Plan Review Details - Permit 08080493
Plan Review Stops For Permit 08080493
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-03 Cont ID  
Sent By jwitmer Date 2008-09-03 Time 11:15 Rev Time 2.22
Received By jwitmer Date 2008-09-02 Time 16:55 Sent To  
Notes
2008-09-03 10:56:15BUILDING PLAN REVIEW
 PERMIT: 08080493
 ADD: 1400 ALLENDALE RD
 CONT:IMPERIAL BUILDERS, INC
 TEL: (561)305-7388
 SEPTEMBER 03,2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 THE SPRAY BOOTH BROCHURE SUBMITTED IS ILLEGABLE PLEASE
 PROVIDE 2 COPIES THAT ARE CLEAR AND LEGIBLE.
 1B): PLEASE SUBMIT (2) OF ALL PLANS, REPORTS, REVISIONS
 , PRODUCT APPROVALS AND OR SUBMITTALS FOR REVIEW FOR
 PERMIT. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) : PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS AND 2004 EXISTING
 BUILDING CODE.
 2004 EXISTING BUILDING CODE SECTION 301.5 A DESIGN
 PROFESSIONAL MUST ELECT A LEVEL OF ALTERATION PURSUANT
 TO SECTION 303,304 & 305. PLANS FAIL TO INDICATE TO
 WHAT DESIGN CRITERIA THESE PLANS WERE TO BE DESIGNED
 TOO.
  
 2) PLANS FAIL TO INDICATE WIND ZONE INFORMATION:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE
 REGISTERED DESIGN PROFESSIONAL.
  
 3) THERE IS A DIFFERENCE BETWEEN TERMINOLOGY IN A SPRAY
 BOOTH AND SPRAY ROOM. THE 2004 FBC- BUILDING CODE
 COMMENTARY LIST THE PRIMARY DIFFERENCE BETWEEN A SPRAY
 ROOM AND A SPRAY BOOTH IS THAT SPRAY BOOTHS ARE
 PARTIALLY OPEN. WHEREAS A SPRAY ROOM IS TO BE ENCLOSED
 WITH FIRE BARRIER ASSEMBLIES HAVING A FIRE -RESISTANCE
 RATING OF AT LEAST 1-HR,
  
 416.2 SPRAY ROOMS.
 SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS
 AND HORIZONTAL ASSEMBLIES OR BOTH WITH NOT LESS THAN A
 1-HOUR FIRE-RESISTANCE RATING. FLOORS SHALL BE
 WATERPROOFED AND DRAINED IN AN APPROVED MANNER.
  
 416.2.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH
 AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE
 OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING, AND SHALL
 BE SO DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM.
 ALUMINUM SHALL NOT BE USED.
  
 416.3 SPRAYING SPACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR
 VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL . WHERE SUCH SPACES
 ARE NOT SEPARATELY ENCLOSED, NONCOMBUSTIBLE SPRAY
 CURTAINS SHALL BE PROVIDED TO RESTRICT THE SPREAD OF
 FLAMMABLE VAPORS.
  
 416.3.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE
 SMOOTH AND CONTINUOUS WITHOUT EDGES, AND SHALL BE SO
 CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR
 FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE
 WASHING AND CLEANING, AND SHALL BE SO DESIGNED TO
 CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM
 SHALL NOT BE USED.
  
 416.4 FIRE PROTECTION.
 AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE
 PROVIDED IN ALL SPRAY, DIP AND IMMERSING SPACES AND
 STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE
 WITH CHAPTER 9 .
  
 4) 903.2.13IN ADDITION TO THE REQUIREMENTS OF SECTION
 903.2 , THE PROVISIONS INDICATED IN TABLE 903.2.13 ALSO
 REQUIRE THE INSTALLATION OF A SUPPRESSION SYSTEM FOR
 CERTAIN BUILDINGS AND AREAS.
 903.2.13 TABLE 903.2.13 FLAMMABLE FINISHES.
  
