Plan Review Details - Permit 08080566
Plan Review Stops For Permit 08080566
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-10 Cont ID  
Sent By rmcdouga Date 2008-09-10 Time 15:11 Rev Time 0.00
Received By rmcdouga Date 2008-09-10 Time 15:11 Sent To Z
Notes
2008-09-10 11:33:472007 FBC W/2007 REVISIONS
 ENCLOSE CARPORT
  
 DENIED BY BUILDING
  
 1) THE VALUE OF THE WORK IS TOO LOW. FOR PERMITTING
 PURPOSES, THE VALUE INCLUDES LABOR, MATERIAL, DESIGN
 FEES, OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A
 CONTRACTOR. PLEASE REVISE VALUE ON APPLICATION AND PAY
 ADDITIONAL PERMIT FEES WHEN PERMIT IS RE-SUBMITTED. FBC
 108.3* CITY AMENDMENTS
  
 2) SUBMIT 2 COPIES OF A SURVEY OR SITE PLAN INDICATING
 THE DISTANCE TO PROPERTY LINES. IF CARPORT WALL IS LESS
 THAN 6 FEET TO THE PROPERTY LINE, SPECIFY THE DISTANCE
 TO ADJACENT STRUCTURES OR SHOW COMPLIANCE WITH FBC
 R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.
  
 3) SPECIFY THE APPLICABLE CODE AND DESIGN DATA ON THE
 PLANS. SEE 2004 FBC W/2007 REVISIONS RESIDENTIAL CODE
 CHAPTER R301 AND ASCE7-02. SPECIFY WIND SPEED (140MPH 3
 SEC GUST), EXPOSURE CATEGORY, WIND IMPORTANCE FACTOR,
 ETC.
  
 4) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1/8
 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 5) SUBMIT 2 COPIES OF THE ENERGY CALCULATION FORM WITH
 THE CORRECT INFORMATION IN THE PROPER LOCATIONS. FBC
 CHAPTER 13-600. MUST BE SIGNED AND DATED BY THE
 PREPARER AND THE OWNER/AGENT.
  
 6) SPECIFY THE CEILING INSULATION ON THE PLANS. THE
 MINIMUM CEILING INSULATION IS R-30 WHEN USING THE
 PRESCRIPTIVE METHOD TO COMPLY WITH THE ENERGY CODE. FBC
 13-600
  
 7) REVISE THE EXTERIOR FRAME WALL INSULATION TO R-19 TO
 COMPLY WITH THE ENERGY CODE. FBC 13-600
  
 8) SPECIFY THE LENGTH OF THE ROOF OVERHANG ON THE PLANS
 IN ORDER TO DETERMINE COMPLIANCE WITH ENERGY CODE. FBC
 13-600
  
 9) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH.
 ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 10) FBC R319.1(5) REQUIRES WOOD SHEATHING AND WALL
 FRAMING ON THE EXTERIOR OF A BUILDING HAVING A
 CLEARANCE OF LESS THAN 6 INCHES FROM THE GROUND TO BE
 PRESSURE TREATED OR DECAY-RESISTANT LUMBER. SHOW
 COMPLIANCE.
  
 11) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
 EXCEPTIONS:
 1. PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS THAN 5
 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2. ACCESS OR VEHICLE RAMPS WHICH RISE TO THE INTERIOR
 FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH RAMPS
 ONLY.
 3. A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO AND
 GARAGE SLABS AND ENTRY AREAS.
 4. IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES, THE
 FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR FINISH
 FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5. MASONRY VENEERS.
  
 12) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 13) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE
 OUTSWING DOOR. DCA RULE 9B-72
  
 14) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE SINGLE
 HUNG WINDOW THAT ARE NOT EXPIRED. DCA RULE 9B-72
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-29 Cont ID  
Sent By btrobaug Date 2008-08-29 Time 10:39 Rev Time 0.00
Received By btrobaug Date 2008-08-29 Time 10:29 Sent To B
Notes
2008-08-29 10:39:31 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.*** A
 NOTE ON THE PLAN REFERENCING THIS REQUIREMENT WILL
 SUFFICE
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-10 Cont ID  
Sent By rmcdouga Date 2008-09-10 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2008-08-27 Time 11:32 Sent To  
Notes
2008-08-27 11:33:58TO "ELECT" RES. SHELF

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-10 Cont ID  
Sent By mcruz Date 2008-09-10 Time 16:00 Rev Time 0.00
Received By mcruz Date 2008-09-10 Time 15:55 Sent To  
Notes
2008-09-10 16:00:26***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY?S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE THE HEIGHT AND SETBACK DIMENSIONS FROM ANY
 EXTERIOR IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES.
 NOTE: PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-72(A)(2) AND (3):
  
 (2) MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 (3) MAXIMUM BUILDING HEIGHT: 30 FEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  