Plan Review Details - Permit 08080402
Plan Review Stops For Permit 08080402
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-05 Cont ID  
Sent By jwitmer Date 2009-04-05 Time 19:16 Rev Time 0.77
Received By jwitmer Date 2009-04-05 Time 19:16 Sent To  
Notes
2009-04-05 19:20:11BUILDING PLAN REVIEW
 PERMIT: 08080402
 ADD: 831 VILLAGE BLVD.
 CONT: OAK CONSTRUCTION
 TEL: (954)583-9625
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 APRIL 05/09
  
 BUILDING PROVISO:
  
 1) SHEET S-2 ROOFTOP HVAC EQUIPMENT SEE NOTE 6 NEW HVAC
 TO MEET THE 2004 FBC WINDLOADS OF 140MPH/ 3 SECOND
 GUST, TO PROVIDE ENGINEERED CALCULATIONS.
  
 2) SHEET D1, NOTE 137 REMOVAL OF EXISTING GENERAL SEE
 ELECTRICAL SHEETS FOR ADDITIONAL INFO, E SHEETS
 INDICATE THE INSTALATION OF A NEW GENERATOR.
 PROVIDE ANCHORING DETAIL OF THE NEW GENERATOR TO THE
 EXISTING SLAB. PROVIDE WIND DESIGN INFORMATION ALSO.
 SEE FIGURE 1609 AND SECTION 1609.1.3 ANCHORAGE AGAINST
 OVERTURNING, UPLIFT AND SLIPPAGE BEFORE CALLING IN
 INSPECTIONS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-02-05 Cont ID  
Sent By jwitmer Date 2009-02-05 Time 15:13 Rev Time 1.55
Received By jwitmer Date 2009-02-05 Time 15:13 Sent To  
Notes
2009-02-05 15:51:43BUILDING PLAN REVIEW
 PERMIT: 08080402
 ADD: 831 VILLAGE BLVD .
 CONT: OAK CONSTRUCTION
 TEL: (954)583-9625
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 FEB. 05/2009
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) PBS & J NO CERTIFICATE OF AUTHORIZATION WAS FOUND
 FOR AN ENGINEERS OFFICE ON THE PLANS.THE PLANS HAVE A
 CERTIFICATE OF AUTHORIZATION FOR A SURVEYORS BUSINESS
 LOCATED AT THE SAME ADDRESS. THERE IS CURRENTLY A
 CERTIFICATE OF AUTHORIZATION FOR PBS J CONSTRUCTION
 SERVICES, INC AT THE SAME OFFICE BUT NOT AS PBS & J,
 INC. 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE
 TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) COMPLIED.
  
 4) (A) COMPLIED.
  
 4)(B) 2ND REQUEST, SHEET S-2 GENERAL NOTES DOES HAVE
 WIND INFORMATION FOR THE HIGH WIND VELOCITY ZONES WHICH
 ARE DADE AND BROWARD COUNTIES. THE CITY OF WEST PALM
 BEACH IS NOT LOCATED WITHIN THIS ZONE. THE CITY IS
 LOCATED IN A WIND BORN DEBRIS REGION WITH A WIND ZONE
 OF 140 MPH, 3 SECOND GUST. SEE FIGURE 1609. PLEASE
 CORRECT PLANS.
  
 5-6) COMPLIED.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-02 Cont ID  
Sent By jwitmer Date 2008-09-02 Time 11:34 Rev Time 4.44
Received By jwitmer Date 2008-09-02 Time 11:34 Sent To  
Notes
2008-09-02 13:18:33BUILDING PLAN REVIEW
 PERMIT: 08080402
 ADD: 831 VILLAGE BLVD .
 CONT: OAK CONSTRUCTION
 TEL: (954)583-9625
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SEPTEMBER 02, 2008
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) PBS & J NO CERTIFICATE OF AUTHORIZATION WAS FOUND
 FOR A ARCHITECTS OFFICE, NO CERTIFICATE OF
 AUTHORIZATION WAS FOUND FOR PBS & J (DBA) FOR AN
 ENGINEERS OFFICE. THERE IS CURRENTLY A CERTIFICATE OF
 AUTHORIZATION FOR POST, BUCKLEY, SCHUH & JEERNIGAN,
 INC.
 481.219 F.S. CERTIFICATE OF AUTHORIZATION. (ARCHITECTS)
 THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH
 SHEET.
 THIS MAY BE ADDED BY HAND.
 471.023 F.S. CERTIFICATE OF AUTHORIZATION. (ENGINEER)
 THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) SHEET A-1 INDICATES THE REUSE OF A BOSTON BEAM, BUT
 NO INFORMATION AS TO THE WEIGHT OF THIS STRUCTURE OR
 HOW IT WILL BE ATTACHED TO THE BAR JOIST, AND IF THE
 ADDITIONAL WEIGHT WILL EFFECT THE BAR JOIST SYSTEM.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 4) (A)SHEET S-2 INDICATES THE WIND DESIGN TO THE 2005
 ASCE 7-05, THE 2004 FBC RECOGNIZES THE ASCE 7-02. 2004
 FBC CHAPTER 35 REFERENECED STANDARDS RECOGNIZES ASCE
 7-02 . ALSO 1603.1.4 WIND DESIGN DATA.
  
 4)(B) SHEET S-2 GENERAL NOTES DOES HAVE WIND
 INFORMATION FOR THE HIGH WIND VELOCITY ZONES WHICH ARE
 DADE AND BROWARD COUNTIES. THE CITY OF WEST PALM BEACH
 IS NOT LOCATED WITHIN THIS ZONE.
 THE CITY IS LOCATED IN A WIND BORN DEBRIS REGION WITH A
 WIND ZONE OF 140 MPH, 3 SECOND GUST. SEE FIGURE 1609.
 PLEASE CORRECT PLANS.
  
 5) SHEET S-1 CONCRETE FLOOR SECTIONS ARE CUT AND
 REMOVED BUT THERE IS NO MENTION OF HOW THE SOILS ARE TO
 BE TERMITE TREATED? 1816.1.
  
 6) SHEET D-1 NUMBER 62 INDICATES A CANOPY TO BE REMOVED
 BUT I COULD NOT LOCATE THIS WORK ON THIS SHEET, PLEASE
 PROVIDE LOCATION USING THE GRID LINES PROVIDED ON THE
 PLANS. 106.1.2.
 ADDITIONAL INFORMATION REQUIRED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-04-24 Cont ID  
Sent By dpalmer Date 2009-04-24 Time 10:15 Rev Time 0.00
Received By dpalmer Date 2009-04-24 Time 10:15 Sent To  
Notes
2009-04-24 10:21:51PLANS ROUTED TO DOUGLAS WISE (BUILDING OFFICIAL) FOR
 PLUMBING REVIEW AT HIS REQUEST.
  
 PLUMBING PLANS SHOULD BE REDLINED FOR THE NEW DUEL FUEL
 GENERATOR, TANK AND GAS LINES TO BE UNDER SEPARATE
 PERMITS. THIS WAS AGREED TO BY PUBLIX CORPORATE
 REPRESENTATIVE, DESIGN TEAM, CONTRACTOR AND PLAN REVIEW
 STAFF BEFORE PLANS WERE RESUBMITTED. THIS WAS GONE OVER
 WITH MR. ROBERT BROWN ALSO.
 ELECTRICAL, ZONING, AND BUILDING ALREADY HAVE PLANS
 REDLINED FOR SEPARATE PERMIT FOR THE LIFE SAFETY
 GENERATOR.
  
  
2009-04-24 10:15:27** REDLINED PLANS**
  
 STORE 319, 831 VILLAGE BLVD
  
 1) NOTE: THE ELECTRICAL DETAIL #1 ON RISER SHEET E-7
 STILL INDICATES A 30KW GENERATOR WHICH IS 45KW ON
 RISER. PER MEETINGS THE GENERATOR WILL BE UNDER
 SEPARATE PERMIT.
 PLEASE COORDINATE RISER AT LATER DATE WITH ANY OTHER
 REVISIONS AS NEEDED.
  
 2) NOTE: ALL CONTINUOUS LOADS 3 OR MORE HOURS NEED TO
 BE SHOWN AND FIGURED AT 125%. 215.3,230.42.
  
 3) NOTE: AS NOTED ABOVE THE LIFE SAFETY GENERATOR WILL
 BE UNDER SEPARATE PERMIT AND PLANS. VALUATION TO BE
 INCREASED TO FOR NEW ELECTRICAL SCOPE OF WORK ALONG
 WITH THE GENERATOR AND OTHER ASSOCIATED WORK. THESE
 VALUES TO BE INCLUDED WITH THE GENERATOR PERMIT
 APPLICATION.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-04-05 Cont ID  
Sent By dpalmer Date 2009-04-05 Time 12:13 Rev Time 0.00
Received By dpalmer Date 2009-04-05 Time 09:15 Sent To  
Notes
2009-04-05 12:13:30 
  
 ** DENIED 3RD REVIEW **
 ** SEVERAL NEW NOTES BASED ON REVISED PLANS. SOME ITEMS
 WHICH WERE REVISED TO ADDRESS PREVIOUS COMMENTS HAVE
 NOW CREATED NEW COMMENTS FOR MANY ITEMS WHICH NEED TO
 MEET MINIMUM CODES.
  
 STORE #319 831 VILLAGE BLVD.
  
