUIRE A THRESHOLD BUILDING REQUIRING A THRESHOLD
 INSPECTOR THEN (3) THREE SETS OF ALL SAID DOCUMENTS
 WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* /2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) COMPLIED.
  
 1D)2 COMPLIED.
  
 1E) 3RD REQUEST, PLANS FAIL TO INDICATE DESIGNED TO THE
 2004 EXISTING BUILDING CODE, CHAPTER 9 ADDITIONS.
  
 2) ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
  
 B) COMPLIED.
  
 C) COMPLIED.
  
 D) 3RD REQUEST, THE RETURN COMMENTSINDICATE THAT NO
 FIRE SPRINKLERS WILL BE INSTALLED IN THE ADDITION.
 EXISSTING BUILDING CODE SECTION 902.3 AND 901.2 AN
 ADDITION SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY.
 THIS BUILDING IS CONSIDERED A HIGH RISE AND SINCE THERE
 ARE FIRE SPRINKLERS WITHIN THE BUILDING THEN THE SYSTEM
 WILL NEED TO BE EXTENDED TO WITHIN THE ADDITION, PLEASE
 SHOW THE EXTENSION OF THE FIRE SPRINKLER LINE.
  
 E) WHETHER THE SPRINKLER SYSTEM IS REQUIRED, YES
 HIGHRISE 2004 EXISTING BUILDING CODE 901.2/ 902.3 AND
 2004 FBC403.2 AUTOMATIC FIRE SPRINKLER SYSTEMS.
  
 G-I) COMPLIED.
 .
 H
 3) THIS BUILDING IS A 9 STORY BUILDING OR CONSIDERED A
 THRESHOLD BUILDING REQUIRING :
 FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 3A) 3RD REQUEST, THE THRESHOLD INSPECTION PLAN
 SUBMITTED IS NOT SIGNED NOR SEALED. THRESHOLD
 INSPECTION PLAN 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 3B)3RD REQUEST, THRESHOLD INSPECTOR: WPB AMENDMENT
 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN
 CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT
 MAY BE ISSUED.
 SEE ATTACHMENT FOR FORMS.
  
 3C) COMPLIED.
  
 4) BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF
 WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS
 LOCATED IN AN "A-5" FLOOD ZONE. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED BEFORE A CERTIFICATE OF
 COMPLETION WILL BE AWARDED.. PLEASE INDICATE THE
 ELEVATION OF THE FLOOR SLAB. THE MINIMUM SLAB ELEVATION
 IS 7'-6".
  
 5) SPOKE WITH THE ENGINEERS FIRM TODAY AND A SIGNED AND
 SEALED LETTER FROM THE SOILS ENGINEER WILL BE FORTH
 COMING FOR THE ONE STORY ADDITION. PLEASE PROVIDE 3
 ORIGINAL SIGNED & SEALED SOILS REPORTS. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 6) COMPLIED.
  
  
 7) 3RD REQUEST, SEMI-COMPLIED. THIS BUILDING TYPE WILL
 BE A MINIMUM OF TYPE IB PLEASE REVIEW COMBUSTIBLE/
 NONCOMBUSTIBLES MATERIALS ALLOWED IN 603.1 FBC. WALL
 ASSEMBLIES ROOF FRAMING AND ROOF DECKS.
 ROOF DECKS THE PLANS DO SHOW TTHE FLAT DECK WITH B DECK
 GALVANIZED PANELS WWITH INSULATION AND A MANSARD STYLE
 PERMITERE WHICH TILE ARE ATTACHED. PLANS INDICATE THE
 USE OF 5/8" DENS-DECK FOR A SHEATHING, PLEASE NOTE THE
 PRODUCT APPROVAL METROTILE PAGES 4-4-7 ALL INDICATE THE
 USE ON 1/2 WOOD PLYWOOD OR WOOD PLANK. NOTE THERE IS NO
 GALVANIZED DECK THAT THE TILE ROOF SCREWS CAN PENETRATE
 TO ANCHOR THE ROOF TILE IN PLACE.
  
 8) COMPLIED.
  
 9) 3D REQUEST, 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED "IN WRITING" ( SHOP DRAWING STAMP BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 10) COMPLIED.
  
 11) FLAT ROOF REVIEW: THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 COMPLIED. __XX(1)_ CONTRACTOR DID NOT PROVIDE THE MEAN
 ROOF HEIGHT IN FEET OF BUILDING NOT ADDITION..MEAN ROOF
 HEIGTH IS TAKEN FROM THE TOP OF THE HIGHRISE NOT THE
 ADDITION, NEGATIVE PRESSURES ARE TAKEN AT ROOF LEVEL,
 POSISTIVE PRESSURES BUILD UP FROM GRADE.
  
 __XX(2)__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO
 BE USED. NOTE THERE IS NO PRODUCT APPROVAL SUBMITTED
 FOR THE FLAT ROOF.
  
 _XX(3) ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR
 ZONE _2&3__ . AGAIN THERE IS NO PRODUCT APPROVAL FOR
 THE FLAT DECK.
  
 _XX__(4) THE SYSTEM PROVIDED STATES LIMITATION# 7,
 SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A
 REVISED FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 MAYBE NO SUBSYSTEM HIGHLIGHTED:
 _XX__ (5)THE SYSTEM PROVIDED INDICATES LIMITATION# 9,
 NO ENHANCED FASTENING ALLOWED.
  
