Plan Review Details - Permit 08080507
Plan Review Stops For Permit 08080507
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-14 Cont ID  
Sent By mjacobs Date 2008-10-14 Time 12:21 Rev Time 0.00
Received By mjacobs Date 2008-10-14 Time 12:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-08 Cont ID  
Sent By mjacobs Date 2008-09-08 Time 14:20 Rev Time 0.00
Received By mjacobs Date 2008-09-08 Time 10:29 Sent To PC
Notes
2008-09-08 14:20:43BUILDING PLAN REVIEW
 PERMIT: 08080507
 ADD: 2161 PBL BLVD
 CONT: RE-ANDERSON CONSTRUCTION INC.
 TEL: (561)776-7389
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 9-8-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5) PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN
 SHOWING ALL CHANGES TO THE EXISTING LAYOUT OF THE
 SPACE. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED. FBC 106.1.1
  
 6) THE DRAWINGS NEED TO INDICATE THE TYPE OF BUILDING
 PER FBC CHAPTER 6 AND THE USE AND OCCUPANCY PER FBC
 CHAPTER 3. STATE THE OCCUPANT LOAD OF THE SPACE PER FBC
 TABLE 1004.1.2. NOW THE SPACE HAS BEEN ALTERED PROVIDE
 A LIFE SAFETY PLAN SHOWING THE MEANS OF EGRESS WHICH
 SHALL INCLUDE EXIT ACCESS, EXITS AND EXIT DISCHARGE:
 ALSO, IF THE BUILDING IS EQUIPPED WITH AND AUTOMATIC
 SPRINKLER SYSTEM SHOW THE LOCATION OF THE SPRINKLER IN
 RELATION TO THE NEW WALLS. THIS CAN BE SHOWN ON THE
 REFLECTED CEILING PLANS. FBC 106.3.5.1.1(5) (6)*
  
 7) SHEET A-3 A PORTION OF THE RECEPTIONIST DESK SHALL
 BE A MAXIMUM HEIGHT OF 36 INCHES AND A MINIMUM WIDTH OF
 36 INCHES; DETAIL #6 ON SHEET A-3 DO NOT MEET THIS
 REQUIREMENT. NOTE: THIS SPACE SHALL BE PROVIDED TO THE
 CUSTOMERS COMING IN FOR SERVICE. SHOW COMPLIANCE.
  
 8) SHEET A-2 IS MISSING THE DETAIL INFORMATION FOR WALL
 TYPES [A] AND [E]. THIS SHEET HAS TWO DETAIL WALLS
 SHOWING AS A TYPE [B]. THE WALL LEGEND ON SHEET A-2
 SHOWS THE NEW WALL TYPES A/B/C AND E CLARIFY.
 ADDITIONAL INFORMATION IS REQUIRED SHOWING THE CORRECT
 TYPES OF WALLS. 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-22 Cont ID  
Sent By btrobaug Date 2008-10-22 Time 11:33 Rev Time 0.00
Received By btrobaug Date 2008-10-22 Time 10:31 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-02 Cont ID  
Sent By btrobaug Date 2008-09-02 Time 15:55 Rev Time 0.00
Received By btrobaug Date 2008-09-02 Time 14:15 Sent To  
Notes
2008-09-02 14:43:45 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} ON SHEET E-1 THERE ARE TWO PANELS LOCATED ON THE
 PLAN BUT ONLY A SCHEDULE FOR PANEL "B". PANEL "B" IS
 RATED AT 225 AMPS MLO WITH #2/0 FEEDERS, INDICATE THE
 OCP FOR THE FEEDERS 215.5 NEC.
  
 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 NEW DEVICES AND EQUIPMENT (WATER HEATER) 106.3.5 FBC.
  
 3} PER 700.12(F)(4) "HE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES." INDICATE COMPLIANCE ON
 THE PLAN SHEET E-2
  
 4} PER 13-415.2.ABC.1.1. PAGE #2 OF THE ENERGY GAUGE
 INPUT DATA REPORT, DOES NOT INDICATE THE CORRECT NUMBER
 OF FIXTURES AS SHOWN ON THE PLAN, ALL THAT IS REQUIRED
 FOR THE ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE
 REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE
 CALCULATION PROCEDURES, GENERAL. THAT REQUIREMENT IS
 COMPLIANT ON SHEET E-2, THEREFORE FORM 400A WILL NOT BE
 REVIEWED FOR THE ELECTRICAL COMPLIANCE OF CHAPTER 13
 FBC.
  