  
 1) NOTE: THE PLANS SHOW A GEN PANEL LOCATED IN THE SAME
 ROOM AS OTHER ELECTRICAL SYSTEMS. PLEASE SEE NFPA-110
 7.2.2. THIS IS BASED ON THE DEFINITIONS WHICH INCLUDES
 ALL EPSS EQUIPMENT UP TO THE LOAD SIDE OF THE TRANSFER
 SWITCH THIS GEN PANEL MAY NOT BE IN THE SAME ROOM WITH
 OTHER EQUIPMENT. PLEASE SEE 2002 NFPA-110.
 PLEASE SEE ELECTRICAL ROOM PLANS ON E-7 WHICH SEEMS TO
 INDICATE A * LIFTER SWITCH*. WHAT IS THIS? PLEASE SEE
 NFPA-110
  
 2) NOTE: PLEASE ALSO SEE 700.9 2005 NEC. PLEASE SEE
 HANDBOOK COMMENTARY WHICH WILL PROVIDE MORE
 INFORMATION. BASED ON THE RISER AND PANELS, THERE IS
 OPTIONAL STAND-BY, AND POSSIBLY LEGALLY REQUIRED
 SYSTEMS IN THE SAME EQUIPMENT.
 THE GEN PANEL WOULD BE REQUIRED TO MEET 700.9 AS A
 SWITCHBOARD. SEE COMMENTARY AS A SWITCHBOARD WOULD
 PROVIDE THE REQUIRED SEPARATION. PLEASE KNOW THAT BASED
 ON COMMENT NUMBER ONE ABOVE THE LOCATION OF THIS GEN
 PANEL NEEDS TO BE ADJUSTED OR RISER NEEDS TO BE REVISED
 TO SHOW DIFFERENT EQUIPMENT. THERE ARE OTHER OPTIONS
 HOWEVER THIS IS ONLY NOTED BY REVIEWER AS NEEDING TO
 MET MINIMUM CODES.
 SYSTEMS NEED TO BE LABELED ACCORDINGLY SUCH AS *
 OPTIONAL STAND-BY AND LIFE SAFETY. BASED ON PANEL
 SCHEDULES SUBMITTED THERE IS LIFE SAFETY, LEGALLY
 REQUIRED AND OPTIONAL STAND-BY LOADS.
 NO PANEL SCHEDULE WAS SUBMITTED FOR E-1 WHICH IS FED
 FROM E SO THOSE LOADS CAN NOT BE DETERMINED TO BE
 700,701, OR 702 SYSTEM LOADS.
 THERE ARE MANY OTHERS.
  
 *** IT IS BEING NOTED BY THIS REVIEWER IN ORDER TO NOT
 DELAY PROJECT(S) SUBMITTED THAT A MEETING BE HELD AS
 SOON AS POSSIBLE TO GO OVER ALL STORES IN SUBMISSION TO
 THE CITY OF WEST PALM BEACH.
 ONCE RISER AND ALL ELECTRICAL SYSTEMS ARE CORRECTED,
 THE GENERATORS THEMSELVES MAY BE UNDER SEPARATE
 PERMITS. THIS MAY BE DISCUSSED IN MORE DETAIL ONCE
 CONTACT/MEETING HAS BEEN HELD.
  
 3) NOTE: PLEASE TAKE A LOOK AT THE SIZE OF THE JUNCTION
 BOX WITH THE FEEDERS ALONG WITH CONTROL CIRCUITS. THE
 FEEDERS GO INTO AND OUT OF THIS BOX ALONG WITH OTHER
 CONDUCTORS. THE PLANS STATE PULL BOX ONLY HOWEVER
 PLEASE BE SURE TO SEE 314.28 AS ANY VARIATION IN THESE
 AS SHOWN MAY INCREASE. THIS IS NOTED ONLY BASED ON
 OTHER COMMENTS THERE MAY BE A NEED FOR A CHANGE.
 PLEASE ALSO SEE EMERGENCY GENERATOR NETWORK CABLING AS
 THE CONDUCTORS SHOWN ON RISER ARE NOT THE SAME. AN
 EXAMPLE IS THE #14 ON RISER AND DETAIL SHOWS ALL #12?
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE PROPOSED GENERATOR, GENERATOR ENCLOSURE,
 ATS EQUIPMENT. BASED ON COMMENT #2 ABOVE, THERE MAY BE
 MORE THAN ONE.
 ENCLOSURES SHALL MEET NFPA-110 7.2.1.1
 NEC 110.3, 700.6, 90.7 ETC
  
 5) NOTE: FUEL STAND-BY TIME, CAPACITY, SIZING ETC NEEDS
 TO BE ON PLANS. MINIMUM TIMES ARE STATED IN NFPA-110
 CHAPTER 4 ALONG WITH NEC 700.12
  
 6) NOTE: PLEASE PROVIDE LOCATION OF DISCONNECT FOR
 FEEDERS MEETING 225.31-225.39. IF USING EXCEPTION IN
 700.12B6, 701.11B5, THEN ALL DISCONNECTING MEANS SHALL
 BE READILY ACCESSIBLE AND WITHIN SIGHT. BASED ON THE
 PLANS THE GENERATOR DOES MEET WITHIN SIGHT HOWEVER AS
 NO DISCONNECTING MEANS IS SHOWN NO OTHER CODE
 COMPLIANCE CAN BE VERIFIED. THE SHUNT TRIP DOES NOT
 MEET 225.38, 225.39.
 THE DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD
 SERVED.
 ** PLEASE BE AWARE THAT ANY BREAKER ON THE GENERATOR
 MAY OR MAY NOT MEET READILY ACCESSIBLE DEPENDING ON
 LOCKED ENCLOSURE, FENCING AROUND ENCLOSURE ETC..
  
