Plan Review Details - Permit 08080616
Plan Review Stops For Permit 08080616
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-12-02 Cont ID  
Sent By jwitmer Date 2009-12-02 Time 15:08 Rev Time 0.77
Received By jwitmer Date 2009-12-02 Time 15:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-10-01 Cont ID  
Sent By jwitmer Date 2009-10-01 Time 10:25 Rev Time 0.77
Received By jwitmer Date 2009-10-01 Time 10:25 Sent To  
Notes
2009-10-01 10:37:31BUILDING PLAN REVIEW
 PERMIT: 08080616
 ADD: 8190 OKEECHOBEE BLVD
 CONT: HALLMARK & SONS
 TEL: (561)644-3498
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
 OCT. 01/ 2009
 1) COMPLIED.
 2) PLEASE NOTE ZONING REVIEWERS COMMENTS DEALING WITH
 ACCESSIBLE ROUTE TO THE RIGHT OF WAY. 11-4.1.2
 ACCESSIBLE SITE AND EXTERIOR FACILITIES: NEW
 CONSTRUCTION.
 THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS,
 STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER
 CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON
 OCTOBER 1,1997.
 NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE
 DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
 EXCEPT: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER AS PROVIDED IN SECTION 553.509, FLORIDA
 STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES MUST,
 AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY
 BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS
 OTHERWISE EXEMPT UNDER SECTION 11-4.1.3(5) OF THIS
 CODE.
 AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING MINIMUM
 REQUIREMENTS:
 (1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
 PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED,
 AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 3) PLEASE SEE ZONING COMMENT AS TO THE AMOUNT OF OVER
 ALL PARKING STALLS.
  
 4) PLEASE ALSO SEE ZONINGS COMMENT ABOUT NEW CANOPY,
 ALTHOUGH NOT PART OF THIS PERMIT IT IS A LOADING ZONE
 REQUIRING A MINIMUM CLEARENCE :
 11-4.6.5 VERTICAL CLEARANCE. PROVIDE MINIMUM VERTICAL
 CLEARANCE OF 114 INCHES (2895 MM) AT ACCESSIBLE
 PASSENGER LOADING ZONES AND ALONG AT LEAST ONE VEHICLE
 ACCESS ROUTE TO SUCH AREAS FROM SITE ENTRANCE(S) AND
 EXIT(S). AT PARKING SPACES COMPLYING WITH SECTION
 11-4.1.2(5)(B), PROVIDE MINIMUM VERTICAL CLEARANCE OF
 98 INCHES (2490 MM) AT THE PARKING SPACE AND ALONG AT
 LEAST ONE VEHICLE ACCESS ROUTE TO SUCH SPACES FROM SITE
 ENTRANCE(S) AND EXIT(S).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISC

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-07-06 Cont ID  
Sent By jwitmer Date 2009-07-06 Time 13:30 Rev Time 0.77
Received By jwitmer Date 2009-07-06 Time 13:30 Sent To  
Notes
2009-07-06 13:49:02BUILDING PLAN REVIEW
 PERMIT: 08080616
 ADD: 8190 OKEECHOBEE BLVD
 CONT: HALLMARK & SONS
 TEL: (561)644-3498
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1) PLEASE REVIEW SHEET 2 OF 7C PLANS INDICATE 2
 HANDICAPPED SPACES AWAY FROM THE BUILDING. ACCESSIBLE
 SPACES ARE TO BE LOCATED ONTHE SHORTEST SAFELY
 ACCESSSIBLE ROUTE.
 ALSO NOTE THAT ACCESSIBLE PARKING SPACES SHALL BE
 DISPERSED AND LOCATED CLOSEST TO THE ACCESSIBLE
 ENTRANCES. 11-4.6.2 LOCATION.
 ACCESSIBLE PARKING SPACES SERVING A PARTICULAR BUILDING
 SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE
 ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE. IN PARKING FACILITIES THAT DO NOT SERVE A
 PARTICULAR BUILDING, ACCESSIBLE PARKING SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL TO
 AN ACCESSIBLE PEDESTRIAN ENTRANCE OF THE PARKING
 FACILITY. IN BUILDINGS WITH MULTIPLE ACCESSIBLE
 ENTRANCES WITH ADJACENT PARKING, ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED CLOSEST TO THE
 ACCESSIBLE ENTRANCES.
  
