| 2008-08-27 12:00:06 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. DECLARE THE GOVERNING CODE (FBC-2004 WITH 2007 |
| | REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5 |
| | RETENTION OF CONSTRUCTION DOCUMENTS. |
| | |
| | 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004 |
| | EXISTING BUILDING CHAPTER 3. |
| | |
| | 3. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION |
| | AND OCCUPANCY LOAD ON THE PLANS. |
| | PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR |
| | PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT |
| | TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED |
| | BELOW. |
| | |
| | A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3, |
| | AND A-5 |
| | |
| | B} BUSSINESS (SEE SECTION 304): GROUP B |
| | |
| | C} EDUCATIONAL (SEE SECTION 305): GROUP E |
| | |
| | D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS |
| | F-1 AND F-2 |
| | |
| | E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3, |
| | H-4, AND H-5 |
| | |
| | F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2, |
| | AND I-3 |
| | |
| | G} MERCANTILE (SEE SECTION 309): GROUP M |
| | |
| | H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3 |
| | AS APPLICABLE IN SECTION 101.2, AND R-4 |
| | |
| | I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2 |
| | |
| | J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP |
| | U |
| | |
| | K} DAY CARE (SEE SECTION 313): GROUP D |
| | |
| | NOTE: PLANS APPREAR TO BE A BUSSINESS, GROUP B. PLEASE |
| | KNOW THAT PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM |
| | NUMBER OF REQUIRED PLUMBING FIXTURES FOR A BUSSINESS |
| | ARE AS FOLLOWS. |
| | |
| | WATER CLOSETS= 1 PER 25 FOR THE FIRST 50 AND 1 PER 50 |
| | FOR THE REMAINDER EXCEEDING 50. |
| | |
| | LAVATORIES= 1 PER 40 FOR THE FIRST 50 AND 1 PER 80 FOR |
| | THE REMAINDER EXCEEDING 50. |
| | |
| | DRINKING FOUNTAIN= 1 PER 100. |
| | |
| | THE SUBMITTED PLANS ARE NOT INDICATING A DRINKING |
| | FOUNTAIN. PLEASE KNOW THAT ONE IS REQUIRED AND THAT IT |
| | SHALL BE ACCESSIBLE PER THE FBC-2004 CHAPTER 11, |
| | FLORIDA ACCESSIBILITY CODE SECTIONS. |
| | |
| | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| | (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING |
| | INFORMATION) |
| | |
| | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| | MAXIMUM. |
| | |
| | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" |
| | OF THE FRONT OF FOUNTAIN. |
| | |
| | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| | MOUNTED NEAR FRONT EDGE. |
| | |
| | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| | SPACE. |
| | |
| | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| | |
| | 4. SHEET A-1 FLOOR PLAN TOILET 1, ROOM #103 AND TOILET |
| | 2, ROOM # 104: PLEASE KNOW THAT THE DOOR CAN NOT SWING |
| | INTO THE CLEAR FLOOR SPACE OF THE ACCESSIBLE LAVATORIES |
| | (LAVATORY CLEAR FLOOR SPACE IS 30" X 48" & MAX. 19" |
| | UNDER LAV.). PER FBC-2004, CHAPTER 11, FLORIDA |
| | ACCESSIBILTY CODE SECTION 11-4.22.2. |
| | |
| | 5. SHEET A-3 DETAIL 4: CORRELATE THE DETAIL WITH THE |
| | BREAKROOM REFERENCE NOTES AND DELETE THE CABINET DOORS |
| | AND BASE AT THE ACCESSIBLE SINK LOCATION. CLEARLY |
| | INDICATE AN OPEN FRONT ON THE DETAIL AT THE ACCESSIBLE |
| | SINK LOCATION. PER FBC-2004, CHAPTER 11, FLORDA |
| | ACCESSIBLITY CODE SECTION 11-4.24.5 CLEAR FLOOR SPACE. |
| | NOTE: CLEARLY INDICATE THE CLEAR FLOOR SPACE FOR THE |
| | ACCESSIBLE SINK ON SHEET A-1 FLOOR PLAN. PER SECTION |
| | 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR |
| | SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE |
| | SINK. |
| | |
| | 6. SHEET P-1 SANITARY RISER DIAGRAM AND PLUMBING PLAN |
| | ARE INDICATING A HORIZONTAL DRY VENT FOR THE WATER |
| | CLOSETS. HORIZONTAL DRY VENTS ARE UNACCEPTABLE PER THE |
| | FBC-2004 PLUMBING SECTION 905.3 VENT CONNECTIONS TO |
| | DRAINAGE SYSTEM. |
| | |
| | 7. SHEET P-1 RESTROOMS DETAIL AND FLOOR PLAN: TOILET |
| | 1, ROOM #103 AND TOILET 2, ROOM # 104: PLEASE KNOW THAT |
| | THE DOOR CAN NOT SWING INTO THE CLEAR FLOOR SPACE OF |
| | THE ACCESSIBLE LAVATORIES (LAVATORY CLEAR FLOOR SPACE |
| | IS 30" X 48" & MAX. 19" UNDER LAV.). PER FBC-2004, |
| | CHAPTER 11, FLORIDA ACCESSIBILTY CODE SECTION |
| | 11-4.22.2. |
| | |
| | 8. SHEET P-1 RESTROOMS DETAIL PLAN: PLEASE |
| | CLARIFY/CORRECT THE FOLLOWING PER THE FBC-2004 CHAPTER |
| | 11, FLORIDA ACCESSIBILITY CODE SECTIONS. |
| | |
| | A} CLEARLY INDICATE THE CLEAR FLOOR SPACE FOR THE |
| | WATER CLOSET IN THE DETAIL (60" X 48"). PER SECTION |
| | 11-4.16.2 CLEAR FLOOR SPACE. |
| | |
| | B} CLEARLY INDICATE THAT THE FLUSH CONTROLS FOR THE |
| | WATER CLOSETS SHALL BE MOUNTED ON THE WIDE SIDE OF |
| | FIXTURE MAXIMUM OF 44" HIGH. PER SECTION 11-4.16.5 |
| | FLUSH CONTROLS. |
| | |
| | C} CLEARLY INDICATE THE LAVATORIES CLEAR FLOOR SPACE |
| | IN THE DETAIL (30" X 48" AND SHALL EXTEND A MAXIMUM OF |
| | 19" UNDERNEATH THE LAVATORIES). PER SECTION 11-4.19.3 |
| | CLEAR FLOOR SPACE. |
| | |
| | D} RESTROOM REFERENCE NOTES (C): NOTE C, STATES "THEN |
| | 9" TO WALL", PLEASE CLARIFY THIS AS BEING THE TOE |
| | CLEARANCE AND THAT IT IS 9" MIN UP FROM FINNISH FLOOR |
| | AND 6" MAX FROM WALL. PER SECTION 11-4.19.2 HEIGHT AND |
| | CLEARANCES, FIGURE 31 LAVATORY CLEARANCES DETAIL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |