Plan Review Details - Permit 08080615
Plan Review Stops For Permit 08080615
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-01-28 Cont ID  
Sent By mjacobs Date 2009-01-28 Time 10:44 Rev Time 0.00
Received By mjacobs Date 2009-01-28 Time 10:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-12-08 Cont ID  
Sent By mjacobs Date 2008-12-08 Time 08:30 Rev Time 0.00
Received By mjacobs Date 2008-12-08 Time 08:30 Sent To  
Notes
2008-12-08 08:30:112ND REVIEW
 BUILDING PLAN REVIEW
 PERMIT: 08080615
 ADD: 2616 E TAMARIND AVE.
 CONT: YAVEL CONSTRUCTION
 TEL: (561)512-9341
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12-8-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) OK
  
 **PARTIALY ADDRESSED: WHAT IS THE USE AND OCCUPANCY**
 4) THE PLANS NEED TO INDICATE THE TYPE OF BUILDING PER
 FBC CHAPTER 6, THE USE AND OCCUPANCY PER CHAPTER 3 AND
 THE OCCUPANT LOAD PER TABLE 1004.1.2.
  
 5) OK
  
 **SOME DETAILS ARE STILL NOT CLEAR. WILL THERE BE A NEW
 SECTION OF THE FLAT ROOM ADDED? IF SO, PLEASE PROVIDE
 THE PRODUCT APPROVAL AND INDICATE THE SYSTEM WHICH WILL
 BE USED. SEE ROOFING POLICY IN PACKAGE.**
 6) THE PLANS SHALL CLEARLY SHOW THE EXISTING STRUCTURAL
 AND FLOOR LAYOUT AND THE PROPOSED CHANGES SHALL BE
 CLEARLY SHOWN ON THE DRAWINGS. THE DRAWINGS SUBMITTED
 SHOW NO DISTENTION BETWEEN THE EXISTING LAYOUT AND THE
 PROPOSED LAYOUT. PRODUCT APPROVALS WERE SUBMITTED FOR
 TWO DOORS HOWEVER, THE DRAWINGS DO NOT SHOW WHICH DOORS
 WILL BE CHANGED. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE CODE. FBC 106.1.1
  
 7) PROVIDE A DETAIL WALL LEGEND SHOWING THE DIFFERENT
 TYPES OF WALLS TO BE CONSTRUCTED AND THE EXISTING
 WALLS. SHOW THE SLOPE OF THE NEW SLAB LEADING TO THE
 LOADING DOCK AREA ON SHEET 2 OF 3. SOME OF THE DETAIL
 INFORMATION PERTAINING TO THE COVERED ENTRY IS NOT
 LEGIBLE.
  
 8) OK
  
 9) SHEET #3 SHOWS THE NEW ROOF JOISTS AS 2X12 SO, HOW
 CAN THE FASCIA BOARD BE 1X10? ALSO ONE DETAIL SHOWS THE
 SPACING OF THE JOISTS AT 24 INCHES ON CENTER AND OTHER
 SHOWS THE SPACING AS 16 INCHES ON CENTER. CLARIFY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-10 Cont ID  
Sent By mjacobs Date 2008-09-10 Time 15:29 Rev Time 0.00
Received By mjacobs Date 2008-09-10 Time 09:51 Sent To  
Notes
2008-09-10 15:29:499-10-08
 BUILDING PLAN REVIEW
 PERMIT: 08080615
 ADD: 2616 E TAMARIND AVE.
 CONT: YAVEL CONSTRUCTION
 TEL: (561)512-9341
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) THE PLANS NEED TO INDICATE THE TYPE OF BUILDING PER
 FBC CHAPTER 6, THE USE AND OCCUPANCY PER CHAPTER 3 AND
 THE OCCUPANT LOAD PER TABLE 1004.1.2.
  
 5) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 6) THE PLANS SHALL CLEARLY SHOW THE EXISTING STRUCTURAL
 AND FLOOR LAYOUT AND THE PROPOSED CHANGES SHALL BE
 CLEARLY SHOWN ON THE DRAWINGS. THE DRAWINGS SUBMITTED
 SHOW NO DISTENTION BETWEEN THE EXISTING LAYOUT AND THE
 PROPOSED LAYOUT. PRODUCT APPROVALS WERE SUBMITTED FOR
 TWO DOORS HOWEVER, THE DRAWINGS DO NOT SHOW WHICH DOORS
 WILL BE CHANGED. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE CODE. FBC 106.1.1
  
 7) PROVIDE A DETAIL WALL LEGEND SHOWING THE DIFFERENT
 TYPES OF WALLS TO BE CONSTRUCTED AND THE EXISTING
 WALLS. SHOW THE SLOPE OF THE NEW SLAB LEADING TO THE
 LOADING DOCK AREA ON SHEET 2 OF 3. SOME THE DETAIL
 INFORMATION PERTAINING TO THE COVERED ENTRY IS NOT
 LEGIBLE.
  
 8) THE PLANS NEED TO STATE THE POINT LOAD, FLOOR LOAD
 AND CONCENTRATED LOAD OF THE DECK PER FBC 1604.8.3 AND
 1607. FOR THE GUARD RAILS SEE 1607.7.1/1607.7.1.1 AND
 TABLE 1607.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-01-26 Cont ID  
Sent By btrobaug Date 2009-01-26 Time 15:07 Rev Time 0.00
Received By btrobaug Date 2009-01-26 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-16 Cont ID  
Sent By btrobaug Date 2008-12-16 Time 08:21 Rev Time 0.00
Received By btrobaug Date 2008-12-08 Time 16:11 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-03 Cont ID  
Sent By btrobaug Date 2008-09-03 Time 13:09 Rev Time 0.00
Received By btrobaug Date 2008-09-03 Time 12:52 Sent To  
Notes
2008-09-03 13:08:27 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES AND EQUIPMENT TO BE INSTALLED UNDER THIS
 PERMIT, ALL THAT'S SHOWN IS TWO LIGHT FIXTURES AND ONE
 SWITCH IN THE STORAGE ROOM INDICATE IF
 NEW OR EXISTING. 106.3.5 FBC.
  
 2} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED
 UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY
 IN THE FIELD AND COMPLIANCE WITH 106.1.3 FBC AS
 AMENDED.
  
 3} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B)..
 INDICATE COMPLIANCE ON THE PLAN, IF EXISTING LOCATE
 SAME.
  
 AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF WORK
 PURPOSED. 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-28 Cont ID  
Sent By mawillia Date 2009-01-28 Time 11:12 Rev Time 0.00
Received By mawillia Date 2009-01-28 Time 10:53 Sent To  
Notes
2009-01-28 11:09:08*****APPROVED*****
  
  
 PLAN SHEETS 1 & 2 (OF 3) WERE STAMPED, INITIALED, AND
 DATED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-26 Cont ID  
Sent By mwennerg Date 2008-12-26 Time 11:26 Rev Time 0.00
Received By mwennerg Date 2008-12-26 Time 11:26 Sent To  
Notes
2008-12-26 11:32:29***DENIED***
  
 1) PROVIDE THE OCCUPANCY CLASSIFICATION IN ACCORDANCE
 WITH NFPA 101, CHAPTER-6.
  
 2) SHEET 2 ILLUSTRATES THREE (3) NEW EXIT SIGNS.
 CLEARLY SHOW HOW THE MEANS OF EGRESS LEAD TO EXIT
 DISCHARGE FROM THE STRUCTURE.
  
 3) SHOW NEW OR EXISTING ADDRESS ON THE BUILDING ON
 SHEET 1 ELEVATION DRAWING.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-22 Cont ID  
Sent By adarroug Date 2009-01-22 Time 11:25 Rev Time 0.00
Received By adarroug Date 2009-01-22 Time 11:25 Sent To  
Notes
2009-01-22 11:25:19TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-16 Cont ID  
Sent By adarroug Date 2008-12-16 Time 08:45 Rev Time 0.00
Received By adarroug Date 2008-12-16 Time 08:45 Sent To P
Notes
2008-12-16 08:50:48TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-04 Cont ID  
Sent By adarroug Date 2008-12-04 Time 08:49 Rev Time 0.00
Received By adarroug Date 2008-12-04 Time 08:49 Sent To  
Notes
2008-12-04 08:51:40TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-11 Cont ID  
Sent By mperson Date 2008-09-11 Time 08:56 Rev Time 0.00
Received By mperson Date 2008-08-28 Time 14:55 Sent To PC
Notes
2008-08-28 14:57:45TO "BOB" BD #4.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-02-03 Cont ID  
Sent By kstevens Date 2009-02-03 Time 07:54 Rev Time 0.00
Received By kstevens Date 2009-02-02 Time 16:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-12-24 Cont ID  
Sent By kstevens Date 2008-12-24 Time 15:39 Rev Time 0.00
Received By kstevens Date 2008-12-24 Time 15:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-11 Cont ID  
Sent By btrobaug Date 2008-12-16 Time 08:29 Rev Time 0.00
Received By mperson Date 2008-09-11 Time 08:13 Sent To I
Notes
2008-09-11 08:54:39PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. DECLARE THE GOVERNING CODE. (FBC-2004 WITH 2007
 REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 3. PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT
 IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE -
 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY..
  