 2) PLEASE NOTE ZONING REVIEWERS COMMENTS DEALING WITH
 ACCESSIBLE ROUTE TO THE RIGHT OF WAY. 11-4.1.2
 ACCESSIBLE SITE AND EXTERIOR FACILITIES: NEW
 CONSTRUCTION.
 THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS,
 STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER
 CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON
 OCTOBER 1,1997.
 NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE
 DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
 EXCEPT: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER AS PROVIDED IN SECTION 553.509, FLORIDA
 STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES MUST,
 AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY
 BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS
 OTHERWISE EXEMPT UNDER SECTION 11-4.1.3(5) OF THIS
 CODE.
 AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING MINIMUM
 REQUIREMENTS:
 (1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
 PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED,
 AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-20 Cont ID  
Sent By jwitmer Date 2008-11-20 Time 15:55 Rev Time 0.77
Received By jwitmer Date 2008-11-20 Time 15:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-05 Cont ID  
Sent By jwitmer Date 2008-09-05 Time 15:50 Rev Time 1.33
Received By jwitmer Date 2008-09-05 Time 15:50 Sent To  
Notes
2008-09-05 16:01:38BUILDING PLAN REVIEW
 PERMIT: 08080616
 ADD: 8190 OKEECHOBEE BLVD
 CONT: HALLMARK & SONS
 TEL: (561)644-3498
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 SEPTEMBER 05, 2008
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) SHEET S-3 SITE LIGHTING, PLEASE PROVIDE FOOTING &
 LIGHT POLE INFORMATION, ALSO PROVIDE WIND DESIGN
 INFORMATION:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status N Date   Cont ID  
Sent By dpalmer Date   Time   Rev Time 0.00
Received By dpalmer Date 2009-06-26 Time 14:52 Sent To  
Notes
2009-06-26 14:49:22NO ELEC PAGES SUBMITTED AS PART OF THE REVISIONS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-01 Cont ID  
Sent By dpalmer Date 2008-12-01 Time 08:28 Rev Time 0.00
Received By dpalmer Date 2008-12-01 Time 08:28 Sent To  
Notes
2008-12-01 08:30:04REDLINED PLANS.
  
  
 1) NOTE: EQUIPMENT GROUNDING CONDUCTOR SHWON BEFORE THE
 FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED.
 250.6,250.24
  
 2) NOTE: PLANS STATE ASTRONOMICAL TIME CLOCK HOWEVER
 NOT BACK UP. A MINIMUM OF 10HR BACK UP IS REQUIRED PER
 13-415.1.ABC.1.4.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-10 Cont ID  
Sent By dpalmer Date 2008-09-10 Time 14:16 Rev Time 0.00
Received By dpalmer Date 2008-09-10 Time 14:16 Sent To  
Notes
2008-09-10 14:16:33 
  
  
  
  
 ** DENIED **
  
 1) NOTE: PLANS SHALL COMPLY WITH FBC 13-415.1.ABC.1.4
 FOR LIGHTING CONTROLS FOR NEW SCOPE OF WORK.
  
 2) NOTE: PLANS SHALL COMPLY WITH FBC 13-415.2.ABC.2.3
 FOR LIGHTING PERFORMANCE CALCULATIONS FOR EXTERIOR
 LIGHTING.
  
 3) NOTE: PLANS NEED TO SHOW CIRCUITING, PANEL SCHEDULE,
 LOADS, CONDUCTORS, BREAKER(S) SIZES ETC.
 408.4, 240.4,310.16, ETC
 FBC 106.3.5.1.2, 106.1.1
  
 4) NOTE: PLEASE SEE 13-413.1.ABC.1.2 FOR VOLTAGE DROP
 REQUIRED.
  
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH
 INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK
 WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE
 REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 8 Status P Date 2010-10-14 Cont ID  
Sent By mgonzale Date 2010-10-14 Time 09:01 Rev Time 1.00
Received By mgonzale Date 2010-10-14 Time 09:01 Sent To  
Notes
2010-10-14 09:35:20PLANS ARE PASSED BASED ON DESCRIPTION:
 REMOVE PARKING SPOT AND REMOVE SOME PAVERS.
  
 PERVIOUS AND IMPREVIOUS INFORMATION WILL BE REPORTED TO
 UTILITIES CUSTOMER SERVICE AS FOLLOWS TO UPDATE CITY
 STORMWATER CHARGES:
  