 5) PLANS & BROCHURE DO NOT INDICATE IF THIS STRUCTURE
 WILL ALSO BE USED AS A DRYING ROOM NEEDING TO MEET THE
 REQUIREMENTS OF 417. PLEASE PROVIDE ADDITIONAL
 INFORMATION. 106.1.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-08 Cont ID  
Sent By dpalmer Date 2008-09-08 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2008-09-08 Time 16:24 Sent To  
Notes
2008-09-08 16:25:43 
  
  
  
  
 ** DENIED REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE FLORIDA STATUTES 471.025 AND
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002. THE PLANS ARE
 SEALED WITH A RAISED SEAL HOWEVER ALL SHEETS IN BOTH
 SETS DO NOT CONTAIN AN ORIGINAL SIGNATURE.
 IT IS VIOLATION OF BOTH OF THE SECTIONS OF FLORIDA LAW
 AS NOTED ABOVE TO PLACE A RAISED SEAL OVER A
 PHOTO-COPIED SIGNATURE. SETS OF PLANS WILL BE RETAINED
 FOR POSSIBLE REVIEW BY THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE ON
 PLANS. SOME OF THE CODES AS STATED ON PLANS ARE NOT
 ADOPTED BY THE STATE OF FLORIDA.
 SOME SHOWN ON PLANS ARE NOTING THE UNIFORM BUILDING
 CODE ETC.
  
 THESE SHOULD BE:
 2004 FBC W/ 2007 REVISIONS
 2003 NFPA-101
  
  
 3) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS WITH
 MORE DETAILS ON WHERE POWER IS COMING FROM, FEEDS, OVER
 CURRENT PROTECTION LOAD CALCULATIONS.
 240.4, 310.16, 215.3, 215.5, 408.4 ETC
 FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-11 Cont ID  
Sent By mwennerg Date 2008-09-11 Time 11:31 Rev Time 0.00
Received By mwennerg Date 2008-09-11 Time 11:31 Sent To  
Notes
2008-09-11 11:42:57***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) SPRAY BOOTH AND ASSOCIATED EQUIPMENT TO COMPY WITH
 NFPA 33.
  
 3) SPRAY BOOTH AND APPLICABLE EQUIPMENT THAT CONVEY
 FLAMMABLE OR COMBUSTIBLE LIQUID SHALL BE BONDED AND
 GROUNDED. 33.6.7
  
 4) IN ADDITION TO OTHER DISTANCE REQUIREMENTS, SPRAY
 BOOTH SHALL BE SEPARATED FROM OTHER OPERATIONS BY A
 DISTANCE OF NOT LESS THAN THREE (3) FEET OR BY
 PARTITION, WALL OR FLOOR/CEILING ASSEMBLY WITH NOT LESS
 THAN ONE (1) HOUR FIRE RATING. 33.5.3
  
 5) PLANS INDICATE THAT THE SPRAY BOOTH WILL BE
 PROTECTED BY A DRY CHEMICAL SYSTEM, NFPA-17. PLEASE
 PROVIDE MORE INFORMATION ILLUSTRATING SYSTEM LAYOUT
 THAT PROTECTS THE BOOTH, EXHAUST PLENUM AND EXHAUST
 DUCTWORK. ADDITIONALLY, PROVIDE MANUFACTURER
 SPECIFICATION SHEETS.
  
 6) SPRAY BOOTH SHALL BE CONNECTED TO THE BUILDING FIRE
 ALARM SYSTEM IF APPLICABLE. IF A FIRE ALARM SYSTEM IS
 NOT PROVIDED, A LOCAL ALARM FOR OCCUPANT NOTIFICATION
 IS STILL REQUIRED IN THE VICINITY OF SPRAYING
 OPERATION.
  
 7) SHOW THE LOCATION OF AUTOMATIC SHUT DOWN. 33.9.2.1
 (4)
  
