| 2008-08-28 11:51:39 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | *NOTE: THE SUBMITTED ISOMETRIC IS NOT INDICATING |
| | CORRESPONING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| | PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS |
| | ON THE ISOMETRIC WITH NO CORRESPONDING LENGTHS. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| | *NOTE: THE SUBMITTED ISOMETRIC IS NOT INDICATING THE |
| | ABOVE GROUND PIPING MATERIAL BY THE METER, GRILL, |
| | GENERATOR, AND POOL HEATER. ALSO THERE IS A 10' OF 3/4" |
| | PIPE GOING TO THE FIRE PLACE THAT DOES NOT CLEARLY |
| | INDICATE THE PIPING MATERIAL. IT LOOKS LIKE PE, HOWEVER |
| | PE PIPING CAN'T BE USED IN THIS LOCATION PER FBC-2004 |
| | FUEL GAS SECTION 403.6 PLASTIC PIPE AND FITTING OUTSIDE |
| | UNDERGROUND ONLY. PLEASE CLARIFY THESE AREAS ON THE |
| | RESUBMITTAL. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | *NOTE: REFERENCE COMMENT #1 AND COMPLY. |
| | |
| | 4. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATORS |
| | (2PSI TO 0.5PSI) TO VERIFY COMPLIANCE WITH STANDARDS |
| | NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC |
| | 402.2. MANUFACTURE SPECIFICATION SHEETS SHALL CLEARLY |
| | INDICATE THE REGULATOR MAKE, MODEL NUMBER, BTU LOAD |
| | CAPACITY, AND A LISTING FROM A RECOGNIZED TESTING |
| | LABORATORY (LISTING EXAMPLES= AGA, CSA, UL). |
| | |
| | 5. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| | |
| | 6. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | (W.P.B. AS AMENDED) SECTION *106.3.4.3. |
| | |
| | 7. PER FS 713.13 (1) THRU (6): A NOTICE OF |
| | COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY |
| | COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE |
| | HWY., BEFORE A PERMIT CAN BE ISSUED. PER FS 713.13 (2): |
| | IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND OF |
| | NO FURTHER EFFECT. |
| | |
| | 8. NOTE: THE SUBMITTEDOMEGA FLEX TRACPIPE TABLE IS |
| | UNACCEPTABLE DUE TO FLORIDA PUBLIC UTILITIES COMPANY |
| | PROVIDES A 12" WC WITH A 0.5 INCH PRESSURE DROP. WE |
| | WILL BE USING FBC-2004 FUEL GAS TABLE 402.4(14) FOR |
| | CSST PIPE. |
| | |
| | 9. PER THE NOTE: GENERATOR PERMIT TO BE PULLED |
| | SEPERATE BY THE ELECTRICIAN. THIS FOR LINES AND CONNECT |
| | ONLY. |
| | *PLEASE KNOW THAT THE GENERATOR NEEDS TO BE INDICATED |
| | AS "FUTURE" AND THAT ALL PIPING TO THE GENERATOR IS AT |
| | CONTRACTORS OWN RISK DUE TO ZONING APPROVAL OF THE |
| | GENERATORS LOCATION. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |