Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-18 Cont ID  
Sent By btrobaug Date 2008-09-18 Time 16:08 Rev Time 0.00
Received By btrobaug Date 2008-09-18 Time 13:08 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-28 Cont ID  
Sent By btrobaug Date 2008-08-28 Time 14:09 Rev Time 0.00
Received By btrobaug Date 2008-08-28 Time 14:07 Sent To FIRE
Notes
2008-08-28 14:09:22 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-19 Cont ID  
Sent By mwennerg Date 2008-09-19 Time 10:27 Rev Time 0.00
Received By mwennerg Date 2008-09-19 Time 10:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-17 Cont ID  
Sent By mwennerg Date 2008-09-17 Time 13:27 Rev Time 0.00
Received By mwennerg Date 2008-09-17 Time 13:27 Sent To  
Notes
2008-09-17 13:32:43***DENIED***
  
 1) PLEASE SEE ELECTRICAL COMMENT #1 REGARDING DESIGN
 PROFESSIONAL RESPONSIBILITIES FOR PLANS.
  
 2) SHEET SE-02 REFERENCES NFPA 101, 2003 SEC.
 7.2.1.6.2. PLEASE ADVISE IF THIS PROJECT COMPLIES WITH
 REFERENCED REQUIREMENTS. INDICATE WHICH REQUIREMENT
 UNDER (1) APPLIES TO THIS PROJECT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-18 Cont ID  
Sent By adarroug Date 2008-09-18 Time 15:37 Rev Time 0.00
Received By adarroug Date 2008-09-18 Time 15:37 Sent To E
Notes
2008-09-18 15:38:08TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-17 Cont ID  
Sent By mwennerg Date 2008-09-17 Time 13:33 Rev Time 0.00
Received By mwennerg Date 2008-08-27 Time 11:11 Sent To  
Notes
2008-08-27 11:11:44TO "ELECT" BOX.