  
 ALTHOUGH NOT A REQUIREMENT, A RESPONSE LETTER
 INDICATING HOW AND WHERE ON THE PLANS EACH COMMENT WAS
 ADDRESSED WOULD HELP EXPEDITE THE PLAN REVIEW PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-11 Cont ID  
Sent By jwitmer Date 2008-09-11 Time 11:49 Rev Time  
Received By mwennerg Date 2008-08-25 Time 12:07 Sent To  
Notes
2008-08-25 12:08:21TO "COMM" BD #8.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-04 Cont ID  
Sent By rregueir Date 2008-09-04 Time 16:36 Rev Time 0.00
Received By rregueir Date 2008-09-04 Time 13:05 Sent To  
Notes
2008-09-04 16:36:10REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE EXHAUST FAN ON THE ROOF APPEARS TO BE WITHIN 10
 FEET OF THE ROOF EDGE. GUARDS SHALL BE PROVIDED WHERE
 FANS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET OF A ROOF EDGE IN ACCORDANCE
 WITH FBCM 304.10. THE GUARD SHALL EXTEND NOT LESS THAN
 30 INCHES BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT,
 FAN OR COMPONENT AND THE TOP OF THE GUARD SHALL BE
 LOCATED NOT LESS THAN 42 INCHES ABOVE THE ELEVATED
 SURFACE ADJACENT TO THE GUARD. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 21-INCH-DIAMETER SPHERE AND SHALL COMPLY WITH THE
 LOADING REQUIREMENTS FOR GUARDS SPECIFIED IN THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2. PAGE A1 SHOWS THE EXHAUST TERMINATION POINT TO BE
 LESS THAN 5 FEET FROM THE PROPERTY LINE. THE
 TERMINATION POINT FOR EXHAUST DUCTS DISCHARGING TO THE
 ATMOSPHERE CONVEYING FLAMMABLE VAPORS, FUMES OR DUSTS
 SHALL BE AT A MINIMUM: 30 FEET FROM THE PROPERTY LINE;
 10 FEET FROM OPENINGS INTO THE BUILDING; 6 FEET FROM
 EXTERIOR WALLS AND ROOFS; 30 FEET FROM COMBUSTIBLE
 WALLS AND OPENINGS INTO THE BUILDING WHICH ARE IN THE
 DIRECTION OF THE EXHAUST DISCHARGE IN ACCORDANCE WITH
 FBCM 502.7.3.6.
  
 3. NO SOURCE OR LOCATION OF MAKEUP AIR HAS BEEN
 IDENTIFIED ON THE PLANS. MAKEUP AIR SHALL BE PROVIDED
 AT A RATE APPROXIMATELY EQUAL TO THE RATE THAT AIR IS
 EXHAUSTED BY THE HAZARDOUS EXHAUST SYSTEM. MAKEUP-AIR
 INTAKES SHALL BE LOCATED SO AS TO AVOID RECIRCULATION
 OF CONTAMINATED AIR IN ACCORDANCE WITH FBCM 510.5.5.
  
 4. PLEASE PROVIDE INFORMATION ON THE CROSS SECTIONAL
 INSIDE AREA OF THE BOOTH, PARTICULARLY IN THE DIRECTION
 OF AIRFLOW. VENTILATION SYSTEMS SHALL BE DESIGNED,
 INSTALLED AND MAINTAINED SUCH THAT THE AVERAGE AIR
 VELOCITY OVER THE OPEN FACE OF THE BOOTH, OR BOOTH
 CROSS SECTION IN THE DIRECTION OF AIRFLOW DURING
 SPRAYING OPERATIONS, IS NOT LESS THAN 100 FEET PER
 MINUTE IN ACCORDANCE WITH FBCM 502.7.3.3. IT CAN NOT BE
 DETERMINED AT THIS TIME IF THE PROPOSED RATE OF 7800
 CFM WILL PRODUCE THE VELOCITY AS REQUIRED BY THIS
 SECTION.
  
 5. PROVIDE WIND LOAD DATA SHOWING THE PROPOSED ROOFTOP
 SUPPORT SYSTEM IS SUFFICIENT TO RESIST WIND PRESSURES.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM 301.13.
  
 6. SEVERAL SECTIONS OF THE SUBMITTAL PACKAGE ARE OF
 POOR QUALITY AND ILLEGIBLE. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE IN ACCORDANCE WITH FBCB 106.1.1. PLEASE
 RESUBMIT DOCUMENTS WHICH ARE CLEAR AND LEGIBLE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2008-09-03 Cont ID  
Sent By bpowell Date 2008-09-03 Time 17:01 Rev Time 0.00
Received By bpowell Date 2008-09-03 Time 17:01 Sent To  
Notes
***NONE***