Plan Review Details - Permit 08080538
Plan Review Stops For Permit 08080538
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-09-02 Cont ID  
Sent By mperson Date 2008-09-02 Time 15:41 Rev Time 0.00
Received By mperson Date 2008-09-02 Time 15:41 Sent To I
Notes
2008-09-02 15:44:03 
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By mperson Date 2008-08-27 Time 14:44 Rev Time 0.00
Received By mperson Date 2008-08-27 Time 14:44 Sent To I
Notes
2008-08-27 15:04:34GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE VALUE ON THE PERMIT APPLICATION IS LOW. PLEASE
 KNOW THAT THE COST OF A GAS STOVE AND WATER HEATER IS
 ALOT MORE THAN $100.00. THE VALUE ON THE PERMIT
 APPLICATION MUST INCLUDE THE TOTAL COST OF LABOR AND
 MATERIALS. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF A NATIONAL CONSTRUCTION COST ANALYSIS
 (MARSHALL-SWIFT, MEANS, ECT...) ADJUST THE VALUE AT THE
 PERMIT CLERK'S DESK AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING. PER (W.P.B. AS AMENDED) SECTION
 108.3 BUILDING PERMIT VALUATION.
  
 2. CLEARLY INDICATE THE LOCATION OF THE GAS METER ON
 THE RESUBMITTED GAS RISER DIAGRAMS. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 3. CLEARLY INDICATE THE DELIVERY PRESSURE OF THE
 NATURAL GAS METER ON THE RESUBMITTED GAS RISER DIAGRAMS
 AS BEING EITHER 0.5 PSI, OR 2 PSI. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR FOR THE WATER HEATER. PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 IF WATER HEATER ROOM IS A CONFINED SPACE, OPENINGS
 REQUIRED PER SECTION 304.3.1 0R SECTION 304.3.2 SHALL
 BE INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-02 Cont ID  
Sent By mperson Date 2008-09-02 Time 15:44 Rev Time 0.00
Received By mperson Date 2008-08-29 Time 15:54 Sent To PC
Notes
2008-08-29 15:55:30TO $5000,00 OR LESS PLBG BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 10:26 Rev Time 0.00
Received By mperson Date 2008-08-27 Time 10:26 Sent To PC
Notes
2008-08-27 10:27:59TO GAS (PLUMB UNDER $5,000.)