 7) NOTE: THE LIGHTING CONTROLS IN BOTH RESTROOMS SHALL
 BE DUAL TECHNOLOGY. AS SHOWN IF DEVICES ARE MOTION ONLY
 AN OCCUPANT COULD BE OUT OF VIEWING AREA. THIS COULD
 CREATE A SAFETY ISSUE.
 OTHER DEVICES BEING INSTALLED AS NEW FOR LOCATIONS SUCH
 AS COOLERS APPEAR TO BE STANDARD SP SWITCHES. THE
 LIGHTING IN THESE AREAS ARE EXEMPT FROM LIGHTING
 PERFORMANCE CALCULATIONS HOWEVER ANY NEW BEING
 INSTALLED MUST MEET 13-415.1, 13-415.1.ABC.1.1, .1.2
 NEW OUTSIDE LIGHTS INDICATE CONTROLS PER ENERGY
 MANAGEMENT SYSTEM HOWEVER PLEASE SEE 13-415.1.ABC.1.4.
 DOES THIS PROVIDE 10HRS MINIMUM BACK UP FOR SCHEDULING
 OR MEET PHOTO-SENSOR REQUIREMENTS? IF THIS WAS THE ONLY
 ITEM IT WOULD HAVE BEEN REDLINED.
  
 8) NOTE: CODES ON PLANS NEED TO INCLUDE NFPA-110 2002.
  
 9) NOTE: NEW NOTE, PLUMBING PLANS SHOW NEW LINES FOR
 GAS TO NEW LS GENERATOR. PLEASE BE SURE TO SEE 7.9 OF
 NFPA-110, MORE SPECIFICALLY 7.9.3.1. *** THIS IS NOTED
 FOR INFORMATION, AS THE GAS REVIEW WILL BE DONE BE THE
 PLUMBING PLANS EXAMINERS. LIFE SAFETY SYSTEMS ARE UNDER
 REVIEW OF FIRE MARSHAL, BUILDING AND ELECTRICAL PLANS
 EXAMINERS.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-02-19 Cont ID  
Sent By dpalmer Date 2009-02-19 Time 13:34 Rev Time 0.00
Received By dpalmer Date 2009-02-19 Time 13:34 Sent To  
Notes
2009-02-19 13:37:01** DENIED SECOND REVIEW **
  
 ** PLEASE SEE NOTES BELOW AS THEY ARE EXACT COMMENTS
 FROM PREVIOUS REVIEW.
  
  
  
 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS WERE
 SUBMITTED MEETING PRESCRIPTIVE REQUIREMENTS. 13-415.2,
 13-415.2.ABC.1.1,.1.2,.1.3 ETC
 THIS WAS GONE OVER AT LENGTH IN MEETING HELD WITH
 DESIGNER FROM FIRM YET THE PLANS ARE RESUBMITTED WITH
 NO CALCULATIONS.
  
 2) NOTE: PLANS STILL DO NOT SHOW ANY COMPLIANCE FOR
 PRESCRIPTIVE REQUIREMENTS FOR NEW AREAS AND NEW
 LIGHTING CONTROLS FOR SEPARATE SPACES. THIS COMMENT WAS
 FOR NEW AREAS ONLY AND COMMENTS WERE GONE OVER WITH
 DESIGNER FROM FIRM AT LENGTH. HOWEVER PLANS STILL ONLY
 SHOW STANDARDS DEVICES AND NO COMPLIANCE FOR NEW IS
 SHOWN.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: NO LETTER WAS SUBMITTED WITH RESPECT TO
 REQUIRED LIGHTING FOR EGRESS OR OCCUPANCY NOT PERMITTED
 WHEN UNDER EMERGENCY POWER. THIS WAS ALSO GONE OVER AT
 LENGTH IN MEETING YET NO CHANGES IN PLANS OR STORE
 OPERATIONS ARE PROVIDED.
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME HOWEVER PLEASE SEE COMMENTS
 ABOUT AS SOME SECTIONS HAVE NOW BEEN REAPEATED TWICE.
  
 6) NOTE: THE RISER AS SHOWN DOES NOT INCLUDE THE MOST
 RECENT ELECTRICAL REVISIONS AS MADE ON SITE WITH THE
 MOST RECENT PERMITTED ELECTRICAL WORK. THIS WILL NEED
 TO BE REVISED.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-29 Cont ID  
Sent By dpalmer Date 2008-08-29 Time 16:57 Rev Time 0.00
Received By dpalmer Date 2008-08-29 Time 16:57 Sent To  
Notes
2008-08-29 16:58:06** DENIED *
  
  
 1) NOTE: PLEASE CONFIRM LICENSING OF THE FIRM AS
 LISTED. THE CERTIFICATE OF AUTHORIZATION NUMBER SHOWN
 IS LISTED FOR POST, BUCKLEY, SCHUH AND JERNIGAN, INC AT
 A LOCATION OTHER THAN LISTED ON PLANS. THE FIRM NAME AS
 LISTED ALONG WITH ADDRESS IS NOT LISTED ON STATE
 WEBSITE.
 PLEASE ALSO INDICATE THE ARCHITECTURAL FIRM LICENSE
 NUMBER THE NUMBER AS LISTED DOES COME UP ON WEBSITE FOR
 ENGINEERING FIRM HOWEVER NOT FOR ARCHITECTURAL
 BUSINESS.
 PLEASE SEE FS 471.023 (ENG) FS 481.219 (ARCH) AND FAC
 61G15-23.002, 61G1-16.004.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON THE ELECTRICAL PLANS AS WELL AS CORRECTING COVER
 SHEETS.
 PLEASE SEE THE COVER SHEET AS IT STATES A 2004 NEC. YET
 THERE IS NO SUCH CODE.
 THE LIFE SAFETY PLAN HOWEVER DOES LIST THE 2005 NEC.
  
 2004 FBC W/2007 REVISIONS.
 2003 NFPA-101
 2002 NFPA-72
  
 3) NOTE: PLEASE INDICATE THE REQUIRED BATTERY BACK UP
 LIGHTING FOR EGRESS PATHS IN AREAS IN WHICH WORK IS
 BEING DONE. AS THIS LOCATION IS A LOCATION IN WHICH
 OCCUPANCY WILL OCCUR UNDER GENERATOR POWER IN ANY EVENT
 OF POWER FAILURE BATTERY BACK UP LIGHTING FOR 1FT
 CANDLE MINIMUM FOR EGRESS PATHS WILL BE REQUIRED.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1, .2.2.
  
 ** NORMAL OCCUPANCY IS BEING PROPOSED IN THIS LOCATION
 UNDER EMERGENCY POWER. IN THIS SITUATION LOSING THE
 *EMERGENCY* BACK UP WOULD CAUSE ALL EGRESS AREAS TO
 HAVE NO LIGHTING WHICH IS A LIFE SAFETY SITUATION.
  
 ** IF EGRESS LIGHTING IS CURRENTLY PROVIDED WITH
 BATTERY BACK UP MEETING THE LIFE SAFETY CODE IN ANY
 AREAS, PLEASE INDICATE.
 AT THIS TIME NO KNOWN BATTERY BACK UP POWER FOR MAIN
 AREAS ARE KNOWN TO BE BATTERY BACK UP.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN AREAS IN WHICH NEW LIGHTING IS BEING
 INSTALLED.
 PLEASE SEE13-415.2.ABC.1.1, .1.2.
  
 5) NOTE: PLEASE PROVIDE HOW LIGHTING CONTROLS FOR NEW
 BEING INSTALLED MEET SECTIONS 13-415.1.ABC.1.1,.1.2 AND
 .1.3.
  
 6) NOTE: PLEASE SEE OWNER INFORMATION ON PERMIT
 APPLICATION DOES NOT COORDINATE WITH THE PALM BEACH
 COUNTY PROPERTY APPRAISER OWNER OF RECORD INFORMATION.
  
 7) NOTE: PLEASE UPDATE ELECTRICAL RISER WITH THE LATEST
 PERMITTED WORK FOR BACK UP GENERATOR ETC.
 230, 240, 310, ETC
 ** THE EXISTING RISER IS NOT REVIEWED FOR CODE
 COMPLIANCE.
  
 8) NOTE: PLEASE PROVIDE INFORMATION ON WHETHER OR NOT
 THE CONTINUOUS LOADS ARE FIGURED AT 125% 215.3,230.42
 ETC.
 220.87
  
 9) NOTE: PLEASE BE SURE THE CIRCUITS ARE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. THIS NOTE IS FOR
 NEW. PLEASE SEE 408.4 WHICH DOES NOT ACCEPT
 *RECEPTACLES* OR *LIGHTING* AS GENERAL NOTATIONS.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-04-27 Cont ID  
Sent By dpalmer Date 2009-04-27 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2009-04-27 Time 08:49 Sent To  
Notes
2009-04-27 08:49:55FIRE REVIEW OK, SHEETS STAMPED, WILL REVISE LS AND A
 SHEETS TO COORDINATE FOR EXIT SIGNS BEFORE INSPECTIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-04-06 Cont ID  
Sent By mawillia Date 2009-04-06 Time 12:11 Rev Time 0.00
Received By mawillia Date 2009-04-06 Time 11:32 Sent To  
Notes
2009-04-06 12:11:34*****PROVISO*****
  
 PLAN SHEETS FP-1, FA-1 & FA-2 WERE PREVIOUSLY
 FIRE-STAMPED ON 02/26/09; SHEETS LS-1, A-2, AND A-4
 WERE STAMPED, INITIALED, AND DATED. PLAN SHEET E-2 TO
 BE FIRE-STAMPED WHEN THE ELECTRICAL EXAMINER'S COMMENTS
 AS WELL AS THE BELOW COMMENT HAS BEEN ADDRESSED:
  
 1. IN THE LOWER RIGHT HAND CORNER OF THE FLOOR PLAN, AN
 EXIT LIGHT IS SHOWN FOR THE DOOR ON SHEET E-2, BUT IS
 NOT SHOWN ON SHEET LS-1 AND A-2. PLEASE CORRELATE
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-02-26 Cont ID  
Sent By mwennerg Date 2009-02-26 Time 10:13 Rev Time 0.00
Received By mwennerg Date 2009-02-26 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-19 Cont ID  
Sent By mwennerg Date 2008-09-19 Time 15:23 Rev Time 0.00
Received By mwennerg Date 2008-09-19 Time 15:23 Sent To  
Notes
2008-09-19 15:29:49***DENIED***
  
 1) BUILDING CODE ANALYSIS INDICATES NFPA, 2003 EDITION.
 LIST SPECIFIC NFPA STANDARD.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) BUILDING CODE ANALYSIS LISTS PROJECT AS EXISTING
 MERCANTILE. SECTION 7.4.1.2 APPLIES TO MEANS OF EGRESS
 OTHER THAN EXISTING BUILDINGS.
  
 4) EXIT SIGNS SHALL BE PROVIDED AT DISTANCES NOT TO
 EXCEED 100'.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 6) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 HOOD/SUPPRESSION SYSTEM.
  
 7) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 8) CLARIFY SCOPE OF WORK REGARDING FIRE ALARM SYSTEM
 AND SHOW ALL EQUIPMENT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2009-04-27 Cont ID  
Sent By dwise Date 2009-04-27 Time 19:51 Rev Time 0.00
Received By dwise Date 2009-04-27 Time 19:51 Sent To  
Notes
2009-04-27 19:51:39GAS UNDER SEPERATE PERMIT AND REVIEW.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-04-02 Cont ID  
Sent By kstevens Date 2009-04-02 Time 18:15 Rev Time 0.00
Received By kstevens Date 2009-04-02 Time 18:15 Sent To  
Notes
2009-04-02 18:26:29DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 NFPA-58
  
 A. SHT P-3 & P-4 FIGURE I.1(B) NOTE 1. REGARDLESS OF
 ITS SIZE, ANY ASME CONTAINER FILLED ON SITE MUST BE
 LOCATED SO THAT THE FILLING CONNECTION AND FIXED
 MAXIMUM LIQUID LEVEL GAUGE ARE AT LEAST 10 FT FROM ANY
 EXTERNAL SOURCE OF IGNITION. SEE TABLE 6.3.9. TANK IS A
 MAXIMUM 7 FT TO THE FAR SIDE OF THE GENERATOR.
  
 B. SUBMIT THE FOLLOWING INFORMATION FOR THE SEPARATE
 GAS PERMIT REQUIRED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - ALSO SHOW THE AUTOMATIC
 TRANSFER VALVE AND SHUT OFF VALES.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 7. INDICATE THE BTU LOAD OF THE EXISTING GENERATOR THAT
 WILL BE REMOVED.
  
 8. SUBMIT MANUF. SPECIFICATIONS FOR THE AUTOMATIC
 TRANSFER VALVE THAT SWITCHES THE GENERATOR FROM LP GAS
 TO NATURAL GAS.
  
 DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS PHM-001 THRU PHM-016. A TITLE BLOCK SHALL BE
 USED ON EACH SHEET CONTAINING THE PRINTED NAME, ADDRESS
 AND LICENSE NUMBER OF THE ENGINEER OR IF APPLICABLE,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER, AND IF
 PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS. FAC
 61G15-23.002(2) & FS 471.025.
  
 2. ALL SHTS WITH MOFFATT & NICHOL TITLE BLOCKS. THE
 ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE,
 (3780 KILROY AIRPORT WAY LONG BEACH CALIFORNIA), DOES
 NOT REFLECT THE ADDRESS IN THE TITLE BLOCKS, (1509 W.
 SWANN AVE. TAMPA FLORIDA). FAC 61G15-23.002(2) & FS
 471.025. PLEASE UPDATE TITLE BLOCKS OR THE DBPR WEBSITE
 PRIOR TO RESUBMITTING TO THE CITY WPB FOR REVIEW. (THE
 ADDRESS ON THE DBPR WEBSITE CAN BE ADDED TO THE TITLE
 BLOCK OF EACH SHEET TO COMPLY WITH THIS REQUIREMENT).
  
 3. SHT G-003 CODE DESIGN CRITERIA SHALL INCLUDE THE
 FBC-2004 WITH 2007 REVISIONS. SECTION 106.1.1.
  
 4. THE WATER SUPPLY TO THE DOCKS SHALL BE PROTECTED
 FROM BACKFLOW PER SECTION 608.13.2. PLEASE INDICATE THE
 RPZV BACKFLOW LOCATION FOR EACH DOCK OR IF ALL DOCKS
 ARE CONNECTED TO ONE METER INDICATE ON PLANS THE
 LOCATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-06-24 Cont ID  
Sent By jgomez Date 2009-06-24 Time 10:07 Rev Time 0.00
Received By jgomez Date 2009-06-24 Time 10:07 Sent To  
Notes
2009-06-24 10:08:09SENT TO RON REGUEIRO'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-03 Cont ID  
Sent By adarroug Date 2009-04-03 Time 11:12 Rev Time 0.00
Received By adarroug Date 2009-04-03 Time 11:12 Sent To  
Notes
2009-04-03 11:13:08TO "C27"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-29 Cont ID  
Sent By adarroug Date 2009-01-29 Time 09:02 Rev Time 0.00
Received By adarroug Date 2009-01-29 Time 09:02 Sent To  
Notes
2009-01-29 09:02:49TO "COMM" BD#39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-19 Cont ID  
Sent By mwennerg Date 2008-09-19 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2008-08-21 Time 11:01 Sent To  
Notes
2008-08-21 11:01:49TO "COMM" BD#34

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-07-01 Cont ID  
Sent By dwise Date 2009-07-01 Time 21:11 Rev Time 0.00
Received By dwise Date 2009-07-01 Time 21:11 Sent To PC
Notes
2009-07-01 21:12:48REVIEWED REVISED SHEETS M-1 THROUGH M-5 INCLUSIVE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-02-22 Cont ID  
Sent By rregueir Date 2009-02-22 Time 13:21 Rev Time 0.00
Received By rregueir Date 2009-02-22 Time 13:09 Sent To  
Notes
2009-02-22 13:21:10******PROVISO******
 PROVIDE SUPPORTING DOCUMENTATION FROM APPLIANCE
 MANUFACTURER SHOWING NEW AC-1 AND AC-2 ARE DESIGNED TO
 RESIST ANTICIPATED WIND PRESSURES IN ACCORDANCE WITH
 FBC-M 301.13. SUCH DATA SHALL BE SUBMITTED FOR PLAN
 REVIEW PRIOR TO FINAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-03 Cont ID  
Sent By rregueir Date 2008-09-03 Time 16:06 Rev Time 0.00
Received By rregueir Date 2008-09-02 Time 15:13 Sent To  
Notes
2008-09-03 16:06:55REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. STRUCTURAL PLANS SHOW A DETAIL FOR NEW CONDENSER #8.
 THE HEIGHT OF THE CONDENSER ABOVE THE ROOF SURFACE IS
 NOT SHOWN ON THE PAGE S-2 DETAILS. SHOW THE MINIMUM
 REQUIRED CLEARANCE FROM THE ROOF SURFACE ON THE PLANS
 IN ACCORDANCE WITH FBCB TABLE 1509.7.
  
 2. PAGE S-2 GENERAL NOTE #6 CALLS FOR DETAIL SHOWING
 HOW THE APPLIANCE IS TO BE ATTACHED TO THE STAND TO
 MEET WIND RESISTANCE REQUIREMENTS. NO SUCH DETAIL OR
 SHOP DRAWING WAS PROVIDED. PROVIDE MISSING INFORMATION
 TO DEMONSTRATE COMPLIANCE WITH THE WIND RESISTANCE
 REQUIREMENTS OF FBCM 301.13 FOR ATTACHMENT TO THE
 STRUCTURE.
  
 3. IN ADDITION TO THE ABOVE REQUIREMENTS, PROVIDE
 DOCUMENTATION FROM THE MANUFACTURER OF CONDENSER #8
 SHOWING THAT THE APPLIANCE ITSELF IS DESIGNED TO RESIST
 WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 4. PAGE M-3 NOTE ON ROOF PLAN INDICATES THAT THE NEW
 AC-1 AND NEW AC-2 WILL FIT ON THE EXISTING ROOF CURB.
 HOWEVER, DETAIL 7 ON PAGE M-4 CALLS FOR A CURB ADAPTER
 FOR NEW AC UNITS. WHICH IS CORRECT? PLEASE CLARIFY IN
 ACCORDANCE WITH FBCB 106.1.1. ADJUST ATTACHMENT DETAIL
 AND NOTES SO PLANS ARE COORDINATED AND SHOW AN
 ATTACHMENT DETAIL WHICH IS IN COMPLIANCE WITH FBCM
 301.13.
  
 5. PROVIDE DOCUMENTATION FROM THE MANUFACTURER OF AC-1
 AND AC-2 SHOWING THESE APPLIANCES ARE DESIGNED TO
 RESIST WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 6. PAGE M-4: DETAIL #8 SHOWS GALVANIZED STRAPS OVER F-6
 TO SECURE THE FAN FOR WIND LOADS. THIS FAN IS AN
 UPBLAST FAN, NOT A DOWN DISCHARGE FAN AS SHOWN IN THIS
 DETAIL. STRAPS OVER AN UPBLAST GREASE EXHAUST FAN WILL
 ACCUMULATE GREASE AND DIVERT IT TO LOCATIONS OTHER THAN
 THE GREASE RESERVOIR SUPPLIED WITH THE FAN. THIS HAS
 THE POTENTIAL TO CREATE AN ADDITIONAL FIRE HAZARD ON
 THE ROOF. IT IS ALSO UNCLEAR HOW THESE STRAPS WILL
 INTERACT WITH THE HINGE MECHANISM ON THE GREASE EXHAUST
 FAN AS REQUIRED IN ACCORDANCE WITH FBCM 506.5.3.
 NOTE: THERE ARE GREASE EXHAUST FANS AND CURBS WHICH ARE
 DESIGNED TO RESIST WIND PRESSURES WITHOUT THE USE OF
 ADDITIONAL, FIELD INSTALLED STRAPPING WHICH WILL AVOID
 INTERFERENCE WITH GREASE EXHAUST DISCHARGE. THIS MAY BE
 A PREFERABLE (TO THE DESIGN PROFESSIONAL OR OWNER)
 MEANS OF ACCOMPLISHING COMPLIANCE WITH THESE CODE
 PROVISIONS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-04-27 Cont ID  
Sent By dwise Date 2009-04-27 Time 19:42 Rev Time 0.00
Received By dwise Date 2009-04-27 Time 19:42 Sent To PC
Notes
2009-04-27 19:42:58ALL GAS AND FUEL TO BE BY SEPERATE PERMIT AND NOT
 INCLUDED IN THE SCOPE OF THIS PERMIT OR REVIEW.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-03-03 Cont ID  
Sent By kstevens Date 2009-03-03 Time 16:41 Rev Time 0.00
Received By kstevens Date 2009-03-03 Time 16:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-25 Cont ID  
Sent By kstevens Date 2008-08-25 Time 16:51 Rev Time 0.00
Received By kstevens Date 2008-08-25 Time 16:51 Sent To  
Notes
2008-08-25 16:58:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS THE TITLE BLOCK SHALL CONTAIN THE PRINTED
 NAME, ADDRESS, AND LICENSE NUMBER OF THE ENGINEER. THE
 ADDRESS DOES NOT REFLECT THE ADDRESS OF RECORD ON THE
 STATE OF FLORIDA, DBPR WEBSITE. PLEASE UPDATE THE
 WEBSITE OR THE TITLE BLOCKS TO REFLECT EACH OTHER PRIOR
 TO RESUBMITTING FOR REVIEW AT THE CITY WPB. FAC
 61G15-23.002(2) & FS 471.025.
  
 2. SHT P-3 THREE LINES TO TWO CD-1 AND ONE CD-2 SHALL
 CONNECT TO THE VENTED HORIZONTAL DRAIN LINE, NOT THE
 FIXTURE DRAIN LINE FROM ANOTHER FIXTURE. SECTION
 912.2.4.
  
 3. SHT P-3 NEW SINK P-12 NOT INDICATED ON THE PLUMBING
 FIXTURE SHOWN ON SHEET P-7. PLEASE CORRELATE. SECTION
 106.1.1.
  
 4. SHT P-5 TWO CD-1 AND ONE CD-2 SHALL CONNECT TO THE
 VENTED HORIZONTAL DRAIN LINE, NOT THE FIXTURE DRAIN
 LINE FROM ANOTHER FIXTURE. SECTION 912.2.4.
  
 5. SHT P-5 TWO CD-1 SHOW NO TRAPS. THIS DOES NOT
 CORRELATE WITH THE FLOOR DRAIN, CLEAN OUTS, ETC.
 SCHEDULE ON SHT P-7 WHICH INDICATES THAT THE CD-1 4"
 CASE DRAINS HAVE A P-TRAP. PLEASE CLARIFY & CORRELATE.
 SECTIONS 106.1.1 & 1002.1.
  
 6. SHT P-7 FOOD PREPARATION SINK DETAIL SHOW A 2" AIR
 GAP. PER SECTION 802.2.1 THE MINIMUM AIR GAP SHALL BE
 MINIMUM TWICE THE EFFECTIVE OPENING OF THE INDIRECT
 WASTE PIPI. THE INDIRECT WASTE PIPE IS SHOWN AS 1-1/2".
 MINIMUM 3" AIR GAP REQUIRED.
  
 7. SHT P-7 WATER FILTER DETAIL. THE WATER FILTER MUST
 MEET THE REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF.
 SPECIFICATIONS SHOWING COMPLIANCE. SECTION 611.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]