 12) ROOFING ASSEMBLIES, METROTILE MANUFACTURING WHICH
 SYSTEM NOT IDENTIFIED, NOR TYPE OF FASTENING
 SYSTEM.1609.6.2.2 COMPONENTS AND CLADDING.
  
 13) PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 14) PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 15) 3RD REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-04 Cont ID  
Sent By jwitmer Date 2008-11-04 Time 16:31 Rev Time 1.55
Received By jwitmer Date 2008-11-04 Time 16:31 Sent To  
Notes
2008-11-04 16:57:30BUILDING PLAN REVIEW
 PERMIT: 08080664
 ADD: 1801 N FLAGLER DR
 CONT: SEACREST SERVICES
 TEL: (561)346-8449
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 NOV.04/2008
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) 2ND REQUEST, PLEASE SUBMIT 3 OF ALL SURVEYS, PLANS,
 REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL
 REQUIRE A THRESHOLD BUILDING REQUIRING A THRESHOLD
 INSPECTOR THEN (3) THREE SETS OF ALL SAID DOCUMENTS
 WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* /2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) COMPLIED.
  
 1D)2ND REQUEST, PLANS SUBMITTED FOR PERMIT (FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.SHEET S-2
 NEEDS UP DATING TO THE 2007 SUPPLEMENTS.
  
 1E) 2ND REQUEST, PLANS FAIL TO INDICATE DESIGNED TO THE
 2004 EXISTING BUILDING CODE, CHAPTER 9 ADDITIONS.
  
 2) ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
  
 B) COMPLIED.
  
 C) 2ND REQUEST, THE TYPE OF CONSTRUCTION AS DEFINED IN
 TABLE 503, CHAPTER 6 & TABLE 601.SHEET S-2 INDICATES
 THIS IS AN ADDITION TO A HIGH RISE. PLEASE REVIEW
 EXISTING BUILDING CODE 901.2 AN ADDITION SHALL NOT
 CREATE OR EXTEND A NONCONFORMITY. BY TRYING TO CLASSIFY
 THE ADDITION AS A TYPE V-B BUILDING YOU ARE ALSO
 DECLARING THE HIGHRISE AS A TYPE V-B BUILDING. THE
 HIGHRISE IS CONSIDERED EITHER A TYPE I-A OR I-B
 DEPENDING ON THE HEIGTH OF THE BUILDING SEE TABLE 503.
 IF THE ADDITION DID NOT COMMUNICATE WITH THE HIGHRISE
 NO DOOR LEADING INTO THE HIGHRISE AND WAS ACTUALLY TWO
 SEPERATE BUILDINGS WE WOULD STILL HAVE TO CONSIDER THE
 CLOSENESS OF THE TWO BUILDINGS SEE TABLE 602 FOR WALL
 RATINGS.
  
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED WITHIN
 THE HIGHRISE? AREA INCREASES MAY OF BEEN TAKEN FOR THE
 HIGHRISE, EXISTING BUILDING CODE, 902.2
  
 E) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .
 H) NUMBER OF FLOORS FOR THE HIGHRISE THIS WILL ACTUALLY
 PROVIDE TTHE BUILDING TYPE CLASSIFICATION TABLE 503FBC,
 BUILDING .902.1 EXISTING BUILDING CODE.
  
 I ) SQ. FT. FOOTPRINT OF EXISTING BUILDING, TABLE 503
 FBC, BUILDING & 902.2 EXISTING BUILDING CODE.
  
 3) THIS BUILDING IS A 9 STORY BUILDING OR CONSIDERED A
 THRESHOLD BUILDING REQUIRING :
 FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 3A) 2ND REQUEST, THRESHOLD INSPECTION PLAN 105.13.1 THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 3B)2ND REQUEST, THRESHOLD INSPECTOR: WPB AMENDMENT
 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN
 CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT
 MAY BE ISSUED.
  
 3C) 2ND REQUEST, THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4) BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF
 WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS
 LOCATED IN AN "A-5" FLOOD ZONE. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED BEFORE A CERTIFICATE OF
 COMPLETION WILL BE AWARDED.. PLEASE INDICATE THE
 ELEVATION OF THE FLOOR SLAB. THE MINIMUM SLAB ELEVATION
 IS 7'-6".
  
 5) PLEASE PROVIDE 3 ORIGINAL SIGNED & SEALED SOILS
 REPORTS. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 6) COMPLIED.
  
  
 7) 2ND REQUEST,THIS BUILDING TYPE WILL BE A MINIMUM OF
 TYPE IB PLEASE REVIEW COMBUSTIBLE/ NONCOMBUSTIBLES
 MATERIALS ALLOWED IN 603.1 FBC. WALL ASSEMBLIES ROOF
 FRAMING AND ROOF DECKS.
  
 8) COMPLIED.
  
 9) 2ND REQUEST, 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED "IN WRITING" BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) SHEET S-1 ROOF FRAMING PLANS INDICATES THE USE OF
 2X10'S BUT THERE IS NO INFORMATION AS TO HOW THEY WILL
 ATTACH TO THE EXISTING BUILDING, LEDGERS, BUCKETS ETC?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 11) FLAT ROOF REVIEW: THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT
 IN FEET OF BUILDING NOT ADDITION..MEAN ROOF HEIGTH IS
 TAKEN FROM THE TOP OF THE HIGHRISE NOT THE ADDITION,
 NEGATIVE PRESSURES ARE TAKEN AT ROOF LEVEL, POSISTIVE
 PRESSURES BUILD UP FROM GRADE.
  
