| 2008-09-02 08:42:13 | |
| | |
| | |
| | |
| | |
| | ** DENIED * |
| | |
| | |
| | ** PLEASE COMPLETE RISER. |
| | |
| | 1) NOTE: PLEASE SEE RISER AS NO CONDUCTORS ARE SHOWN |
| | FROM METER TO GUTTER AND FROM GUTTER TO EACH SERVICE |
| | DISCONNECT/PANEL. |
| | PLEASE SEE 240.4,310.16. |
| | FBC 106.3.5.1.2, 106.1.1 FOR ADDITIONAL INFORMATION AND |
| | CLARITY |
| | |
| | 2) NOTE: PLEASE INDICATE THE SIZE OF THE GROUNDING |
| | ELECTRODE CONDUCTOR PER 250.66 ( NO ALUMINUM IS |
| | PERMITTED) |
| | |
| | 3) NOTE: PLEASE INDICATE A MINIMUM OF TOW GROUNDING |
| | ELECTRODES (GROUND RODS) AND SIZE OF GROUND RODS. |
| | 250.50-250.56 |
| | |
| | 4) NOTE: THE EQUIPMENT GROUNDING CONDUCTOR TO THE SUB |
| | PANEL NEEDS TO BE COPPER. 90.4, 110.11 |
| | |
| | 5) NOTE: PLANS MAY NOT CONTAIN ANY TITLE BLOCKS FROM |
| | ENGINEERING FIRM UNLESS THOSE PLANS ARE SIGNED, DATED |
| | AND SEALED BY THE SAID ENGINEER. FS 471.025, FAC |
| | 61G15-23.002 |
| | ** THE SCOPE OF WORK DOES NOT REQUIRE AN ENGINEER. |
| | |
| | 6) NOTE: PLEASE SEE THE APPLIED VALUE SHALL INCLUDE ALL |
| | LABOR AND MATERIALS WHETHER OR NOT ANY IS OWNER |
| | SUPPLIED. |
| | FBC 108.3 |
| | THE EQUIPMENT ON THIS RISER CAN NOT BE PURCHASED FOR |
| | THE APPLIED VALUE. |
| | |
| | 7) NOTE: PLEASE STATE AIC RATINGS FOR SERVICE EQUIPMENT |
| | PER 110.9. |
| | |
| | 8) NOTE: PLEASE INDICATE THE SIZE OF THE METER CAN. |
| | 230.2, 230.70 |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |