| Plan Review Stops For Permit 08080402 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-04-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-04-05 |
Time |
19:16 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-04-05 |
Time |
19:16 |
Sent To |
|
|
| Notes |
| 2009-04-05 19:20:11 | BUILDING PLAN REVIEW | | | PERMIT: 08080402 | | | ADD: 831 VILLAGE BLVD. | | | CONT: OAK CONSTRUCTION | | | TEL: (954)583-9625 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | APRIL 05/09 | | | | | | BUILDING PROVISO: | | | | | | 1) SHEET S-2 ROOFTOP HVAC EQUIPMENT SEE NOTE 6 NEW HVAC | | | TO MEET THE 2004 FBC WINDLOADS OF 140MPH/ 3 SECOND | | | GUST, TO PROVIDE ENGINEERED CALCULATIONS. | | | | | | 2) SHEET D1, NOTE 137 REMOVAL OF EXISTING GENERAL SEE | | | ELECTRICAL SHEETS FOR ADDITIONAL INFO, E SHEETS | | | INDICATE THE INSTALATION OF A NEW GENERATOR. | | | PROVIDE ANCHORING DETAIL OF THE NEW GENERATOR TO THE | | | EXISTING SLAB. PROVIDE WIND DESIGN INFORMATION ALSO. | | | SEE FIGURE 1609 AND SECTION 1609.1.3 ANCHORAGE AGAINST | | | OVERTURNING, UPLIFT AND SLIPPAGE BEFORE CALLING IN | | | INSPECTIONS. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-02-05 |
Time |
15:13 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2009-02-05 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2009-02-05 15:51:43 | BUILDING PLAN REVIEW | | | PERMIT: 08080402 | | | ADD: 831 VILLAGE BLVD . | | | CONT: OAK CONSTRUCTION | | | TEL: (954)583-9625 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | FEB. 05/2009 | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B ) INFORMATIONAL FL S S 713.13 NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 2) PBS & J NO CERTIFICATE OF AUTHORIZATION WAS FOUND | | | FOR AN ENGINEERS OFFICE ON THE PLANS.THE PLANS HAVE A | | | CERTIFICATE OF AUTHORIZATION FOR A SURVEYORS BUSINESS | | | LOCATED AT THE SAME ADDRESS. THERE IS CURRENTLY A | | | CERTIFICATE OF AUTHORIZATION FOR PBS J CONSTRUCTION | | | SERVICES, INC AT THE SAME OFFICE BUT NOT AS PBS & J, | | | INC. 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE | | | TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN | | | ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING | | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. | | | THIS MAY BE ADDED BY HAND. | | | | | | 3) COMPLIED. | | | | | | 4) (A) COMPLIED. | | | | | | 4)(B) 2ND REQUEST, SHEET S-2 GENERAL NOTES DOES HAVE | | | WIND INFORMATION FOR THE HIGH WIND VELOCITY ZONES WHICH | | | ARE DADE AND BROWARD COUNTIES. THE CITY OF WEST PALM | | | BEACH IS NOT LOCATED WITHIN THIS ZONE. THE CITY IS | | | LOCATED IN A WIND BORN DEBRIS REGION WITH A WIND ZONE | | | OF 140 MPH, 3 SECOND GUST. SEE FIGURE 1609. PLEASE | | | CORRECT PLANS. | | | | | | 5-6) COMPLIED. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-02 |
Time |
11:34 |
Rev Time |
4.44 |
| Received By |
jwitmer |
Date |
2008-09-02 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2008-09-02 13:18:33 | BUILDING PLAN REVIEW | | | PERMIT: 08080402 | | | ADD: 831 VILLAGE BLVD . | | | CONT: OAK CONSTRUCTION | | | TEL: (954)583-9625 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SEPTEMBER 02, 2008 | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B ) INFORMATIONAL FL S S 713.13 NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 2) PBS & J NO CERTIFICATE OF AUTHORIZATION WAS FOUND | | | FOR A ARCHITECTS OFFICE, NO CERTIFICATE OF | | | AUTHORIZATION WAS FOUND FOR PBS & J (DBA) FOR AN | | | ENGINEERS OFFICE. THERE IS CURRENTLY A CERTIFICATE OF | | | AUTHORIZATION FOR POST, BUCKLEY, SCHUH & JEERNIGAN, | | | INC. | | | 481.219 F.S. CERTIFICATE OF AUTHORIZATION. (ARCHITECTS) | | | THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN | | | ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL | | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH | | | SHEET. | | | THIS MAY BE ADDED BY HAND. | | | 471.023 F.S. CERTIFICATE OF AUTHORIZATION. (ENGINEER) | | | THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN | | | ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING | | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. | | | THIS MAY BE ADDED BY HAND. | | | | | | 3) SHEET A-1 INDICATES THE REUSE OF A BOSTON BEAM, BUT | | | NO INFORMATION AS TO THE WEIGHT OF THIS STRUCTURE OR | | | HOW IT WILL BE ATTACHED TO THE BAR JOIST, AND IF THE | | | ADDITIONAL WEIGHT WILL EFFECT THE BAR JOIST SYSTEM. | | | 106.1.2 ADDITIONAL INFORMATION REQUIRED. | | | | | | 4) (A)SHEET S-2 INDICATES THE WIND DESIGN TO THE 2005 | | | ASCE 7-05, THE 2004 FBC RECOGNIZES THE ASCE 7-02. 2004 | | | FBC CHAPTER 35 REFERENECED STANDARDS RECOGNIZES ASCE | | | 7-02 . ALSO 1603.1.4 WIND DESIGN DATA. | | | | | | 4)(B) SHEET S-2 GENERAL NOTES DOES HAVE WIND | | | INFORMATION FOR THE HIGH WIND VELOCITY ZONES WHICH ARE | | | DADE AND BROWARD COUNTIES. THE CITY OF WEST PALM BEACH | | | IS NOT LOCATED WITHIN THIS ZONE. | | | THE CITY IS LOCATED IN A WIND BORN DEBRIS REGION WITH A | | | WIND ZONE OF 140 MPH, 3 SECOND GUST. SEE FIGURE 1609. | | | PLEASE CORRECT PLANS. | | | | | | 5) SHEET S-1 CONCRETE FLOOR SECTIONS ARE CUT AND | | | REMOVED BUT THERE IS NO MENTION OF HOW THE SOILS ARE TO | | | BE TERMITE TREATED? 1816.1. | | | | | | 6) SHEET D-1 NUMBER 62 INDICATES A CANOPY TO BE REMOVED | | | BUT I COULD NOT LOCATE THIS WORK ON THIS SHEET, PLEASE | | | PROVIDE LOCATION USING THE GRID LINES PROVIDED ON THE | | | PLANS. 106.1.2. | | | ADDITIONAL INFORMATION REQUIRED. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-04-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-24 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-24 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2009-04-24 10:21:51 | PLANS ROUTED TO DOUGLAS WISE (BUILDING OFFICIAL) FOR | | | PLUMBING REVIEW AT HIS REQUEST. | | | | | | PLUMBING PLANS SHOULD BE REDLINED FOR THE NEW DUEL FUEL | | | GENERATOR, TANK AND GAS LINES TO