 PER 105.1 FBC AN ELECTRIC PERMIT IS REQUIRED FOR
 REMOVING AND TO SAFE OFF ALL CIRCUITS THAT MUST BE
 REMOVED FOR DEMOLITION.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD
 SHEETS TO EXPEDITE AND SUBMIT WRITTEN RESPONSE TO THE
 COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-21 Cont ID  
Sent By mawillia Date 2008-10-21 Time 11:07 Rev Time 0.00
Received By mawillia Date 2008-10-21 Time 10:54 Sent To  
Notes
2008-10-21 11:07:00*****APPROVED*****
  
  
 PLAN SHEETS A-1 AND LS-1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-04 Cont ID  
Sent By mwennerg Date 2008-09-04 Time 11:27 Rev Time 0.00
Received By mwennerg Date 2008-09-04 Time 11:27 Sent To  
Notes
2008-09-04 11:33:07***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003. PLEASE ADD TO
 PLANS.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241. PLEASE ADD TO PLANS.
  
 3) SITE SHALL BE KEPT CLEAN FROM EXCESSIVE DEBRIS BUILD
 UP DAILY OR MORE FREQUENT AS NECESSARY.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-07 Cont ID  
Sent By adarroug Date 2009-01-07 Time 13:37 Rev Time 0.00
Received By adarroug Date 2009-01-07 Time 13:37 Sent To FIRE
Notes
2009-01-07 13:38:02TO "F"BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-07 Cont ID  
Sent By shill Date 2008-10-07 Time 09:14 Rev Time 0.00
Received By shill Date 2008-10-07 Time 09:14 Sent To  
Notes
2008-10-07 09:25:34TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-09-08 Time   Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 08:04 Sent To  
Notes
2008-08-26 09:16:29TO "BOB" BD #13.
2008-08-26 08:04:43WAITING FOR "BOB" BD.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-10-07 Cont ID  
Sent By tgordon Date 2008-10-07 Time 15:30 Rev Time 0.45
Received By tgordon Date 2008-10-07 Time 15:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-03 Cont ID  
Sent By tgordon Date 2008-09-03 Time 10:59 Rev Time 1.30
Received By tgordon Date 2008-09-03 Time 10:59 Sent To  
Notes
2008-09-03 11:45:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MECHANICAL CONTRACTOR NEEDS TO APPLY FOR THE
 MECHANICAL PERMIT BEFORE PASSING PLAN REVIEW TO COMPLY
 WITH, FAC 61G4-12.016 EXEMPTION; PRACTICE OF
 ENGINEERING.
 A CONTRACTOR LICENSED UNDER CHAPTER 489, PART I, F.S.,
 IS EXEMPTED FROM LICENSURE AS AN ENGINEER PURSUANT TO
 THE TERMS OF SECTION 471.003(2)(I), F.S., "ONLY WHEN HE
 INSTALLS THE SYSTEM HE DESIGNS". VIOLATION OF THIS RULE
 WILL BE CONSIDERED A VIOLATION OF SECTION
 489.129(1)(M), F.S.
  
 2) PLAN M-1 OUTSIDE AIR SCHEDULE DOES NOT COMPLY WITH
 ASHRAE 62.1-2004 TABLE 6-1, OR WITH 2004 FBC/M TABLE
 403.3. PLEASE STATE WHERE THE CALCULATIONS ARE COMING
 FROM AND CORRECT. SEE 2004 FBC/M 403.3 AND 403.4.
  
 3) SHOW ON MECHANICAL PLAN M-1 THE OUTSIDE AIR DUCTS,
 PER 2004 FBC/M 401.
  
 4) PLEASE SHOW EXISTING A/C SYSTEM #1 INFORMATION IN
 THE EQUIPMENT SCHEDULE (MAKE, MODEL NUMBERS, CFM'S,
 TOTAL BTU'S AND HEATER SIZE) SO A COMPLETE REVIEW CAN
 BE DONE (LIST AS EXISTING), PER 2004 FBC
 13-407.1.ABC.1.1.
  
 5) THE MECHANICAL PLAN SHOWS A SUPPLY AIR GRILL AS S-3
 AND A RETURN AIR GRILL AS R-4, THE AIR DISTRIBUTION
 SCHEDULE ON THE PLAN DOES NOT LISTS THEM. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-15 Cont ID  
Sent By mperson Date 2008-10-15 Time 13:51 Rev Time 0.30
Received By mperson Date 2008-10-15 Time 13:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By mperson Date 2008-08-27 Time 10:17 Rev Time 1.15
Received By mperson Date 2008-08-27 Time 10:17 Sent To  
Notes
2008-08-27 12:00:06PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. DECLARE THE GOVERNING CODE (FBC-2004 WITH 2007
 REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 3. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 AND OCCUPANCY LOAD ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED
 BELOW.
  
 A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3,
 AND A-5
  
 B} BUSSINESS (SEE SECTION 304): GROUP B
  
 C} EDUCATIONAL (SEE SECTION 305): GROUP E
  
 D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS
 F-1 AND F-2
  
 E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3,
 H-4, AND H-5
  
 F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2,
 AND I-3
  
 G} MERCANTILE (SEE SECTION 309): GROUP M
  
 H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3
 AS APPLICABLE IN SECTION 101.2, AND R-4
  
 I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2
  
 J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP
 U
  
 K} DAY CARE (SEE SECTION 313): GROUP D
  
 NOTE: PLANS APPREAR TO BE A BUSSINESS, GROUP B. PLEASE
 KNOW THAT PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES FOR A BUSSINESS
 ARE AS FOLLOWS.
  
 WATER CLOSETS= 1 PER 25 FOR THE FIRST 50 AND 1 PER 50
 FOR THE REMAINDER EXCEEDING 50.
  
 LAVATORIES= 1 PER 40 FOR THE FIRST 50 AND 1 PER 80 FOR
 THE REMAINDER EXCEEDING 50.
  
 DRINKING FOUNTAIN= 1 PER 100.
  
 THE SUBMITTED PLANS ARE NOT INDICATING A DRINKING
 FOUNTAIN. PLEASE KNOW THAT ONE IS REQUIRED AND THAT IT
 SHALL BE ACCESSIBLE PER THE FBC-2004 CHAPTER 11,
 FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
  
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
  
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
  
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
  
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
  
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 4. SHEET A-1 FLOOR PLAN TOILET 1, ROOM #103 AND TOILET
 2, ROOM # 104: PLEASE KNOW THAT THE DOOR CAN NOT SWING
 INTO THE CLEAR FLOOR SPACE OF THE ACCESSIBLE LAVATORIES
 (LAVATORY CLEAR FLOOR SPACE IS 30" X 48" & MAX. 19"
 UNDER LAV.). PER FBC-2004, CHAPTER 11, FLORIDA
 ACCESSIBILTY CODE SECTION 11-4.22.2.
  
 5. SHEET A-3 DETAIL 4: CORRELATE THE DETAIL WITH THE
 BREAKROOM REFERENCE NOTES AND DELETE THE CABINET DOORS
 AND BASE AT THE ACCESSIBLE SINK LOCATION. CLEARLY
 INDICATE AN OPEN FRONT ON THE DETAIL AT THE ACCESSIBLE
 SINK LOCATION. PER FBC-2004, CHAPTER 11, FLORDA
 ACCESSIBLITY CODE SECTION 11-4.24.5 CLEAR FLOOR SPACE.
 NOTE: CLEARLY INDICATE THE CLEAR FLOOR SPACE FOR THE
 ACCESSIBLE SINK ON SHEET A-1 FLOOR PLAN. PER SECTION
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
  
 6. SHEET P-1 SANITARY RISER DIAGRAM AND PLUMBING PLAN
 ARE INDICATING A HORIZONTAL DRY VENT FOR THE WATER
 CLOSETS. HORIZONTAL DRY VENTS ARE UNACCEPTABLE PER THE
 FBC-2004 PLUMBING SECTION 905.3 VENT CONNECTIONS TO
 DRAINAGE SYSTEM.
  
 7. SHEET P-1 RESTROOMS DETAIL AND FLOOR PLAN: TOILET
 1, ROOM #103 AND TOILET 2, ROOM # 104: PLEASE KNOW THAT
 THE DOOR CAN NOT SWING INTO THE CLEAR FLOOR SPACE OF
 THE ACCESSIBLE LAVATORIES (LAVATORY CLEAR FLOOR SPACE
 IS 30" X 48" & MAX. 19" UNDER LAV.). PER FBC-2004,
 CHAPTER 11, FLORIDA ACCESSIBILTY CODE SECTION
 11-4.22.2.
  
 8. SHEET P-1 RESTROOMS DETAIL PLAN: PLEASE
 CLARIFY/CORRECT THE FOLLOWING PER THE FBC-2004 CHAPTER
 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 A} CLEARLY INDICATE THE CLEAR FLOOR SPACE FOR THE
 WATER CLOSET IN THE DETAIL (60" X 48"). PER SECTION
 11-4.16.2 CLEAR FLOOR SPACE.
  
 B} CLEARLY INDICATE THAT THE FLUSH CONTROLS FOR THE
 WATER CLOSETS SHALL BE MOUNTED ON THE WIDE SIDE OF
 FIXTURE MAXIMUM OF 44" HIGH. PER SECTION 11-4.16.5
 FLUSH CONTROLS.
  
 C} CLEARLY INDICATE THE LAVATORIES CLEAR FLOOR SPACE
 IN THE DETAIL (30" X 48" AND SHALL EXTEND A MAXIMUM OF
 19" UNDERNEATH THE LAVATORIES). PER SECTION 11-4.19.3
 CLEAR FLOOR SPACE.
  
 D} RESTROOM REFERENCE NOTES (C): NOTE C, STATES "THEN
 9" TO WALL", PLEASE CLARIFY THIS AS BEING THE TOE
 CLEARANCE AND THAT IT IS 9" MIN UP FROM FINNISH FLOOR
 AND 6" MAX FROM WALL. PER SECTION 11-4.19.2 HEIGHT AND
 CLEARANCES, FIGURE 31 LAVATORY CLEARANCES DETAIL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved