Plan Review Details - Permit 08080570
| Plan Review Stops For Permit 08080570 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-09-18 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-09-18 |
Time |
13:08 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-08-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-08-28 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-08-28 |
Time |
14:07 |
Sent To |
FIRE |
|
| Notes |
| 2008-08-28 14:09:22 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-09-19 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-09-19 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-09-19 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-09-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-09-17 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-09-17 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2008-09-17 13:32:43 | ***DENIED*** | | | | | | 1) PLEASE SEE ELECTRICAL COMMENT #1 REGARDING DESIGN | | | PROFESSIONAL RESPONSIBILITIES FOR PLANS. | | | | | | 2) SHEET SE-02 REFERENCES NFPA 101, 2003 SEC. | | | 7.2.1.6.2. PLEASE ADVISE IF THIS PROJECT COMPLIES WITH | | | REFERENCED REQUIREMENTS. INDICATE WHICH REQUIREMENT | | | UNDER (1) APPLIES TO THIS PROJECT. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-18 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-18 |
Time |
15:37 |
Sent To |
E |
|
| Notes |
| 2008-09-18 15:38:08 | TO "F" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-09-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-09-17 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-08-27 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2008-08-27 11:11:44 | TO "ELECT" BOX. |
|
|
|