 ADDRESS: 8200 OKECHOBEE BLVD
 TOTAL SITE IMPERVIOUS: 1.81 AC (79,026 SF)
 TOTAL PERVIOUS SURFACE AREA .82 AC (35,537 SF)
 TOTAL SITE = 2.63 AC (114,563 SF)
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 7 Status P Date 2009-12-04 Cont ID  
Sent By dlauderm Date 2009-12-04 Time 09:00 Rev Time 1.00
Received By dlauderm Date 2009-12-04 Time 08:46 Sent To  
Notes
2009-12-04 09:08:30REVIEWER: DEAN S. LAUDERMILK, PROJECT COORDINATOR
 WORK-494-1083
 FAX: 494-1116
 EMAIL: [email protected]
 PASSED WITH PROVISO:
 1. REVISED PLANS NEED TO BE SUBMITTED SEPARATELY TO
 ENGINEERING SERVICES, ATT.:
 EMERY FABIAN, PROJECT MANAGER FOR THIS PROJECT.
 ENGINEERING REVIEW MAY REQUIRE ADDITIONAL FEES.
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 6 Status F Date 2009-09-30 Cont ID  
Sent By dlauderm Date 2009-09-30 Time 12:58 Rev Time 2.00
Received By dlauderm Date 2009-09-30 Time 12:53 Sent To  
Notes
2009-09-30 12:56:29FAILED.
 REVIEWER: DEAN LAUDERMILK, ENGINEERING PLAN REVIEWER,
 EMAIL: [email protected], OFFICE: 494-1083 (ENG.),
 805-6716 (CONSTRUCTION SERVICES)
 1-NEEDS FIRE REVIEW, ADDED FIRE HYDRANT. WATER AND
 SEWER PLAN ONLY COVERS THIS ITEM SO IT WILL NOT BE
 REVIEWED BY ESD.
 2-SHEET S-1: DUMPSTER CAN NOT BE BUILT INSIDE THE FP&L
 UTILITY EASEMENT, RELOCATE IT.
 3-SHEET S-1: STREET LIGHT IS SHOWN IN THE AREA BEHIND
 THE WHEEL STOP WHERE THE CAR OVERHANGS, RELOCATE TO THE
 NORTH.
 4-SHEET S-2: DUMPSTER IS NOT THE REQUIRED SIZE. THE
 INTERNAL DIMENSIONS NEED TO BE A MINIMUM OF 12.5??? BY
 12.5???. USE MEASUREMENTS IN CITY DETAIL GC-9 FOUND AT
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/STANDARDS/2007_DET
 AILS_PDFS/GENERAL_CONSTRUCTION/GC-9.PDF
 5-NEW IMPERVIOUS AND PERVIOUS CALCULATIONS ARE
 REQUIRED. AERIAL OF SITE SHOWS EXISTING PARKING LOT IN
 THE SOUTH END OF THE PROPERTY IS EXISTING AND IS NOT
 SHOWN TO BE REMOVED.
 6-POLLUTION CONTROL PLAN DOES NOT COVER THE PROTECTION
 OF THE EXISTING AND NEW CATCH BASINS BEFORE, DURING AND
 AFTER CONSTRUCTION. IT MAY BE INCLUDED IN THE NINE PAGE
 POLLUTION CONTROL DOCUMENT LISTED AS NOTE 5 ON THE
 PLAN, BUT IT WAS NOT INCLUDED WITH THESE PLANS.
 7-12' UTILITY EASEMENT ON THE SOUTH SIDE OF THE
 PROPERTY THAT RUNS FROM OKEECHOBEE SOUTH THAT HAS TREES
 IN IT, THIS IS NOT ALLOWED UNLESS THE UTILITY (FP&L)
 SIGNS OFF.
 8-PLANTING THREE TREES ON TOP OF THE WATER AND SEWER
 LINES TO THE EXISTING BUILDING, THIS IS NOT ALLOWED.
 THE ROOT BALL OF TREES NEED TO BE 5??? FROM THE
 UTILITY.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2009-06-19 Cont ID  
Sent By dlauderm Date 2009-06-19 Time 11:34 Rev Time 0.00
Received By dlauderm Date 2009-06-19 Time 11:33 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2009-09-30 Cont ID  
Sent By mgonzale Date 2009-04-29 Time 10:47 Rev Time 1.00
Received By dlauderm Date 2009-04-29 Time 10:46 Sent To  
Notes
2009-04-29 10:47:23*** APPROVED ***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-12-23 Cont ID  
Sent By lwagner Date 2009-01-14 Time 09:30 Rev Time 1.00
Received By mgonzale Date 2008-12-23 Time 15:29 Sent To ENG
Notes
2008-12-23 15:31:19SEE PREVIOUS COMMENT. THE PLAN SHOWS NO SIGNFICANT
 CHANGE AS TO OUR DISCIPLINE.
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-12-04 Cont ID  
Sent By mgonzale Date 2008-12-04 Time 14:11 Rev Time 1.00
Received By mgonzale Date 2008-12-04 Time 14:06 Sent To ENG
Notes
2008-12-04 14:11:37ENGINEERING REVIEW 12/4/08
  
 PLANS HAVE COME THRU THE CITY'S ENGINEERING DEPARTMENT.
 OUTFALL MUST BE INSPECTED BY THE CITY OF WPB.
  
 CONTACT EMERY FABIAN (561) 494-1040
 FOR PRE-CONSTRUCTION AND ASSIGNMENT OF A
 UTILITIES CONSTRUCTION COORDINATOR.
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-09-11 Cont ID  
Sent By rchokshi Date 2008-09-11 Time 13:33 Rev Time 0.00
Received By rchokshi Date 2008-09-11 Time 13:24 Sent To  
Notes
2008-09-11 13:33:12FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B), EFFECTIVE
 MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE, TURBIDITY DETAILS
 ETC., PLANS MUST BE SHOWING SILT FENCE AROUND THE SITE
 & TURBIDITY AROUND STORM CATCH BASIN DRAINS, WATER
 FALLS, LAKES DURING CONSTRUCTION AND ALL DEMOLITION
 PHASE. HEIGHT OF THE SILT FENCE & TURBIDITY SHOULD BE
 HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. DUMPSTER LOCATION ON DWG, MUST BE ACCESSIBLE FOR
 PICKUP TRUCK.
  
 6. PLEASE SHOW ON YOUR STORM WATER QUALITY CALCULATION
 THAT YOU HAVE CONSIDERED FLOOD ZONE AREA, & 5,10, 25,
 100 YEAR FLOOD CRITERIA AND CROWN OF THE ROAD WHEN YOU
 DETERMINE THE FIRST FLOOR ELEVATION. FIRST FLOOR
 ELEVATION SHOULD BE ATLEAST 1 FOOT HIGHER THAN HIGHEST
 CROWN OF THE ROAD.
  
 7. PLEASE SHOW ON DRAINAGE DRAWING THE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREA YOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASE MAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CAN SEE THE LAYOUT OF STORM WATER PIPES FROM ALL
 OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST, AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT & STORM WATER QUALITY CALCULATIONS. STORM WATER
 QUALITY CALS MUST BE APPROVED FROM 1000 45TH STREET
 ENGINEERING SERVICES BEFORE WE ISSUE A PERMIT.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2009-12-02 Cont ID  
Sent By mcarsill Date 2009-12-02 Time 07:31 Rev Time 0.00
Received By mcarsill Date 2009-12-02 Time 07:25 Sent To  
Notes
2009-12-02 07:31:021. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, AND
 AFTER CONSTRUCTION.
  
