Plan Review Details - Permit 08080590
Plan Review Stops For Permit 08080590
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-27 Cont ID  
Sent By mjacobs Date 2008-10-27 Time 10:11 Rev Time 0.00
Received By mjacobs Date 2008-10-27 Time 10:11 Sent To PC
Notes
2008-10-27 10:28:58REVISION FOR SING INFORMATION TO MOONUMENT FOR
 MICHEALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-14 Cont ID  
Sent By mjacobs Date 2008-10-14 Time 09:53 Rev Time 0.00
Received By mjacobs Date 2008-10-14 Time 09:53 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-06 Cont ID  
Sent By mjacobs Date 2008-10-06 Time 12:01 Rev Time 0.00
Received By mjacobs Date 2008-10-06 Time 12:01 Sent To PC
Notes
2008-10-06 12:01:37PLANS WILL BE STAMPED WHEN FEES ARE PAID.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-18 Cont ID  
Sent By mjacobs Date 2008-09-18 Time 15:11 Rev Time 0.00
Received By mjacobs Date 2008-09-18 Time 13:34 Sent To PC
Notes
2008-09-18 15:04:50BUILDING PLAN REVIEW
 PERMIT: 08080590
 ADD: 2021 OKEECHOBEE BLVD
 CONT: BROADWAY SIGN & LIGHTING
 TEL: (561) 748-6282
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 9-18-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) THE ENGINEERED DRAWINGS AND CALCULATION SUBMITTED
 FOR THE INSTALLATION OF THE SIGN CONTAIN AN ORIGINAL
 SEAL OVER PHOTO-COPY SIGNATURES WHICH DO NOT CONFORM TO
 OUR RECORD KEEPING PRACTICES PER 106.1.3*. A
 PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND AFFIX HIS
 SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, FINAL BID
 DOCUMENTS BEING FILED FOR PUBLIC RECORD. ALL DRAWINGS,
 REPORTS AND SPECIFICATIONS BEING FILED FOR PUBLIC
 RECORD SHALL CONTAIN ORIGINAL SEALS, DATE AND
 SIGNATURES. THE PLANS ARE ALSO MISSING THE TITLE BLOCK
 AS REQUIRED PER FAC 61G15-23.002 AND FBC 106.1.
  
 2) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FRO PERMITTING PURPOSES VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, AND ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT EXCLUDING
 LAND.
  
 3) WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION 6 OF ASCE 7. FBC
 1609.1.1 PLEASE SHOW THIS INFORMATION ON THE PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-10 Cont ID  
Sent By dpalmer Date 2008-10-10 Time 10:24 Rev Time 0.00
Received By dpalmer Date 2008-10-10 Time 10:24 Sent To B
Notes
2008-10-10 10:25:49REDLINED 600.5,
 ALL LISTINGS OF ITEMS TO BE VIF. 110.3
  
 ** PLANS ROUTED TO BUILDING FOR PROCESSING AND FINAL
 STAMPING.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-06 Cont ID  
Sent By dpalmer Date 2008-10-06 Time 08:25 Rev Time 0.00
Received By dpalmer Date 2008-10-06 Time 08:25 Sent To B
Notes
2008-10-06 08:25:33 
 ** DENIED 2ND REVIEW **
  
 ** SOME NOTES FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING.
  
 1) NOTE: AS REQUESTED ON PREVIOUS REVIEW. THE APPLIED
 VALUE FOR THE SCOPE OF WORK WAS NOT ADJUSTED PER FBC
 108.3. IT IS NOT POSSIBLE TO DESIGN, CONSTRUCT, AND
 INSTALL THIS SIGN ON THE APPLIED VALUE OF $1,500.
 THIS IS PLACING FALSE INFORMATION ON PERMIT APPLICATION
 AS THE SCOPE OF WORK IS SUBSTANTIALLY HIGHER. PLEASE
 ADJUST VALUE OR ONE WILL BE ASSESSED USING THE LATEST
 ADOPTED STANDARDS BY ICC, FBC.
  
 2) NOTE: AS REQUESTED ON PREVIOUS REVIEW.
 PLEASE SEE FS 471.023, FAC 61G15-23.002 AS THE TITLE
 BLOCKS WHICH ARE NOW ON PLANS ARE MISSING THE REQUIRED
 LICENSING PER FLORIDA STATUTES NOTED.
 PLEASE SECTION AS THE COMPANY IS REQUIRED TO HAVE A
 CERTIFICATE OF AUTHORIZATION NUMBER.
  