 4. SHEET 2 OF 3, "B" TRENCH DRAIN DETAIL: CLEARLY
 INDICATE ON THE RESUBMITTED PLANS THE FOLLOWING
 INFORMATION PER THE FOLLOWING FBC-2004 PLUMBING
 SECTIONS.
  
 A} CLEARLY INDICATE THE SIZE OF THE TRENCH DRAIN. IS
 THIS A PREFABRICATED TRENCH DRAIN? IF THIS IS A
 PREFABRICATED TRENCH DRAIN CLEARLY INDICATE THE MAKE
 AND MODEL NUMBER ON THE DETAIL. PER SECTION 1101.1
 SCOPE.
  
 B} CLEARLY INDICATE WHERE THE DISCHAGE OF THE STORM
 WATER FOR THE TRENCH DRAIN IS LOCATED AND THE SIZE OF
 THE DRAIN PIPE ON THE RESUBMITTED PLANS. WILL THE
 TRENCH DRAIN DISCHARGE INTO AN EXISTING CATCH BASIN OR
 UNDERGROUND STORM PIPE? PLEASE CLARIFY THIS PER SECTION
 1101.1 SCOPE.
  
 5. SHEET 2 OF 3, 1ST FLOOR PLAN IS INDICATING A STORAGE
 ROOM ADDITION. PLEASE PROVIDE A ROOF PLAN THAT
 INDICATES HOW THE ROOF WILL BE PITCHED TO PROPERLY
 DRAIN, AND INDICATE THE FOLLOWING INFORMATION PER THE
 FOLLOWING CODE REFERENCES.
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF AND
 VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS AND
 SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004 PLUMBING,
 SECTION 1106.
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
 6. SHEET 2 OF 3, COVER ENTRY AND BALCONY DETAIL DOES
 NOT CLEARLY INDICATE HOW THE BALCONY WILL DRAIN STORM
 WATER. PLEASE CLARIFY THE DETAILAND CLEARLY INDICATE
 HOW THE BALCONY WILL DISCHARGE STORM WATER. PRIMARY AND
 SECONDARY DRAINS MAY BE REQUIRED FOR THE BALCONY. PER
 FBC-2004 PLUMBING SECTION 1101.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2009-01-27 Cont ID  
Sent By eschneid Date 2009-01-27 Time 16:35 Rev Time 0.50
Received By eschneid Date 2009-01-27 Time 16:35 Sent To  
Notes
2009-01-27 16:40:50PASSED W/PROVISO
  
 A SHADE OR FLOWERING TREE SHALL BE PLANTED IN THE
 SOUTHEAST CORNER OF THE SITE (OUTSIDE OF THE 15 FOOT
 EASEMENT) PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY. THE TREE SHALL BE PLANTED IN ACCORDANCE WITH
 THE PLANTING DIAGRAM ATTACHED TO THE PLAN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-09-09 Cont ID  
Sent By adavila Date 2008-09-09 Time 13:52 Rev Time 0.00
Received By adavila Date 2008-09-09 Time 13:51 Sent To  
Notes
2008-09-09 13:53:00PROVISO SHADE/FLOWER TREE SHALL BE PLANTED ON THE
 SOUTHEAST CORNER OF THE SITE AS SHOWN ON THE SURVEY PER
 THE ATTACHED PLANTING DETAILS.
  
 PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  