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 3. BUILDING ADDRESS SHALL BE PROVIDED. A MINIMUM OF AT
 LEAST 6" HIGH AND AT LEAST 1" HIGH NUMBERS ARE
 REQUIRED.
  
 4. SEPARATE PLANS AND PERMITS RTO BE SUBMITTED FOR
 PHASE ON AND PHASE TWO CONSTRUCTION.
  
  
 APPROVED PROVISO;
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2009-10-07 Cont ID  
Sent By mawillia Date 2009-10-07 Time 15:48 Rev Time 0.00
Received By mawillia Date 2009-10-07 Time 15:24 Sent To  
Notes
2009-10-07 15:48:36*****DENIED*****
  
  
 1. PLEASE INDICATE LOCATION OF ALL EXISTING AND
 PROPOSED FIRE HYDRANT(S) APPLICABLE TO THE PROJECT
 SITE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-06-29 Cont ID  
Sent By mawillia Date 2009-06-29 Time 10:54 Rev Time 0.00
Received By mawillia Date 2009-06-29 Time 10:43 Sent To  
Notes
2009-06-29 10:53:43******REVISION APPROVED*****
  
 REVISED SHEET S-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-06-03 Cont ID  
Sent By mawillia Date 2009-06-03 Time 13:47 Rev Time 0.00
Received By mawillia Date 2009-06-03 Time 13:41 Sent To  
Notes
2009-06-03 13:47:53*****REVISION, PBCWD #2, APPROVED*****
  
 PLAN SHEET 2 OF THE SUBMITTED WATER AND SANITARY PLANS
 (SHEETS (1 THRU 7A), WHICH WAS NOT INCLUDED IN THE
 ORIGINAL FILED SET, WAS STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-05-13 Cont ID  
Sent By mawillia Date 2009-05-13 Time 15:19 Rev Time 0.00
Received By mawillia Date 2009-05-13 Time 14:04 Sent To  
Notes
2009-05-13 15:17:46******UNSAT*****
  
 REVISED SHEET S-1 STAMPED, INITIALED, AND DATED,
 HOWEVER THE SUBMITTED WATER AND SANITARY PLANS (SHEETS
 (1 THRU 7A) WAS NOT A PART OF OUR FILED SET. PLAN SHEET
 2 OF THIS SECTION OF THE PLANS WOULD NEED TO BE
 FIRE-STAMPED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-12-01 Cont ID  
Sent By mawillia Date 2008-12-01 Time 16:39 Rev Time 0.00
Received By mawillia Date 2008-12-01 Time 16:32 Sent To  
Notes
2008-12-01 16:38:28******APPROVED*****
  
 SHEET S-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-09-11 Cont ID  
Sent By mwennerg Date 2008-09-11 Time 16:01 Rev Time 0.00
Received By mwennerg Date 2008-09-11 Time 16:01 Sent To  
Notes
2008-09-11 16:02:47***PROVISO***
  
 WORK SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 1, 2003
 CHAPTER 18 FOR EMERGENCY VEHICLE ACCESS.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-11-02 Cont ID  
Sent By lmartine Date 2009-10-29 Time 16:41 Rev Time 0.00
Received By lmartine Date 2009-10-29 Time 16:41 Sent To  
Notes
2009-11-02 16:41:47C--10

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-09-08 Cont ID  
Sent By jwitmer Date 2009-09-08 Time 13:18 Rev Time 0.00
Received By jwitmer Date 2009-09-08 Time 13:18 Sent To  
Notes
2009-09-08 13:19:45INCOMING TO: C-27

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-06-23 Cont ID  
Sent By jgomez Date 2009-06-23 Time 15:31 Rev Time 0.00
Received By jgomez Date 2009-06-23 Time 15:30 Sent To ENG
Notes
2009-06-23 15:35:34SENT TO ENGINEERING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-06-05 Cont ID  
Sent By lmartine Date 2009-06-04 Time 11:17 Rev Time 0.00
Received By lmartine Date 2009-06-04 Time 11:19 Sent To  
Notes
2009-06-05 11:18:24C-20

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-06-05 Cont ID  
Sent By dpalmer Date 2009-04-28 Time 15:52 Rev Time 0.00
Received By lmartine Date 2009-04-28 Time 15:52 Sent To  
Notes
2009-04-28 15:52:59TO C-14

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-17 Cont ID  
Sent By adarroug Date 2008-12-17 Time 10:05 Rev Time 0.00
Received By adarroug Date 2008-12-17 Time 10:05 Sent To Z
Notes
2008-12-17 10:05:37TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 14:54 Rev Time 0.00
Received By adarroug Date 2008-11-04 Time 14:54 Sent To  
Notes
2008-11-04 14:54:20TO "COMM" BD#19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-11 Cont ID  
Sent By mwennerg Date 2008-09-11 Time 16:03 Rev Time 0.00
Received By mwennerg Date 2008-08-28 Time 15:03 Sent To  
Notes
2008-08-28 15:04:25TO "COM" BD. #20.