 3) NOTE: AS REQUESTED ON PREVIOUS REVIEW. PLEASE SUBMIT
 THE MANUFACTURES SPECS/CUT SHEETS FOR THE LED
 SYSTEM/DRIVER.
 MUST MEET A NRTL.
 110.3
 FBC 106.1.1 FOR ADDITIONAL INFORMATION.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-17 Cont ID  
Sent By dpalmer Date 2008-09-17 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2008-09-17 Time 14:22 Sent To B
Notes
2008-09-17 14:23:05 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK IS SUBSTANTIALLY UNDER STATED. THE VALUE SHALL BE
 INCLUDE ALL LABOR , MATERIALS, DESIGN COST ETC EVEN IF
 ANY OF IT IS OWNER SUPPLIED.
 FBC 108.3
  
 2) NOTE: PLEASE SEE THAT THE PLANS DO NOT SHOW ENOUGH
 INFORMATION FOR ELECTRICAL CODE COMPLIANCE. PLEASE SEE
 NEC 600.5,600.6,600.7, 600.8 ETC. 240.4,310.16, 250
 ETC.
 PLEASE SUBMIT THE SPECS/MANUFACTURES CUT SHEET ON THE
 LED EQUIPMENT/DRIVER.
 110.3.
 FBC 106.1.1,106.1.2, FOR CLARITY, ADDITIONAL
 INFORMATION.
  
 3) NOTE: PLEASE SEE BOTH SETS OF PLANS SUBMITTED ARE IN
 FACT SEALED OVER PHOTO-COPIED SIGNATURES. PLACING A
 RAISED SEAL OVER A PHOTO-COPIED SIGNATURE AND DATE IS A
 VIOLATION OF FLORIDA STATUTES 471.025 AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002. THIS IS NOT A LOCAL
 CODE, ORDINANCE OR REQUIREMENT THIS IS A STATUTORY
 REQUIREMENT. AT THIS TIME PLANS WILL BE RETAINED FOR
 POSSIBLE REVIEW BY THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS LEGAL COUNSEL.
  
 4) NOTE: PLEASE SEE FAC 61G15-23.002 AS PLANS ARE
 MISSING THE REQUIRED TITLE BLOCKS WITH ALL INFORMATION
 AS NOTED IN SECTION OF THE ADMINISTRATIVE CODE.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-10-21 Cont ID  
Sent By adarroug Date 2008-10-21 Time 11:11 Rev Time 0.00
Received By adarroug Date 2008-10-21 Time 11:11 Sent To Z
Notes
2008-10-21 11:11:30TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-08 Cont ID  
Sent By adarroug Date 2008-10-08 Time 09:09 Rev Time 0.00
Received By adarroug Date 2008-10-08 Time 09:09 Sent To E
Notes
2008-10-08 09:10:25TO "DPALMER' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-25 Cont ID  
Sent By adarroug Date 2008-09-25 Time 11:41 Rev Time 0.00
Received By adarroug Date 2008-09-25 Time 11:41 Sent To Z
Notes
2008-09-25 11:42:03TO"Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 08:58 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 08:58 Sent To E
Notes
2008-09-10 08:58:48TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-09-18 Time   Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 08:16 Sent To  
Notes
2008-08-28 08:17:22TO "ZONING" BOX.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-10-24 Cont ID  
Sent By kdfreema Date 2008-10-24 Time 14:59 Rev Time 0.00
Received By kdfreema Date 2008-10-24 Time 14:59 Sent To  
Notes
2008-10-24 15:00:28REVISION TO ADD FACE CHANGE ON FREE STANDING SIGN ALONG
 OKEECHOBEE.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-03 Cont ID  
Sent By kdfreema Date 2008-10-03 Time 13:54 Rev Time 0.00
Received By kdfreema Date 2008-10-03 Time 13:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2008-09-09 Cont ID  
Sent By mcruz Date 2008-09-09 Time 10:57 Rev Time 0.00
Received By mcruz Date 2008-09-09 Time 10:57 Sent To I
Notes
***NONE***