Plan Review Details - Permit 08080547
Plan Review Stops For Permit 08080547
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-04 Cont ID  
Sent By jwitmer Date 2008-11-04 Time 12:05 Rev Time 0.77
Received By jwitmer Date 2008-11-04 Time 12:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-10 Cont ID  
Sent By jwitmer Date 2008-09-10 Time 14:04 Rev Time 0.77
Received By jwitmer Date 2008-09-10 Time 14:04 Sent To  
Notes
2008-09-10 14:07:25BUILDING PLAN REVIEW
 PERMIT: 08080547
 ADD: 901 45TH ST
 CONT: OVERLAND CONSTRUCTION
 TEL: (561)683-3210
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1B) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 1C) PLANS FAIL TO INDICATE DESIGNING TO THE 2004
 EXISTING BUILDING CODE, PLANS DO INDICATE LEVEL II
 ALTERATION.
  
 1D) SHEET A-7 DETAIL# 3, PLEASE PROVIDE HOW THE BENCH
 WILL BE ATTACHED TO THE WALL, INCLUDE BACKING
 INFORMATION. 11-4.23.5/ 11-4.26.3.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-11-24 Cont ID  
Sent By dpalmer Date 2008-11-24 Time 13:34 Rev Time 0.00
Received By dpalmer Date 2008-11-24 Time 13:34 Sent To B
Notes
2008-11-24 13:34:24SENT TO BUILDING FOR NEW A-6 SHEET

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-04 Cont ID  
Sent By dpalmer Date 2008-11-04 Time 13:47 Rev Time 0.00
Received By dpalmer Date 2008-11-04 Time 13:47 Sent To  
Notes
2008-11-04 13:47:29 
  
  
  
 ** DENIED 2ND REVIEW **
  
 1) NOTE: PER PREVIOUS REVIEW NOTES. PLEASE KNOW THE
 MINIMUM LOCATIONS, LEVELS AND HEIGHTS FOR HORNS,
 STROBES, HORN/STROBE PULL STATIONS ARE TO BE SHOWN ON
 PLANS AS A BASE DESIGNER PER FS 633.
 THE PLANS STATE THE SCOPE OF WORK IS UNDER SEPARATE
 PERMIT AND STATES THE CODE SHALL BE MET. MAY NOT QUOTE
 THE CODE IN LIEU OF SPECIFIC DETAIL.
 FBC 11-4.28.1,.2. AND .3.
  
 2) NOTE: PLEASE BE SURE THE ARCHITECTURAL PLANS ARE
 REVISED WITH ELECTRICAL REFLECTED PLANS.
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
 FBC 13-415.1.ABC.1.1, .1.2
  
 3) NOTE: PLEASE SEE THE TIME CURVE COORDINATION STUDY
 SUBMITTED IS NOT SIGNED DATED OR SEALED FOR REVIEW. ALL
 DOCUMENTS MUST HAVE COMPLETED TITLE BLOCKS, SIGNED,
 DATED AND SEALED PER FAC61G15-23.002, FS 471.025
  
 4) NOTE: PLEASE SEE SECTION OF CODE SHOULD HAVE BEEN
 NEC 517 PART II. THIS WAS TYPED PREVIOUSLY AS 11 IN
 ERROR BY REVIEWER. PLEASE ADJUST. IF THIS WERE THE ONLY
 COMMENT THIS COULD HAVE BEEN REDLINED.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-15 Cont ID  
Sent By dpalmer Date 2008-09-15 Time 09:25 Rev Time 0.00
Received By dpalmer Date 2008-09-12 Time 17:07 Sent To  
Notes
2008-09-15 09:26:02 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THAT THE PLANS STATE THE FIRE ALARM
 SYSTEM SHALL COMPLY WITH NFPA-72. HOWEVER BASED ON MANY
 ASPECTS OF THE FLORIDA BUILDING CODE IN CHAPTER 11
 THERE ARE ITEMS WHICH ARE SUBSTANTIALLY MORE
 RESTRICTIVE. PLEASE SEE FBC 11-4.28,.1,.2 AND .3.
 PLEASE BE SURE TO STATE ALL MINIMUM LEVELS FOR ADA
 COMPLIANCE.
  
 2) NOTE: PLEASE INCLUDE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2.ABC.1.1, .1.2.
  
 3) NOTE: PLEASE INCLUDE LIGHTING CONTROLS FOR NEW WORK
 BEING INSTALLED PER 13-415.1.ABC.1.1, .1.2.
  
 4) NOTE: PLEASE SEE THE FOLLOWING CODES NEED TO BE
 REVISED ON PLANS.
 2004 FBC W/2007 REVISIONS.
 1999 NFPA-99
  
 5) NOTE: PLEASE INCLUDE NOTES ON PLANS FOR NEC 517 PART
 11. MAY STATE ONLY THE SECTION.
  
 6) NOTE: PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND
 SO THAT COMPLIANCE WITH FBC CHAPTER 13 AS NOTED ABOVE
 CAN BE VERIFIED.
  