Review Stop L LANDSCAPING
Rev No 6 Status P Date 2009-11-17 Cont ID  
Sent By rkussner Date 2009-11-17 Time 16:29 Rev Time 0.00
Received By rkussner Date 2009-11-17 Time 16:29 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 5 Status F Date 2009-11-04 Cont ID  
Sent By rkussner Date 2009-11-04 Time 09:11 Rev Time 0.00
Received By rkussner Date 2009-11-04 Time 09:11 Sent To  
Notes
2009-11-04 09:18:41***LANDSCAPE REVIEW FAILED***
  
 1. LANDSCAPE PLAN MUST BE CONSISTANT WITH PLAN
 SUBMITTED THROUGH SITE PLAN PROCESS AND ZONING MUST
 APPROVE PROJECT PRIOR TO LANDSCAPE PERMIT APPROVAL.
  
 2. SUBMIT A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIRALS AND LABOR. IT
 SHALL BE BROKEN DOWN INTO UNIT COST.
  
 3. THE TREE SPECIES ALONG THE EAST AND NORTH PERIMETER
 SHALL BE CHANGED TO A MORE ACCEPTABLE SPECIES. THE
 PROPOSED TREES ARE HARD TO FIND THAT MEET THE REQUIRED
 FLORIDA #1 GRADE AND THERE ARE OTHER PROBLEMS
 ASSOCIATED WITH THIS SPECIES. THE APPLICANT SHALL GO
 BACK TO THE PINK TABEBUIA OR OTHER ACCEPTABLE SPECIES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  

Review Stop L LANDSCAPING
Rev No 4 Status F Date 2009-09-23 Cont ID  
Sent By rkussner Date 2009-09-23 Time 14:39 Rev Time 0.00
Received By rkussner Date 2009-09-23 Time 14:39 Sent To  
Notes
2009-09-23 15:00:49***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PROVIDE A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR. IT
 SHALL BE BROKEN DOWN INTO UNIT COST.
  
 2. PROPOSED LANDSCAPING ALONG THE OKEECHOBEE BOULEVARD
 LANDSCAPE BUFFER IS NOT CONSISTENT WITH WHAT THE
 REMAINDER OF THE SHOPPING PLAZA HAS PLANTED ALONG THE
 OKEECHOBEE FRONTAGE. STAFF RECOMMENDS THAT THE ENTIRE
 FRONTAGE BE CONSISTENT. THAT WILL INVOLVE INSTALLING
 PALM GROUPINGS COMPOSED OF THREE SABAL PALMS AND
 ALTERNATING WITH MAHOGANY TREES. THE PALMS SHOULD BE
 UNDERPLANTED WITH FAKAHATCHEE GRASS. THE PROPOSED
 PLANTING LOOKS DISJOINTED AND DOES NOT RELATE TO THE
 BALANCE OF THE SITE.
  
 3, PURSUANT TO SECTION 94-443 (C)(3)(C), WHEN DIVIDER
 MEDIANS ARE USED, SHADE OR FLOWERING TREES WITHIN THE
 DIVIDER MEDIAN SHALL BE PLANTED AT 30-FOOT INTERVALS. A
 MINIMUM OF TWO (2) SHADE OR FLOWERING TREES ARE
 REQUIRED IN THE SQUARE LANDSCAPE AREA IN THE MIDDLE OF
 THE FRONT PARKING LOT.
  
 4. THERE IS A SYMBOL 'AN' ADJACENT TO THE SIGN BUT IT
 IS NOT POINTING TO ANYTHING. PLEASE CLARIFY IF THE
 ANNUALS ARE BEING PROPOSED AROUND THE SIGN..
  
 5. THERE ARE EXISTING SABAL PALM GROUPINGS AT THE FRONT
 CORNERS OF THE BUILDING. THERE IS A NOTE ON THE PLAN
 THAT EXISTING PALMS WILL REMAIN, BUT IT DOESN'T POINT
 TO ANYTHING. . PLEASE SHOW ALL TREE AND PLANT MATERIAL
 THAT WILL REMAIN. ALL EXISTING VEGETATION SHALL
 ACCURATELY BE IDENTIFIED.
  
 6. PURSUANT TO SECTION 94-445 (4)(G)(3), AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED
 LANDSCAPE AREAS FOR ALL PROPERTIES. THIS INCLUDES THE
 RIGHT-OF-WAY.
  
 7. THE LANDSCAPING ALONG THE WEST PERIMETER OF THE SITE
 WILL BE PLANTED WITHIN AN FPL EASEMENT. WRITTEN
 AUTHORIZATION TO PLANT WITHIN THAT OR ANY OTHER
 EASEMENT WILL BE REQUIRED AT THE TIME OF SITE PLAN
 REVIEW.
  
 8. APPLY FOR A TREE ALTERATION PERMIT AND PROVIDE TWO
 (2) COPIES EACH OF THE PLANTING AND VEGETATIVE ACTION
 PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2009-06-11 Cont ID  
Sent By rkussner Date 2009-06-11 Time 09:48 Rev Time 0.00
Received By rkussner Date 2009-06-11 Time 09:48 Sent To  
Notes
2009-06-11 09:58:31***LANDSCAPE REVIEW FAILED***
  
 1. THE STREET LIGHTS SHALL BE REMOVED FROM THE
 LANDSCAPE ISLANDS. THE TREES SHALL BE CENTERED WITHIN
 THE ISLANDS TO MAXIMIZE THE SHADE PROVIDED TO THE
 ADJACENT PARKING STALLS. THE STREET LIGHT ALONG THE
 WEST SIDE OF THE ENTRANCE TRAVEL AISLE SHALL BE LOCATED
 ELSEWERE TO ALLOW THE FOURTH MAGNOLIA TO BE PLANTED.
  
 2. REPEAT COMMENT: SUBMIT A CERTIFIED COST ESTIMATE
 BROKEN DOWN INTO UNIT COST THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-14662.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-05-08 Cont ID  
Sent By rkussner Date 2009-05-08 Time 16:39 Rev Time 0.00
Received By rkussner Date 2009-05-08 Time 16:39 Sent To  
Notes
2009-05-08 17:41:32***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVEIW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PURSUANT TO SECTION 94-443 (C)(3)(A), ALL TERMINAL
 LANDSCAPE ISLANDS SHALL CONTAIN AT LEAST ONE SHADE OR
 FLOWERING TREE. A TREE SHALL BE ADDED AT THE WEST END
 OF THE SOUTH PARKING ROW.
  
 2. PURSUANT TO SECTION 94-443 (C)(4), FOR OTHER PAVED
 AREAS UTILIZED BY MOTOR VEHICLES, INCLUDING ASILES,
 LOADING AREAS, CIRCULATION AREAS AND DRIVE-IN SERVICE
 AREAS, ADDITIONAL LANDSCAPING SHALL BE PROVIDED AS
 FOLLOWS: FOUR SQUARE FEET OF LANDSCAPED AREA SHALL BE
 REQUIRED FOR EACH 100 SQUARE FEET, OR FRACTION
 THEREROF. ADDTIONAL TREES SHALL BE PLANTED AROUND THE
 NORTHWEST CORNER OF THE VEHICULAR USE AREA LOCATED
 NORTH OF THE LOADING AREA.
  
 3. TREES AND PLANTING SHALL BE INSTALLED ON THE WEST
 SIDE OF THE ENTRY AISLE TO MACH WHAT WAS PLANTED ON THE
 EAST SIDE OF THE AISLE.
  
 4. PROVIDE THE LOCATION OF THE DUMPSTER ENCLOSURE.
  
 5. IN KEEPING WITH XERISCAPE GUIDELINES, PLEASE
 UNDERPLANT THE PROPOSED PALMS LOCATED ON THE NORTH SIDE
 OF THE BUILDING.
  
 6. SUBMIT A CERTIFIED COST ESTIMATE BROKEN DOWN INTO
 UNIT COST THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE
 MATERILALS AND LABOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop L LANDSCAPING
Rev No 1 Status F Date   Cont ID  
Sent By RAK Date 2008-12-23 Time   Rev Time 0.00
Received By rkussner Date 2009-09-23 Time 14:38 Sent To PC
Notes
2008-12-23 09:49:11***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-444 (B), WALLS THAT SURROUND
 A DUMPSTER ENCLOSURE SHALL BE LANDSCAPED WITH SHRUBS
 AND HEDGES PLANTED AT TWO-FOOT INTERVALS.
  
 2. PURSUANT TO SECTION 94-443 (B)(4), AT LEAST ONE
 SHADE OR FLOWERING TREE SHALL BE PLANTED IN A REQUIRED
 BUFFER STRIP FOR EACH 30 LINEAR FEET OR PORTION
 THEREOF. THERE ARE GAPS THAT EXCEED 30 FEET BETWEEN THE
 TREES ALONG THE EAST AND WEST SIDES OF THE SITE.
  
 3. A LARGE SHADE OR FLOWERING TREE (OR TREES) SHALL BE
 PLANTED WITHIN THE ROUNDABOUT LOCATED IN THE SOUTHWEST
 QUADRANT OF THE SITE.
  
 4. PURSUANT TO SECTION 94-443 (C)(3), THE SHADE TREES
 SHALL BE LOCATED IN SUCH A MANNER TO PRODUCE MAXIMUM
 OVERHEAD CANOPY FOR THE VEHICLES. THE PROPOSED TREE IN
 THE TERMINAL LANDSCAPE ISLAND LOCATED NORTH OF THE
 ROUNDABOUT SHALL BE CENTERED WITH THE ADJACENT PARKING
 STALL. IN ADDITION, BECAUSE THE ITERMINAL SLAND
 ADJACENT TO THE HANDICAP SPACE AT THE NORTHWEST CORNER
 OF THE BUILDING IS LARGE, AN ADDITIONAL SHADE TREE
 SHALL BE ADDED NEXT TO THE PARKING STALL TO PROVIDE
 SHADE. THE TREE SHALL BE OF THE SAME SPECIES AS THE
 OTHER PROPOSED TREES TO BE PLANTED IN THE OTHER ISLAND
 WITHIN THAT PARKING LOT.
  
 5. THERE ARE NO PROPOSED TREES TO PROVIDE SHADE FOR THE
 CHILDREN ALONG THE EAST OR WEST SIDES OF THE PLAY AREA.
 IF THE LANDSCAPE AREA WHERE THE PROPOSED HEDGES ARE TO
 BE PLANTED WERE EXPANDED, TREES COULD BE INSTALLED
 BETWEEN THE FENCE AND SIDEWALK.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-01-14 Cont ID  
Sent By lwagner Date 2009-01-14 Time 09:30 Rev Time 0.00
Received By lwagner Date 2009-01-14 Time 09:30 Sent To  
Notes
2009-01-14 09:29:53IRRIGATION PERMIT REQUIRED

Review Stop Z ZONING
Rev No 7 Status P Date 2009-11-18 Cont ID  
Sent By eschneid Date 2009-11-18 Time 16:05 Rev Time 0.33
Received By eschneid Date 2009-11-18 Time 16:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 6 Status F Date 2009-09-21 Cont ID  
Sent By eschneid Date 2009-09-21 Time 16:41 Rev Time 1.00
Received By eschneid Date 2009-09-21 Time 16:41 Sent To  
Notes
2009-09-21 17:04:41FAILED
  
 1) THE DUMPSTER ENCLOSURE DOES NOT CONFORM TO CITY OF
 WEST PALM BEACH MINIMUMS. PLEASE PROVIDE STANDARD
 DETAIL.
  
 2) NEED AN EASEMENT RELEASE FROM FPL TO PUT THE
 DUMPSTER PAD AND ENCLOSURE IN THE FPL EASEMENT.
  
 3) THE HC PARKING ROW CONTAINS 7 PARKING SPACES, YET
 THE COUNT ON THE PLANS SHOWS 8. THE PARKING TABLE SHALL
 BE CORRECTED TO SHOW THE 146 PARKING SPACES THAT ARE
 SHOWN AS PROVIDED ON THE PLAN.
  
 4) THE ENGINEERING SERVICES DEPARTMENT SHALL APPROVE,
 IN WRITING, THE USE OF WHEEL STOPS 6 INCHES FROM THE
 EDGE OF PAVEMENT WITH THE 1.5 FOOT OVERHANG AS SHOWN.
 THE APPROVAL SHALL INCLUDE THAT THE PROPOSAL WILL
 PROVIDE ADEQUATE STRENGTH TO SECURE THE WHEEL STOPS
 WITHOUT DAMAGE TO THE PAVING. PLEASE NOTE, IF THE
 ENGINEERING SERVICES DEPARTMENT DOES NOT APPROVE THE
 PROPOSAL, THEN A TYPE "D" CURB IS REQUIRED.
  
 5) PROVIDE PARKING DETAILS FOR ALL OF THE PARKING
 CONFIGURATIONS USED ON THE PLAN. PLEASE NOT THAT THE
 SITE AND CIVIL PLANS SHALL SHOW THE SAME CONDITIONS IF
 BOTH SETS OF PLANS PROVIDE DETAILS.
  
 6) THE STRIPING PLAN INCORRECTLY LABELS PHASE 1 AND 2.
  
 7) HOW WILL PHASE 1 AND 2 BE SEPARATED BEFORE PHASE 2
 IS COMMENCED?
  
 8) THE MAXIMUM FOOT CANDLES ALONG THE SOUTH PROPERTY
 LINE MAY BE 0.5.
  
 9) THE BIKE RACK DETAIL DOES NOT CONFORM TO CITY
 STANDARDS - THE WAVE IS NOT ALLOWED. PLEASE CONTACT
 ALEX HANSEN AT (561) 822- 1463 FOR DETAILS. PROVIDE THE
 BIKE PARKING AREA DIMENSIONS ON THE PLAN TO VERIFY THAT
 IT CONTAINS PARKING FOR A MINIMUM OF 6 BICYCLES.
  
 10) THE HEIGHT OF THE NEW PORTE-COCHERE SHALL BE
 PROVIDED ON THE PLANS.
  
 11) THE TERMINAL ISLAND ADJACENT TO THE 10 SPACE
 PARKING ROW ON THE SOUTH SIDE OF THE BUILDING SHALL BE
 A MINIMUM OF 5 FEET WIDE WHEN MEASURED INSIDE THE
 CURBS.
  
 PLEASE NOTE THAT A REVISED PLAN MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 5 Status F Date 2009-06-10 Cont ID  
Sent By eschneid Date 2009-06-10 Time 16:41 Rev Time 0.75
Received By dlauderm Date 2009-06-10 Time 16:41 Sent To FIRE
Notes
2009-06-10 16:58:05FAILED
  
 PROVIDE ANSWERS IN WRITING.
  
 1) REPEAT COMMENT (IN PART): THE HANDICAP SPACES ARE
 REQUIRED TO BE THE CLOSEST SPACES TO THE ACCESSIBLE
 ENTRANCE(S). ALL HC SPACES NEED TO BE LOCATED IN THE
 NEW PARKING AREA NORTH OF THE ENTRANCE - THE TWO SPACES
 ON THE NORTH SIDE OF THE DRIVE AISLE DO NOT MEET ADA
 REQUIREMENTS. PLEASE NOTE THE BUILDING REVIEWER
 COMMENTS ON THE POSSIBLE NEED TO LOCATE SPACES AT THE
 REAR OF THE BUILDING.
  
 2) REPEAT COMMENT (IN PART): THE SOUTHERNMOST
 CROSS-WALK NOT COUNT AS A CONNECTION TO A PUBLIC
 SIDEWALK AS IT DOES NOT ALIGN WITH THE SEDONA COMMONS
 SIDEWALK. ADDITIONALLY, THE SEDONA COMMONS SIDEWALK MAY
 BE REMOVED AS PART OF THE REDEVELOPMENT OF THAT AREA OF
 THE SITE.
  
 3) REPEAT COMMENT (IN PART): THE (NEW) NORTHERNMOST
 CROSS-WALK DOES NOT ALIGN WITH THE PROPOSED SEDONA
 COMMONS SIDEWALK.
  