 __XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _XX___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
  
 _XX__ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 MAYBE NO SUBSYSTEM HIGHLIGHTED:
 _XX__ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 12) ROOFING ASSEMBLIES, METROTILE MANUFACTURING WHICH
 SYSTEM NOT IDENTIFIED, NOR TYPE OF FASTENING
 SYSTEM.1609.6.2.2 COMPONENTS AND CLADDING.
  
 13) PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 14) PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 15) 2ND REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-08 Cont ID  
Sent By jwitmer Date 2008-09-08 Time 11:09 Rev Time 2.22
Received By jwitmer Date 2008-09-08 Time 11:09 Sent To  
Notes
2008-09-08 12:04:47 
 BUILDING PLAN REVIEW
 PERMIT: 08080664
 ADD: 1801 N FLAGLER DR
 CONT: SEACREST SERVICES
 TEL: (561)346-8449
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 SEPTEMBER 08,2008
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 3 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL
 REQUIRE A THRESHOLD BUILDING REQUIRING A THRESHOLD
 INSPECTOR THEN (3) THREE SETS OF ALL SAID DOCUMENTS
 WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* /2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 1E) PLANS FAIL TO INDICATE DESIGNED TO THE 2004
 EXISTING BUILDING CODE, CHAPTER 9 ADDITIONS.
  
 2) ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
  
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
  
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
  
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
  
 E) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .
 H) NUMBER OF FLOORS
  
 I ) SQ. FT. FOOTPRINT OF EXISTING BUILDING
  
 3) THIS BUILDING IS A 9 STORY BUILDING OR CONSIDERED A
 THRESHOLD BUILDING REQUIRING :
 FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 3A) THRESHOLD INSPECTION PLAN 105.13.1 THE ENFORCING
 AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT
 TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 3C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A-5" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE A CERTIFICATE OF COMPLETION WILL BE
 AWARDED.. PLEASE INDICATE THE ELEVATION OF THE FLOOR
 SLAB. THE MINIMUM SLAB ELEVATION IS 7'-6".
  
 5) PLEASE PROVIDE 3 ORIGINAL SIGNED & SEALED SOILS
 REPORTS. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 6) THE PARTIAL SITE PLAN INDICATES THAT THE NEW
 ADDITION HAS A CLEAR UNOBSTRUCTED PATH TO THE EAST FOR
 MORE THAN 600 FEET. THIS WILL MAKE IT LOCATED WITH A
 "C" ZONE NOT THE "B" ZONE LISTED LISTED ON SHEET
 S-2. ALSO NOTE THE NEGATIVE PRESSURES ARE TAKEN FROM
 THE BUILDINGS HIGHEST POINT SO THE NEGATIVE PRESSURES
 WILL ALSO BE MUCH HIGHER . THIS BUILDING IS ALSO OVER
 60 FEET IN HEIGHT REQUIREING THE
 PRESSURES TO BE TAKEN FROM ASCE 7-02 SECTION 6. PLEASE
 SEE 2004 FBC 2007 SUPPLEMENTS 1609.4 SEE CATEGORY "C"
 TYPE TERRAIN. 1609.1.1.
  
  
  
 7) THIS BUILDING TYPE WILL BE A MINIMUM OF TYPE IB
 PLEASE REVIEW COMBUSTIBLE/ NONCOMBUSTIBLES MATERIALS
 ALLOWED IN 603.1 FBC. WALL ASSEMBLIES ROOF FRAMING AND
 ROOF DECKS.
  
 8) PLANS DO NOT PROVIDE IF THIS ADDITION WILL HAVE A/C?
 PLEASE PROVIDE COMPLIANCE WITH CHAPTER 13 OF THE FBC.
 13-101.1.2.
  
 9) 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) SHEET S-1 ROOF FRAMING PLANS INDICATES THE USE OF
 2X10'S BUT THERE IS NO INFORMATION AS TO HOW THEY WILL
 ATTACH TO THE EXISTING BUILDING, LEDGERS, BUCKETS ETC?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 11) FLAT ROOF REVIEW: THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT
 IN FEET OF BUILDING NOT ADDITION..
  
 __XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _XX___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
  
 _XX__ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 MAYBE NO SUBSYSTEM HIGHLIGHTED:
 _XX__ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 12) UNKNOWNS METROTILE MANUFACTURING WHICH SYSTEM NOT
 IDENTIFIED, NOR TYPE OF FASTENING SYSTEM.
  
 13) PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 14) PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-01-16 Cont ID  
Sent By dpalmer Date 2009-01-16 Time 14:55 Rev Time 0.00
Received By dpalmer Date 2009-01-16 Time 14:55 Sent To  
Notes
2009-01-16 14:56:05** DENIED PLANS**
  
 **THIRD REVIEW**
  
  
  
  
 1) NOTE: THE TITLE BLOCKS ARE STILL MISSING THE
 REQUIRED LICENSING PER FS 471.023 AND FAC 61G15-23.002.
 THE CERTIFICATE # AS SHOWN FOR KING STRUCTURAL GROUP IS
 IN FACT THE PE LICENSE NUMBER. A CERTIFICATE OF
 AUTHORIZATION NUMBER IS REQUIRED BY STATE STATUTES.
 THIS HAS BEEN NOTED THREE TIMES WITH NO CORRECTION FOR
 LICENSING. PLANS MAY BE RETAINED FOR REVIEW FROM THE
 FLORIDA BOARD OF ENGINEERS LEGAL COUNSEL.
  
 2) NOTE: PLEASE SEE ALL PREVIOUS NOTES. LIGHTING
 CONTROLS DO NOT COMPLY TO 13-415.1.ABC.1, .1.1, .1.2.
 A MANUAL SWITCH IS NOT THE ONLY REQUIREMENT.
 MUST CONTAIN AN AUTOMATIC MEANS OF SHUTTING OFF THE
 LIGHTING.
  
 3) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED AS
 REQUESTED ON ALL PREVIOUS REVIEWS. THE RESPONSE
 MENTIONS THE CIRCUITING WAS ADDED HOWEVER THESE ARE
 BLANK ON PLANS.
 PLEASE PROVIDE LOADS ON THE EXISTING PANEL WHICH IS
 BEING NOTED WITH THE NEW LOADS ADDED.
 THE LOAD ON THE CIRCUIT FOR THE A/C IS SHOWN AT 2500VA
 WHICH FAR EXCEEDS THE RATING OF A 1-POLE 20AMP BRANCH
 CIRCUIT.
 240.4,310.16,408.4, 220.87, 215.5 ETC
  
 4) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3.
 THE RESPONSE MENTIONS THIS *ADDITION CONTAINS A SINGLE
 INDEPENDENTLY OPERATED LIGHTING SYSTEM*
 THIS OFFICE DOES NOT KNOW WHAT THIS RESPONSE IS FOR???
 THE ABOVE SECTIONS GIVEN SINCE THE BEGINNING OF THE
 REVIEW PROCESS IS FOR MINIMUM LIGHTING PERFORMANCE
 CALCULATIONS PER THE SECTIONS ABOVE FROM THE FLORIDA
 BUILDING CODE. THERE IS NO EXCEPTION FOR INDEPENDENT
 SYSTEMS WHICH EXEMPTS LIGHTING PERFORMANCE CALCULATIONS
 AND ENERGY COMPLIANCE WITH FBC CHAPTER 13.
  
 5) NOTE: THE ELECTRICAL SHEET WAS REVISED TO INDICATE
 CODES HOWEVER THE NFPA-70 DOES NOT SHOW ANY YEAR
 EDITION.
 PLANS MAY NOT STATE LATEST EDITION AS THE CODES ARE
 ALWAYS BEING REVISED. THE CODES ARE BASED ON THE TIME
 OF PERMIT APPLICATION PER FS 553.73.
  
 6) NOTE: PER NOTICE GIVEN ON PREVIOUS REVIEW A FEE HAS
 NOW BEEN ASSESSED PER FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THERE ARE SEVERAL
 SECTIONS OF CODES WHICH WERE REPEATED. THE AMOUNT OF
 $672 IS DUE BEFORE THE FOLLOWING RESUB. THE RESUB FEE
 WILL NOT BE REQUIRED.
  
  
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-18 Cont ID  
Sent By dpalmer Date 2008-11-18 Time 11:49 Rev Time 0.00
Received By dpalmer Date 2008-11-18 Time 11:49 Sent To  
Notes
2008-11-18 11:49:45 
  
  
 ** FAILED 2ND REVIEW **
  
 ** PLEASE SEE THAT MANY NOTES FORM PREVIOUS REVIEW ARE
 STILL NOT ADDRESSED.
  
  
 1) NOTE: PLEASE SEE TITLE BLOCKS ARE STILL MISSING
 REQUIRED LICENSING UNDER FS 471.023, FAC61G15-23.002.
 PLEASE INCLUDE INFORMATION. PLEASE KNOW WORKING AS A
 FIRM WITHOUT LICENSING IS REQUIRED TO BE FORWARDED TO
 BE SENT TO THE FLORIDA BOARD OF ENGINEERS. PLEASE
 SUPPLY INFORMATION OR THIS OFFICE WILL HAVE NO CHOICE
 BUT TO FORWARD AS STATED.
  
 2) NOTE: PLEASE INCLUDE ALL REQUIRED CODES FOR MINIMUM
 DESIGN FOR THIS TRADE REVIEWER AS FOLLOWS.
 2004 FBC W/2007 REVISION.
 2003 NFPA-101
 2005 NFPA-70
  
 3) NOTE: PLEASE SUBMIT LIGHTING INFORMATION FOR FBC
 CHAPTER 13. 13-415.2.ABC.1.1,.1.2, .1.3.
 PLEASE SEE THAT INFORMATION ABOUT ENERGY CALCULATIONS
 PER 13-400.3
  
 4) NOTE: PLEASE COMPLETE CIRCUITING, COMPLETE WIRING
 METHODS FOR ALL RECEPTACLES, GROUNDING, BONDING,
 BREAKERS, ETC PANEL SCHEDULE, FEEDERS, LOADS ETC.
 408.4,240.4,310.16,220.87,225.31-225.39
  
 5) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2, .1.3 AND
 .1.4 FOR REQUIRED MINIMUM LIGHTING CONTROLS.
  
 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS A
 STATUTORY REQUIREMENT AND ONLY A NOTICE GIVEN AT THIS
 TIME AS THERE ARE SEVERAL REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-10 Cont ID  
Sent By dpalmer Date 2008-09-10 Time 14:46 Rev Time 0.00
Received By dpalmer Date 2008-09-10 Time 14:46 Sent To  
Notes
2008-09-10 14:46:53 
  
  
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE FAC 61G15-23.022 FOR MISSING
 INFORMATION REQUIRED ON TITLE BLOCKS. PLEASE SEE FS
 471.023 AS THE CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED IS MISSING.
  
 2) NOTE: PLANS ARE REQUIRED TO STATES THE CODES IN
 AFFECT AT THE TIME OF APPLICATION AND DESIGN.
 THE FOLLOW SHALL BE STATED ON THE PLANS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
  
 3) NOTE: PLEASE COMPLETE PLANS WITH ALL CIRCUITING,
 CONDUCTORS, PANEL, LOADS, FEEDS, GROUNDING/BONDING
 SYSTEM ETC.
 PLANS ARE NOT COMPLETE AT THIS TIME WITH SEVERAL ITEMS
 AS REQUIRED PER THE FOLLOWING SECTIONS OF THE NEC.
 .
 250.50, 250.110 ETC GROUNDING/BONDING SYSTEM AND
 GROUNDING.
 408.4, 310.16, 240.4 FOR CONDUCTORS, BREAKERS, PANEL
 SCHEDULE ETC
 215.5,240.4,310.16, 220.87 FOR LOADS, FEEDERS, PANEL
 ETC
  
  
 ** PLANS STATE CIRCUITS TO EXISTING PANEL HOWEVER HOW
 CAN THIS PANEL BE EXISTING WHEN THE STRUCTURE HAS NOT
 BEEN BUILT AT THIS TIME. PLEASE BE SURE TO SECTIONS OF
 CODE GIVEN ABOVE.
 ** AS PLANS ARE NOT COMPLETE AT THIS TIME, THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 4) NOTE: PLEASE SEE FBC 13-413.1.ABC.1.1, .1.2 FOR
 MINIMUM REQUIRED FOR VOLTAGE DROP.
  
 5) NOTE: PLEASE SEE FBC 13-415.2.ABC.1.1, .1.2 AND .1.3
 FOR LIGHTING PERFORMANCE CALCULATIONS.
  
 6) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.4 FOR EXTERIOR
 LIGHTING ON THIS STRUCTURE. AT THIS TIME THE PLANS DO
 NOT INDICATE ANY LIGHTING FOR DRIVE UP, GATE AREAS ETC.
  
 7) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 FOR
 LIGHTING CONTROLS.
  
  
  
  
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH
 INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK
 WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE
 REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-02-10 Cont ID  
Sent By mwennerg Date 2009-02-10 Time 09:48 Rev Time 0.00
Received By mwennerg Date 2009-02-10 Time 09:48 Sent To  
Notes
2009-02-10 09:49:31PLANS WILL BE STAMPED WHEN RETURNED WITH OTHER REVIEW
 COMMENT CORRECTIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-11-24 Cont ID  
Sent By mwennerg Date 2008-11-24 Time 16:00 Rev Time 0.00
Received By mwennerg Date 2008-11-24 Time 16:00 Sent To  
Notes
2008-11-24 16:02:27***DENIED***
  
 COMMENTS WERE TAKEN DIRECTLY FROM THE FIRST FIRE
 REVIEW:
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) ILLUSTRATE EXISTING DRIVE WIDTH AND OTHER PERTINENT
 DIMENSIONS AS IT APPLIES TO THE NEW GUARD HOUSE.
  
 3) PROVIDE INFORMATION REGARDING NEW GATE ARMS. IE
 FAILSAFE MECHANISM IN EVENT OF POWER LOSS, WIDTH OF
 ARMS, POWER SOURCE ETC. PROVIDE MANUFACTURER
 SPECIFICATION SHEETS.
  
 4) PLANS ILLUSTRATE A NEW CONCRETE WALK WITH SLOPE.
 INDICATE LENGTH OF WALK AND DIMENSIONS OF SLOPE.
  
 5) WILL THE GUARD HOUSE BE STAFFED?
  
  
 ALTHOUGH NOT A REQUIREMENT, A RESPONSE LETTER
 INDICATING HOW AND WHERE ON THE PLANS EACH COMMENT WAS
 ADDRESSED WOULD HELP TO EXPEDITE THE PLAN REVIEW
 PROCESS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By mwennerg Date 2008-09-26 Time 14:19 Rev Time 0.00
Received By mwennerg Date 2008-09-26 Time 14:19 Sent To  
Notes
2008-09-26 14:36:25***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) ILLUSTRATE EXISTING DRIVE WIDTH AND OTHER PERTINENT
 DIMENSIONS AS IT APPLIES TO THE NEW GUARD HOUSE.
  
 3) PROVIDE INFORMATION REGARDING NEW GATE ARMS. IE
 FAILSAFE MECHANISM IN EVENT OF POWER LOSS, WIDTH OF
 ARMS, POWER SOURCE ETC. PROVIDE MANUFACTURER
 SPECIFICATION SHEETS.
  
 4) PLANS ILLUSTRATE A NEW CONCRETE WALK WITH SLOPE.
 INDICATE LENGTH OF WALK AND DIMENSIONS OF SLOPE.
  
 5) WILL THE GUARD HOUSE BE STAFFED?
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-13 Cont ID  
Sent By adarroug Date 2009-01-13 Time 10:45 Rev Time 0.00
Received By adarroug Date 2009-01-13 Time 10:45 Sent To  
Notes
2009-01-13 10:48:26TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 09:32 Rev Time 0.00
Received By adarroug Date 2008-11-04 Time 09:32 Sent To  
Notes
2008-11-04 09:35:19TO "COMM" BD#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-29 Cont ID  
Sent By adarroug Date 2008-09-29 Time 09:46 Rev Time 0.00
Received By adarroug Date 2008-09-02 Time 13:08 Sent To  
Notes
2008-09-02 13:13:17TO "COMM" BD#16

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-02-21 Cont ID  
Sent By rregueir Date 2009-02-21 Time 15:16 Rev Time 0.00
Received By rregueir Date 2009-02-21 Time 15:14 Sent To PC
Notes
2009-02-21 15:16:37MECHANICAL REVIEW IS PASSED. HOWEVER, SINCE THE WORK
 SCOPE FOR MULTIPLE DISCIPLINES ARE SHOWN ON EACH
 CSHEET, MECHANICAL PLANS WILL BE STAMPED UPUN PASSED
 REVIEWS BY BUILDING AND ELECTRICAL TRADES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 13:15 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 12:47 Sent To  
Notes
2008-11-22 13:15:09 
  
 REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. MINI-SPLIT OK. HOWEVER, THE FOLLOWING ITEMS SHALL BE
 ADDRESSED AS A RESULT OF THE ADDITION OF THE MINI-SPLIT
 SYSTEM FROM PREVIOUS PLANS:
  
 A) PLEASE SHOW ON PLANS THE MEANS AND LOCATION OF
 CONDENSATE DISPOSAL. CONDENSATE FROM ALL COOLING COILS
 SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN
 APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO
 CAUSE A NUISANCE IN ACCORDANCE WITH FBCM 307.2.1.
 CONDENSATE SHALL NOT DISCHARGE INTO A SANITARY SEWER
 SYSTEM PER CITY ORDINANCE.
  
 B) PROVIDE WIND RESISTANCE INFORMATION FOR THE OUTDOOR
 CONDENSING UNIT. MECHANICAL APPLIANCES AND SUPPORTS
 THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT
 AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM
 301.13. SHOW HOW THE APPLIANCE IS TO BE SECURED TO
 RESIST WIND PRESSURES AND PROVIDE MANUFACTURER'S DATA
 SHOWING THE APPLIANCE IS DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH THIS SECTION.
  
 C) THERE ARE NO PROVISIONS ON ELECTRICAL PLANS TO
 PROVIDE POWER FOR THE INDOOR OR OUTDOOR PORTIONS OF
 THIS SYSTEM. PLEASE CLARIFY IN ACCORDANCE WITH FBCM
 304.1.
  
 2. **NOT ADDRESSED** SHOW HOW THE REQUIRED RATE OF
 VENTILATION IS TO BE PROVIDED IN ACCORDANCE WOTH FBCM
 403.
  
 3. **NOT ADDRESSED** THE ENGINEERING BUSINESS
 CERTIFICATE OF AUTHORIZATION NUMBER SHALL APPEAR IN THE
 TITLE BLOCK IN ACCORDANCE WITH FAC RULE 61G15-23.002.
 **THERE IS STILL NO CERTIFICATE OF AUTHORIZATION NUMBER
 IN THEE ENGINEERING BUSINESS TITLE BLOCK. PLEASE SEE
 FAC RULE 61G15-23.002 FOR ENGINEERING BUSINESS TITLE
 BLOCK REQUIREMENTS IN ACCORDANCE WITH F.S. 471.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-09 Cont ID  
Sent By rregueir Date 2008-09-09 Time 11:14 Rev Time 0.00
Received By rregueir Date 2008-09-09 Time 10:58 Sent To  
Notes
2008-09-09 11:14:19REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. MECHANICAL NOTES CALL FOR NEW SUPPLY DUCT FROM
 EXISTING SYSTEM. THERE ARE NO PROVISIONS FOR RETURN AIR
 FROM THIS SPACE. SHOW HOW BALANCED RETURN IS TO BE
 ACHIEVED IN ACCORDANCE WITH FBCM 601.4.
  
 2. SHOW HOW THE REQUIRED RATE OF VENTILATION IS TO BE
 PROVIDED IN ACCORDANCE WOTH FBCM 403.
  
 3. THE ENGINEERING BUSINESS CERTIFICATE OF
 AUTHORIZATION NUMBER SHALL APPEAR IN THE TITLE BLOCK IN
 ACCORDANCE WITH FAC RULE 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status N Date 2009-02-20 Cont ID  
Sent By kstevens Date 2009-02-20 Time 08:08 Rev Time 0.00
Received By kstevens Date 2009-02-19 Time 12:27 Sent To  
Notes
2009-02-20 08:09:13NO PLUMBING WORK SHOWN OR REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-11-24 Cont ID  
Sent By kstevens Date 2008-11-24 Time 13:25 Rev Time 0.00
Received By kstevens Date 2008-11-24 Time 13:25 Sent To  
Notes
2008-11-24 13:35:00DENIED
 REFERENCE: FBC-2004 PLUMBING W/2005, 2006 & 2007
 REVISIONS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. ALL SHEETS. THE CERTIFICATE OF AUTHORIZATION IS
 REQUIRED IN THE TITLE BLOCK OF THE ENGINEERING COMPANY.
 FAC 61G15-23.002(2) & FS 471.025.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2. SHT S-2 BASIS OF DESIGN. PLEASE INDICATE ALL
 REVISIONS TO THE FLORIDA BUILDING CODE, (2005, 2006 &
 2007). AS WELL AS THE OCCUPANCY OF THE BUILDING.
 SECTIONS 106.1 & 106.3.5.1.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. PER TABLE 403.1 MINIMUM FACILITIES, AT LEAST A WATER
 CLOSET AND LAV ARE REQUIRED AND MAYBE A DRINKING
 FOUNTAIN. IF TOILET FACILITIES ARE PROVIDED PER SECTION
 403.4 EXCEPTION. IF SO PLEASE INDICATE THE LOCATION ON
 THE PLANS AS WELL AS THE DISTANCE FROM THE GUARD HOUSE
 TO THE FACILITIES PER SECTION 403.4.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ***********NEW COMMENTS***********
  
 1B. PLANS SHALL BE SUBMITTED IN A MINIMUM (TWO) SETS OF
 PLANS BOUND/STAPLED TOGETHER. PLANS SUBMITTED WERE
 LOOSE SHEETS. SECTION 106.1.
  
 2B. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B) AND
 THE DESIGN PROFESSIONAL. THIS IS GIVEN AS A NOTICE ONLY
 AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-03 Cont ID  
Sent By kstevens Date 2008-09-03 Time 08:27 Rev Time 0.00
Received By kstevens Date 2008-09-03 Time 08:27 Sent To  
Notes
2008-09-03 08:40:36DENIED
 REFERENCE: FBC-2004 PLUMBING W/2005, 2006 & 2007
 REVISIONS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2004 CHAPTER 1
  
 1. ALL SHEETS. THE CERTIFICATE OF AUTHORIZATION IS
 REQUIRED IN THE TITLE BLOCK OF THE ENGINEERING COMPANY.
 FAC 61G15-23.002(2) & FS 471.025.
  
 2. SHT S-2 BASIS OF DESIGN. PLEASE INDICATE ALL
 REVISIONS TO THE FLORIDA BUILDING CODE, (2005, 2006 &
 2007). AS WELL AS THE OCCUPANCY OF THE BUILDING.
 SECTIONS 106.1 & 106.3.5.1.1.
  
 3. PER TABLE 403.1 MINIMUM FACILITIES, AT LEAST A WATER
 CLOSET AND LAV ARE REQUIRED AND MAYBE A DRINKING
 FOUNTAIN. IF TOILET FACILITIES ARE PROVIDED PER SECTION
 403.4 EXCEPTION. IF SO PLEASE INDICATE THE LOCATION ON
 THE PLANS AS WELL AS THE DISTANCE FROM THE GUARD HOUSE
 TO THE FACILITIES PER SECTION 403.4.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2009-01-22 Cont ID  
Sent By jroach Date 2009-01-22 Time 17:58 Rev Time 0.00
Received By jroach Date 2009-01-22 Time 17:58 Sent To  
Notes
2009-01-22 18:39:53ZONING PLAN REVIEW
  
 PERMIT NO.: 08080664
 ADDRESS: 1801 NORTH FLAGLER DRIVE
 CONTRACTOR/CONTACT: JAY PETRONI
 TELEPHONE NO.: (561) 346.8449
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 THE FOLLOWING COMMENTS FROM PREVIOUS REVIEWS CONTINUE
 TO REMAIN UNADDRESSED....
  
 1) A MINOR AMENDMENT TO THE RESIDENTIAL PLANNED
 DEVELOPMENT (RPD) SHALL BE SUBMITTED TO, AND APPROVED
 BY, THE PLANNING AND ZONING DEPARTMENT PRIOR TO
 ISSUANCE OF A BUILDING PERMIT. NO MINOR AMENDMENT
 APPLICATION HAS BEEN SUBMITTED TO THE PLANNING AND
 ZONING DEPARTMENT.
  
 2) PLEASE PROVIDE TWO (2) COPIES OF A CURRENT AND
 ACCURATE SURVEY OF THE AREA UPON WHICH THE PROPOSED
 GUARD HOUSE IT TO BE LOCATED. THE SURVEY PROVIDED IS
 NOT CURRENT, NOR ACCURATE OF THE EXISTING CONDITIONS.
 THE SURVEY PROVIDED IS DATED 1998 AND WAS PRIOR TO THE
 CONSTRUCTION OF THE EXISTING DEVELOPMENT.
  
 3) PLEASE PROVIDE A LANDSCAPE PLAN, SIGNED AND SEALED
 BY A REGISTERED LANDSCAPE ARCHITECT, INDICATING WHAT
 LANDSCAPING WILL BE PLACED AROUND THE EXTERIOR OF THE
 GUARD HOUSE. YOUR RESPONSE INDICATES THAT THE EXISTING
 LANDSCAPING WILL BE MINIMALLY IMPACTED; HOWEVER, IT
 APPEARS THAT EXISTING PALMS/TREES ARE IN THE LOCATION
 OF THE PROPOSED GUARD HOUSE. IF SO, A TREE RELOCATION
 PERMIT WILL BE REQUIRED AND A LANDSCAPE PLAN PREPARED
 BY A REGISTERED LANDSCAPE ARCHITECT WILL ALSO BE
 REQUIRED. NO LANDSCAPE PLANS HAVE BEEN SUBMITTED,
 THEREFORE, THE FULL EXTENT OF THE MODIFICATIONS CANNOT
 BE DETERMINED.
  
 4) THE FUNCTIONALITY OF THE GUARD HOUSE DOES NOT WORK.
 THE PROPOSED LOCATION OF THE GUARD HOUSE CONFLICTS WITH
 TRAFFIC CIRCULATION, PARKING, ETC. PLEASE CONTACT ME
 PRIOR TO THE SUBMITTAL OF THE MINOR AMENDMENT TO
 DISCUSS. THE PROPOSED LOCATION CONTINUES TO CONFLICT
 WITH TRAFFIC CIRCULATION, ETC. THERE IS NO PLACE FOR
 GUESTS WHO HAVE BEEN REFUSED ENTRY TO TURN AROUND.
 BECAUSE GUESTS AND RESIDENTS WILL ALL BE UTILIZING THE
 SAME GATE, CARS WILL BE STACKED, IMPEDEING THE THE
 PARKING. PLEASE CONTACT ME REGARDING THESE ISSUES.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-11-17 Cont ID  
Sent By jroach Date 2008-11-17 Time 14:59 Rev Time 0.00
Received By jroach Date 2008-11-17 Time 14:59 Sent To  
Notes
2008-11-17 15:04:46***FAILED***
  
 NO COMMENTS FROM THE FIRST REVIEW WERE ADDRESSED.
 PLEASE PROVIDE A WRITTEN RESPONSE, AS WELL AS REVISED
 PLANS, REFLECTING THE FOLLOWING REPEAT COMMENTS:
  
 1) A MINOR AMENDMENT TO THE RESIDENTIAL PLANNED
 DEVELOPMENT (RPD) SHALL BE SUBMITTED TO, AND APPROVED
 BY, THE PLANNING AND ZONING DEPARTMENT PRIOR TO
 ISSUANCE OF A BUILDING PERMIT.
  
 2) PLEASE PROVIDE TWO (2) COPIES OF A CURRENT AND
 ACCURATE SURVEY OF THE AREA UPON WHICH THE PROPOSED
 GUARD HOUSE IT TO BE LOCATED.
  
 3) PLEASE PROVIDE THE DIRECTION (I.E. NORTH, SOUTH,
 EAST, OR WEST) ON THE ELEVATIONS.
  
 4) PLEASE PROVIDE A LANDSCAPE PLAN, SIGNED AND SEALED
 BY A REGISTERED LANDSCAPE ARCHITECT, INDICATING WHAT
 LANDSCAPING WILL BE PLACED AROUND THE EXTERIOR OF THE
 GUARD HOUSE.
  
 5) THE MEASURE OF SCALE SHOWN ON THE SITE PLAN IS
 INCORRECT. IMPORTANT - NO SITE PLAN WAS INCLUDED AS
 PART OF THE RESUBMITTAL. PLEASE BE SURE TO INCLUDE A
 SITE PLAN WITH ALL FUTURE RESUBMITTALS.
  
 6) THE FUNCTIONALITY OF THE GUARD HOUSE DOES NOT WORK.
 THE PROPOSED LOCATION OF THE GUARD HOUSE CONFLICTS WITH
 TRAFFIC CIRCULATION, PARKING, ETC. PLEASE CONTACT ME
 PRIOR TO THE SUBMITTAL OF THE MINOR AMENDMENT TO
 DISCUSS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-15 Cont ID  
Sent By bpowell Date 2008-09-15 Time 13:54 Rev Time 0.00
Received By bpowell Date 2008-09-15 Time 13:54 Sent To  
Notes
2008-09-15 14:05:061. A MINOR AMENDMENT TO THE PLANNED DEVELOPMENT SHALL
 BE APPROVED PRIOR TO SUBMITTING FOR A BUILDING PERMIT.
  
 2. PLEASE INCLUDE TWO (2) COPIES OF A SURVEY.
  
 3. ON THE ELEVATIONS PLEASE INDICATE WHICH SIDE, NORTH
 OR SOUTH, THE DOORS AND WINDOWS OF THE GUARD HOUSE WILL
 BE LOCATED ON.
  
 4. PLEASE INCLUDE AN ELEVATION SHOWING WHAT THE SIDE OF
 THE EXISTING BUILDING WILL LOOK LIKE WHEN THE GUARD
 HOUSE IS ATTACHED.
  
 5. PLEASE INCLUDE A LANDSCAPE PLAN THAT SHOWS THE
 LANDSCAPING THAT WILL BE PLACED AROUND THE GUARD HOUSE.
  
 6. THE MEASURE OF SCALE SHOWN ON THE SITE PLAN IS
 INCORRECT.
  
 7. THE FUNCTIONALITY OF THE GUARD HOUSE DOES NOT WORK.
 PLEASE SET UP A MEETING WITH STAFF PRIOR TO SUBMITTING
 FOR THE REQUIRED MINOR AMENDMENT.
  
 IF YOU HAVE ANY QUESTIONS OR COMMENTS PLEASE CONTACT:
 BOBBY POWELL JR., PLANNER, [email protected], (561)
 822-1401