 7) NOTE: PLEASE PROVIDE THE SELECTIVE COORDINATION
 STUDY FOR NEW PANEL BACK TO MAIN.
 240.12, NFPA-99
 PLEASE ALSO PROVIDE SELECTIVE COORDINATION OF GFCI PER
 517.17, 3-3.2.1.5
  
 ** NOTES ON PLANS MENTIONS CONTRACTOR TO PROVIDE
 HOWEVER THIS NEEDS TO BE PART OF THE SUBMITTED PLANS.
  
  
  
  
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH
 INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK
 WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE
 REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-10 Cont ID  
Sent By mwennerg Date 2008-11-10 Time 10:35 Rev Time 0.00
Received By mwennerg Date 2008-11-10 Time 10:35 Sent To  
Notes
2008-11-10 10:36:04STAMPED NEW SHEETS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-09-23 Cont ID  
Sent By mwennerg Date 2008-09-23 Time 12:58 Rev Time 0.00
Received By mwennerg Date 2008-09-23 Time 12:58 Sent To  
Notes
2008-09-23 12:59:29STAMPED A-1, A-2, A-3, AND FS-1.01.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-19 Cont ID  
Sent By adarroug Date 2008-11-19 Time 16:41 Rev Time 0.00
Received By adarroug Date 2008-11-19 Time 16:41 Sent To E
Notes
2008-11-19 16:41:46TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-28 Cont ID  
Sent By adarroug Date 2008-10-28 Time 14:02 Rev Time 0.00
Received By adarroug Date 2008-10-28 Time 14:02 Sent To  
Notes
2008-10-28 14:03:14TO "COMM" BD#17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-23 Cont ID  
Sent By mwennerg Date 2008-09-23 Time 12:59 Rev Time 0.00
Received By mwennerg Date 2008-08-26 Time 15:45 Sent To  
Notes
2008-08-26 15:45:52TO "COMM" BD. #4.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-15 Cont ID  
Sent By rregueir Date 2008-11-15 Time 14:11 Rev Time 0.00
Received By rregueir Date 2008-11-15 Time 14:11 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-09-09 Cont ID  
Sent By rregueir Date 2008-09-09 Time 09:05 Rev Time 0.00
Received By rregueir Date 2008-09-09 Time 08:54 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2008-11-06 Cont ID  
Sent By kstevens Date 2008-11-06 Time 15:31 Rev Time 0.00
Received By kstevens Date 2008-11-06 Time 15:31 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2008-09-02 Cont ID  
Sent By kstevens Date 2008-09-02 Time 15:30 Rev Time 0.00
Received By kstevens Date 2008-09-02 Time 15:32 Sent To  
Notes
2008-11-06 15:33:32DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 REVISIONS
 NFPA 99 1999
  
 1. SHT A-1 CODE INFORMATION TO INCLUDE FBC W/2007
 REVISIONS ADDED TO OTHER REVISIONS INDICATED & NFPA 99
 TO BE 1999 EDITION PER FBC-2004 PLUMBING CHAPTER 13.
  
 2. SHT P1.01 APPLICABLE CODES & STANDARDS. NFPA 99 TO
 BE 1999 EDITION PER FBC-2004 PLUMBING CHAPTER 13 &
 FBC-2004 SHALL INCLUDE 2007 REVISIONS ALSO.
  
 ****INFORMATIONAL****
 ALTHOUGH THE MEDGAS IS REVIEWED UNDER NFPA 99 1999
 EDITION, AHCA (AGENCY FOR HEALTH CARE ADMINISTRATORS)
 WILL BE INSPECTING UNDER NFPA 99 2005 EDITION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-11-06 Cont ID  
Sent By kstevens Date 2008-11-06 Time 15:31 Rev Time 0.00
Received By kstevens Date 2008-11-06 Time 15:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-02 Cont ID  
Sent By kstevens Date 2008-09-02 Time 09:43 Rev Time 0.00
Received By kstevens Date 2008-09-02 Time 09:43 Sent To  
Notes
2008-09-02 09:52:36DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 REVISIONS
 NFPA 99 1999
  
 1. SHT A-1 CODE INFORMATION TO INCLUDE FBC W/2007
 REVISIONS ADDED TO OTHER REVISIONS INDICATED & NFPA 99
 TO BE 1999 EDITION PER FBC-2004 PLUMBING CHAPTER 13.
  
 2. SHT P1.01 APPLICABLE CODES & STANDARDS. NFPA 99 TO
 BE 1999 EDITION PER FBC-2004 PLUMBING CHAPTER 13 &
 FBC-2004 SHALL INCLUDE 2007 REVISIONS ALSO.
  
 ****INFORMATIONAL****
 ALTHOUGH THE MEDGAS IS REVIEWED UNDER NFPA 99 1999
 EDITION, AHCA (AGENCY FOR HEALTH CARE ADMINISTRATORS)
 WILL BE INSPECTING UNDER NFPA 99 2005 EDITION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  