 4) THE CONNECTION TO THE PUBLIC ROW SHALL BE
 CONSTRUCTED TO OKEECHOBEE BLVD. AND SHALL BE SHOWN ON
 ALL PLANS.
  
 PLEASE NOTE THAT THE REVISED PLANS MAY GENERATE NEW
 COMMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 4 Status F Date 2009-05-07 Cont ID  
Sent By eschneid Date 2009-05-07 Time 17:00 Rev Time 1.50
Received By eschneid Date 2009-05-07 Time 17:00 Sent To  
Notes
2009-05-07 17:18:07FAILED
  
 PROVIDE ANSWERS IN WRITING.
  
 1) WHAT HAPPENED TO THE DAY CARE THAT WAS SUBMITTED AS
 A PREVIOUS REVISION?
  
 2) THE PARKING DATA TABLE IS STILL CALCULATED WITH THE
 DAY CARE INCLUDED, YET THE DAYCARE IS NOT SHOWN ON
 PLANS. THE PARKING COUNTS DO NOT MATCH THE PARKING
 SHOWN.
  
 3) THE HANDICAP SPACES ARE REQUIRED TO BE THE CLOSEST
 SPACES TO THE ACCESSIBLE ENTRANCE. ALL HC SPACES NEED
 TO BE LOCATED IN THE NEW PARKING AREA NORTH OF THE
 ENTRANCE. OTHER PARKING SHALL BE ADJUSTED ACCORDINGLY.
  
 4) THE SOUTHERNMOST CROSS-WALK IS SHOWN DIFFERENTLY ON
 THE VARIOUS PLANS, AND DOES NOT MATCH THE PREVIOUSLY
 APPROVED VERSION (6/18/08). NOTE THAT THE SEDONA
 COMMONS PORTION OF THE CONNECTION IS NOT PLANNED TO BE
 BUILLT AT THIS TIME AND THUS THE CONNECTION TO THE
 PUBLIC ROW WILL NOT EXIST AS INDICATED AND A SIDEWALK
 TO OKEECHOBEE BLVD. MAY BE NEEDED.
  
 5) THE (NEW) NORTHERNMOST CROSS-WALK DOES NOT ALIGN
 WITH THE SEDONA COMMONS SIDEWALK AND RUNS INTO A TREE
 AND HEDGE ON THE LANDSCAPE PLAN.
  
 6) THE CIVIL PLANS SHALL SHOW PROTECTION OF THE
 LANDSCAPE AREAS WITH A D-CURB IN ALL LOCATIONS (NOT
 CLEAR AT NORTHERN DRIVE TO OKEECHOBEE BLVD).
  
 7) THE LANDSCAPE PLANS SHALL CLEARLY SHOW CURBING ALONG
 THE EAST PROPERTY LINE SOUTH OF THE DRIVEWAY CONNECTION
 TO SEDONNA COMMONS.
  
 8) IT APPEARS THE NEW LANDSCAPE PLAN HAS A TREE BEING
 INSTALLED ON TOP OF AN EXISTING CATCH BASIN IN THE
 NORTHEAST CORNER OF THE SITE (NONE SHOWN ON PREVIOUS
 PLANS).
  
 9) A REVISED TREE ALTERATION PERMIT IS REQUIRED.
  
 PLEASE NOTE THAT THE REVISED PLANS MAY GENERATE NEW
 COMMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-12-22 Cont ID  
Sent By eschneid Date 2008-12-22 Time 17:21 Rev Time 0.00
Received By eschneid Date 2008-12-19 Time 08:59 Sent To  
Notes
2008-12-22 17:40:48FAILED
  
 1) THE REQUIRED PARKING NUMBERS SHALL INCLUDE ALL OF
 THE BUILDINGS ON THE SITE. ADDITIONALLY, THEY SHALL BE
 CALCULATED CORRECTLY.
  
 2) THE REQUIRED HEDGE IS NOT SHOWN AROUND THE DUMPSTER
 ON THE LANDSCAPE PLAN.
  
 3) ALL FENCING SHALL BE UNDER A SEPARATE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-11-19 Cont ID  
Sent By adavila Date 2008-11-19 Time 16:47 Rev Time 0.00
Received By adavila Date 2008-11-19 Time 13:43 Sent To  
Notes
2008-11-19 16:47:36PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2009-01-14 Cont ID  
Sent By adavila Date 2008-09-03 Time 12:06 Rev Time 0.00
Received By adavila Date 2008-09-03 Time 12:06 Sent To ENG
Notes
2008-09-03 12:07:28PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. THE PAVING AND DRAINING PLANS SHOW LIGHT POLES IN
 LOCATIONS NOT APPROVED PER THE APPROVED SITE PLAN,
 LANDSCAPE PLAN AND PHOTOMETRIC PLAN. PLEASE REVISE.
 2. NEW LIGHT POLES SHOW CONFLICT WITH THE APPROVED
 LANDSCAPE. LIGHT POLES SHALL BE RELOCATED SO AS TO NOT
 PRESENT ANY CONFLICT.
 3. DUMPSTER ENCLOSURE DETAIL DOES NOT MATCH THE
 DUMPSTER ENCLOSURE DETAIL ON THE APPROVED SITE PLAN.
 PLEASE REVISE.
 4. ALL PLANS SHALL SHOW SAME CONDITIONS (SITE PLAN,
 LANDSCAPE PLAN, PHOTOMETRIC PLAN, PAVING AND DRAINAGE
 PLANS, ETC.)
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.