BE UNDER SEPARATE | | | PERMITS. THIS WAS AGREED TO BY PUBLIX CORPORATE | | | REPRESENTATIVE, DESIGN TEAM, CONTRACTOR AND PLAN REVIEW | | | STAFF BEFORE PLANS WERE RESUBMITTED. THIS WAS GONE OVER | | | WITH MR. ROBERT BROWN ALSO. | | | ELECTRICAL, ZONING, AND BUILDING ALREADY HAVE PLANS | | | REDLINED FOR SEPARATE PERMIT FOR THE LIFE SAFETY | | | GENERATOR. | | | | | | | | 2009-04-24 10:15:27 | ** REDLINED PLANS** | | | | | | STORE 319, 831 VILLAGE BLVD | | | | | | 1) NOTE: THE ELECTRICAL DETAIL #1 ON RISER SHEET E-7 | | | STILL INDICATES A 30KW GENERATOR WHICH IS 45KW ON | | | RISER. PER MEETINGS THE GENERATOR WILL BE UNDER | | | SEPARATE PERMIT. | | | PLEASE COORDINATE RISER AT LATER DATE WITH ANY OTHER | | | REVISIONS AS NEEDED. | | | | | | 2) NOTE: ALL CONTINUOUS LOADS 3 OR MORE HOURS NEED TO | | | BE SHOWN AND FIGURED AT 125%. 215.3,230.42. | | | | | | 3) NOTE: AS NOTED ABOVE THE LIFE SAFETY GENERATOR WILL | | | BE UNDER SEPARATE PERMIT AND PLANS. VALUATION TO BE | | | INCREASED TO FOR NEW ELECTRICAL SCOPE OF WORK ALONG | | | WITH THE GENERATOR AND OTHER ASSOCIATED WORK. THESE | | | VALUES TO BE INCLUDED WITH THE GENERATOR PERMIT | | | APPLICATION. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2009-04-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-05 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-05 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2009-04-05 12:13:30 | | | | | | | ** DENIED 3RD REVIEW ** | | | ** SEVERAL NEW NOTES BASED ON REVISED PLANS. SOME ITEMS | | | WHICH WERE REVISED TO ADDRESS PREVIOUS COMMENTS HAVE | | | NOW CREATED NEW COMMENTS FOR MANY ITEMS WHICH NEED TO | | | MEET MINIMUM CODES. | | | | | | STORE #319 831 VILLAGE BLVD. | | | | | | | | | 1) NOTE: THE PLANS SHOW A GEN PANEL LOCATED IN THE SAME | | | ROOM AS OTHER ELECTRICAL SYSTEMS. PLEASE SEE NFPA-110 | | | 7.2.2. THIS IS BASED ON THE DEFINITIONS WHICH INCLUDES | | | ALL EPSS EQUIPMENT UP TO THE LOAD SIDE OF THE TRANSFER | | | SWITCH THIS GEN PANEL MAY NOT BE IN THE SAME ROOM WITH | | | OTHER EQUIPMENT. PLEASE SEE 2002 NFPA-110. | | | PLEASE SEE ELECTRICAL ROOM PLANS ON E-7 WHICH SEEMS TO | | | INDICATE A * LIFTER SWITCH*. WHAT IS THIS? PLEASE SEE | | | NFPA-110 | | | | | | 2) NOTE: PLEASE ALSO SEE 700.9 2005 NEC. PLEASE SEE | | | HANDBOOK COMMENTARY WHICH WILL PROVIDE MORE | | | INFORMATION. BASED ON THE RISER AND PANELS, THERE IS | | | OPTIONAL STAND-BY, AND POSSIBLY LEGALLY REQUIRED | | | SYSTEMS IN THE SAME EQUIPMENT. | | | THE GEN PANEL WOULD BE REQUIRED TO MEET 700.9 AS A | | | SWITCHBOARD. SEE COMMENTARY AS A SWITCHBOARD WOULD | | | PROVIDE THE REQUIRED SEPARATION. PLEASE KNOW THAT BASED | | | ON COMMENT NUMBER ONE ABOVE THE LOCATION OF THIS GEN | | | PANEL NEEDS TO BE ADJUSTED OR RISER NEEDS TO BE REVISED | | | TO SHOW DIFFERENT EQUIPMENT. THERE ARE OTHER OPTIONS | | | HOWEVER THIS IS ONLY NOTED BY REVIEWER AS NEEDING TO | | | MET MINIMUM CODES. | | | SYSTEMS NEED TO BE LABELED ACCORDINGLY SUCH AS * | | | OPTIONAL STAND-BY AND LIFE SAFETY. BASED ON PANEL | | | SCHEDULES SUBMITTED THERE IS LIFE SAFETY, LEGALLY | | | REQUIRED AND OPTIONAL STAND-BY LOADS. | | | NO PANEL SCHEDULE WAS SUBMITTED FOR E-1 WHICH IS FED | | | FROM E SO THOSE LOADS CAN NOT BE DETERMINED TO BE | | | 700,701, OR 702 SYSTEM LOADS. | | | THERE ARE MANY OTHERS. | | | | | | *** IT IS BEING NOTED BY THIS REVIEWER IN ORDER TO NOT | | | DELAY PROJECT(S) SUBMITTED THAT A MEETING BE HELD AS | | | SOON AS POSSIBLE TO GO OVER ALL STORES IN SUBMISSION TO | | | THE CITY OF WEST PALM BEACH. | | | ONCE RISER AND ALL ELECTRICAL SYSTEMS ARE CORRECTED, | | | THE GENERATORS THEMSELVES MAY BE UNDER SEPARATE | | | PERMITS. THIS MAY BE DISCUSSED IN MORE DETAIL ONCE | | | CONTACT/MEETING HAS BEEN HELD. | | | | | | 3) NOTE: PLEASE TAKE A LOOK AT THE SIZE OF THE JUNCTION | | | BOX WITH THE FEEDERS ALONG WITH CONTROL CIRCUITS. THE | | | FEEDERS GO INTO AND OUT OF THIS BOX ALONG WITH OTHER | | | CONDUCTORS. THE PLANS STATE PULL BOX ONLY HOWEVER | | | PLEASE BE SURE TO SEE 314.28 AS ANY VARIATION IN THESE | | | AS SHOWN MAY INCREASE. THIS IS NOTED ONLY BASED ON | | | OTHER COMMENTS THERE MAY BE A NEED FOR A CHANGE. | | | PLEASE ALSO SEE EMERGENCY GENERATOR NETWORK CABLING AS | | | THE CONDUCTORS SHOWN ON RISER ARE NOT THE SAME. AN | | | EXAMPLE IS THE #14 ON RISER AND DETAIL SHOWS ALL #12? | | | | | | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS ON THE PROPOSED GENERATOR, GENERATOR ENCLOSURE, | | | ATS EQUIPMENT. BASED ON COMMENT #2 ABOVE, THERE MAY BE | | | MORE THAN ONE. | | | ENCLOSURES SHALL MEET NFPA-110 7.2.1.1 | | | NEC 110.3, 700.6, 90.7 ETC | | | | | | 5) NOTE: FUEL STAND-BY TIME, CAPACITY, SIZING ETC NEEDS | | | TO BE ON PLANS. MINIMUM TIMES ARE STATED IN NFPA-110 | | | CHAPTER 4 ALONG WITH NEC 700.12 | | | | | | 6) NOTE: PLEASE PROVIDE LOCATION OF DISCONNECT FOR | | | FEEDERS MEETING 225.31-225.39. IF USING EXCEPTION IN | | | 700.12B6, 701.11B5, THEN ALL DISCONNECTING MEANS SHALL | | | BE READILY ACCESSIBLE AND WITHIN SIGHT. BASED ON THE | | | PLANS THE GENERATOR DOES MEET WITHIN SIGHT HOWEVER AS | | | NO DISCONNECTING MEANS IS SHOWN NO OTHER CODE | | | COMPLIANCE CAN BE VERIFIED. THE SHUNT TRIP DOES NOT | | | MEET 225.38, 225.39. | | | THE DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD | | | SERVED. | | | ** PLEASE BE AWARE THAT ANY BREAKER ON THE GENERATOR | | | MAY OR MAY NOT MEET READILY ACCESSIBLE DEPENDING ON | | | LOCKED ENCLOSURE, FENCING AROUND ENCLOSURE ETC.. | | | | | | 7) NOTE: THE LIGHTING CONTROLS IN BOTH RESTROOMS SHALL | | | BE DUAL TECHNOLOGY. AS SHOWN IF DEVICES ARE MOTION ONLY | | | AN OCCUPANT COULD BE OUT OF VIEWING AREA. THIS COULD | | | CREATE A SAFETY ISSUE. | | | OTHER DEVICES BEING INSTALLED AS NEW FOR LOCATIONS SUCH | | | AS COOLERS APPEAR TO BE STANDARD SP SWITCHES. THE | | | LIGHTING IN THESE AREAS ARE EXEMPT FROM LIGHTING | | | PERFORMANCE CALCULATIONS HOWEVER ANY NEW BEING | | | INSTALLED MUST MEET 13-415.1, 13-415.1.ABC.1.1, .1.2 | | | NEW OUTSIDE LIGHTS INDICATE CONTROLS PER ENERGY | | | MANAGEMENT SYSTEM HOWEVER PLEASE SEE 13-415.1.ABC.1.4. | | | DOES THIS PROVIDE 10HRS MINIMUM BACK UP FOR SCHEDULING | | | OR MEET PHOTO-SENSOR REQUIREMENTS? IF THIS WAS THE ONLY | | | ITEM IT WOULD HAVE BEEN REDLINED. | | | | | | 8) NOTE: CODES ON PLANS NEED TO INCLUDE NFPA-110 2002. | | | | | | 9) NOTE: NEW NOTE, PLUMBING PLANS SHOW NEW LINES FOR | | | GAS TO NEW LS GENERATOR. PLEASE BE SURE TO SEE 7.9 OF | | | NFPA-110, MORE SPECIFICALLY 7.9.3.1. *** THIS IS NOTED | | | FOR INFORMATION, AS THE GAS REVIEW WILL BE DONE BE THE | | | PLUMBING PLANS EXAMINERS. LIFE SAFETY SYSTEMS ARE UNDER | | | REVIEW OF FIRE MARSHAL, BUILDING AND ELECTRICAL PLANS | | | EXAMINERS. | | | | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-02-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-19 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-19 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2009-02-19 13:37:01 | ** DENIED SECOND REVIEW ** | | | | | | ** PLEASE SEE NOTES BELOW AS THEY ARE EXACT COMMENTS | | | FROM PREVIOUS REVIEW. | | | | | | | | | | | | 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS WERE | | | SUBMITTED MEETING PRESCRIPTIVE REQUIREMENTS. 13-415.2, | | | 13-415.2.ABC.1.1,.1.2,.1.3 ETC | | | THIS WAS GONE OVER AT LENGTH IN MEETING HELD WITH | | | DESIGNER FROM FIRM YET THE PLANS ARE RESUBMITTED WITH | | | NO CALCULATIONS. | | | | | | 2) NOTE: PLANS STILL DO NOT SHOW ANY COMPLIANCE FOR | | | PRESCRIPTIVE REQUIREMENTS FOR NEW AREAS AND NEW | | | LIGHTING CONTROLS FOR SEPARATE SPACES. THIS COMMENT WAS | | | FOR NEW AREAS ONLY AND COMMENTS WERE GONE OVER WITH | | | DESIGNER FROM FIRM AT LENGTH. HOWEVER PLANS STILL ONLY | | | SHOW STANDARDS DEVICES AND NO COMPLIANCE FOR NEW IS | | | SHOWN. | | | 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | | | 3) NOTE: NO LETTER WAS SUBMITTED WITH RESPECT TO | | | REQUIRED LIGHTING FOR EGRESS OR OCCUPANCY NOT PERMITTED | | | WHEN UNDER EMERGENCY POWER. THIS WAS ALSO GONE OVER AT | | | LENGTH IN MEETING YET NO CHANGES IN PLANS OR STORE | | | OPERATIONS ARE PROVIDED. | | | | | | 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A | | | NOTICE GIVEN AT THIS TIME HOWEVER PLEASE SEE COMMENTS | | | ABOUT AS SOME SECTIONS HAVE NOW BEEN REAPEATED TWICE. | | | | | | 6) NOTE: THE RISER AS SHOWN DOES NOT INCLUDE THE MOST | | | RECENT ELECTRICAL REVISIONS AS MADE ON SITE WITH THE | | | MOST RECENT PERMITTED ELECTRICAL WORK. THIS WILL NEED | | | TO BE REVISED. | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-08-29 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-08-29 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2008-08-29 16:58:06 | ** DENIED * | | | | | | | | | 1) NOTE: PLEASE CONFIRM LICENSING OF THE FIRM AS | | | LISTED. THE CERTIFICATE OF AUTHORIZATION NUMBER SHOWN | | | IS LISTED FOR POST, BUCKLEY, SCHUH AND JERNIGAN, INC AT | | | A LOCATION OTHER THAN LISTED ON PLANS. THE FIRM NAME AS | | | LISTED ALONG WITH ADDRESS IS NOT LISTED ON STATE | | | WEBSITE. | | | PLEASE ALSO INDICATE THE ARCHITECTURAL FIRM LICENSE | | | NUMBER THE NUMBER AS LISTED DOES COME UP ON WEBSITE FOR | | | ENGINEERING FIRM HOWEVER NOT FOR ARCHITECTURAL | | | BUSINESS. | | | PLEASE SEE FS 471.023 (ENG) FS 481.219 (ARCH) AND FAC | | | 61G15-23.002, 61G1-16.004. | | | | | | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED | | | ON THE ELECTRICAL PLANS AS WELL AS CORRECTING COVER | | | SHEETS. | | | PLEASE SEE THE COVER SHEET AS IT STATES A 2004 NEC. YET | | | THERE IS NO SUCH CODE. | | | THE LIFE SAFETY PLAN HOWEVER DOES LIST THE 2005 NEC. | | | | | | 2004 FBC W/2007 REVISIONS. | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | 3) NOTE: PLEASE INDICATE THE REQUIRED BATTERY BACK UP | | | LIGHTING FOR EGRESS PATHS IN AREAS IN WHICH WORK IS | | | BEING DONE. AS THIS LOCATION IS A LOCATION IN WHICH | | | OCCUPANCY WILL OCCUR UNDER GENERATOR POWER IN ANY EVENT | | | OF POWER FAILURE BATTERY BACK UP LIGHTING FOR 1FT | | | CANDLE MINIMUM FOR EGRESS PATHS WILL BE REQUIRED. | | | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1, .2.2. | | | | | | ** NORMAL OCCUPANCY IS BEING PROPOSED IN THIS LOCATION | | | UNDER EMERGENCY POWER. IN THIS SITUATION LOSING THE | | | *EMERGENCY* BACK UP WOULD CAUSE ALL EGRESS AREAS TO | | | HAVE NO LIGHTING WHICH IS A LIFE SAFETY SITUATION. | | | | | | ** IF EGRESS LIGHTING IS CURRENTLY PROVIDED WITH | | | BATTERY BACK UP MEETING THE LIFE SAFETY CODE IN ANY | | | AREAS, PLEASE INDICATE. | | | AT THIS TIME NO KNOWN BATTERY BACK UP POWER FOR MAIN | | | AREAS ARE KNOWN TO BE BATTERY BACK UP. | | | | | | 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | | CALCULATIONS IN AREAS IN WHICH NEW LIGHTING IS BEING | | | INSTALLED. | | | PLEASE SEE13-415.2.ABC.1.1, .1.2. | | | | | | 5) NOTE: PLEASE PROVIDE HOW LIGHTING CONTROLS FOR NEW | | | BEING INSTALLED MEET SECTIONS 13-415.1.ABC.1.1,.1.2 AND | | | .1.3. | | | | | | 6) NOTE: PLEASE SEE OWNER INFORMATION ON PERMIT | | | APPLICATION DOES NOT COORDINATE WITH THE PALM BEACH | | | COUNTY PROPERTY APPRAISER OWNER OF RECORD INFORMATION. | | | | | | 7) NOTE: PLEASE UPDATE ELECTRICAL RISER WITH THE LATEST | | | PERMITTED WORK FOR BACK UP GENERATOR ETC. | | | 230, 240, 310, ETC | | | ** THE EXISTING RISER IS NOT REVIEWED FOR CODE | | | COMPLIANCE. | | | | | | 8) NOTE: PLEASE PROVIDE INFORMATION ON WHETHER OR NOT | | | THE CONTINUOUS LOADS ARE FIGURED AT 125% 215.3,230.42 | | | ETC. | | | 220.87 | | | | | | 9) NOTE: PLEASE BE SURE THE CIRCUITS ARE SPECIFIC TO | | | ROOMS AND AREAS IN WHICH THEY FEED. THIS NOTE IS FOR | | | NEW. PLEASE SEE 408.4 WHICH DOES NOT ACCEPT | | | *RECEPTACLES* OR *LIGHTING* AS GENERAL NOTATIONS. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-04-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-27 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-27 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2009-04-27 08:49:55 | FIRE REVIEW OK, SHEETS STAMPED, WILL REVISE LS AND A | | | SHEETS TO COORDINATE FOR EXIT SIGNS BEFORE INSPECTIONS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2009-04-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-04-06 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-06 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2009-04-06 12:11:34 | *****PROVISO***** | | | | | | PLAN SHEETS FP-1, FA-1 & FA-2 WERE PREVIOUSLY | | | FIRE-STAMPED ON 02/26/09; SHEETS LS-1, A-2, AND A-4 | | | WERE STAMPED, INITIALED, AND DATED. PLAN SHEET E-2 TO | | | BE FIRE-STAMPED WHEN THE ELECTRICAL EXAMINER'S COMMENTS | | | AS WELL AS THE BELOW COMMENT HAS BEEN ADDRESSED: | | | | | | 1. IN THE LOWER RIGHT HAND CORNER OF THE FLOOR PLAN, AN | | | EXIT LIGHT IS SHOWN FOR THE DOOR ON SHEET E-2, BUT IS | | | NOT SHOWN ON SHEET LS-1 AND A-2. PLEASE CORRELATE | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-02-26 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-02-26 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-02-26 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-09-19 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-09-19 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-09-19 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2008-09-19 15:29:49 | ***DENIED*** | | | | | | 1) BUILDING CODE ANALYSIS INDICATES NFPA, 2003 EDITION. | | | LIST SPECIFIC NFPA STANDARD. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) BUILDING CODE ANALYSIS LISTS PROJECT AS EXISTING | | | MERCANTILE. SECTION 7.4.1.2 APPLIES TO MEANS OF EGRESS | | | OTHER THAN EXISTING BUILDINGS. | | | | | | 4) EXIT SIGNS SHALL BE PROVIDED AT DISTANCES NOT TO | | | EXCEED 100'. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 6) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR | | | HOOD/SUPPRESSION SYSTEM. | | | | | | 7) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 8) CLARIFY SCOPE OF WORK REGARDING FIRE ALARM SYSTEM | | | AND SHOW ALL EQUIPMENT. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2009-04-27 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-04-27 |
Time |
19:51 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-04-27 |
Time |
19:51 |
Sent To |
|
|
| Notes |
| 2009-04-27 19:51:39 | GAS UNDER SEPERATE PERMIT AND REVIEW. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2009-04-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-02 |
Time |
18:15 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-02 |
Time |
18:15 |
Sent To |
|
|
| Notes |
| 2009-04-02 18:26:29 | DENIED | | | REFERENCE: | | | FBC-2004 FUEL GAS | | | NFPA-58 | | | | | | A. SHT P-3 & P-4 FIGURE I.1(B) NOTE 1. REGARDLESS OF | | | ITS SIZE, ANY ASME CONTAINER FILLED ON SITE MUST BE | | | LOCATED SO THAT THE FILLING CONNECTION AND FIXED | | | MAXIMUM LIQUID LEVEL GAUGE ARE AT LEAST 10 FT FROM ANY | | | EXTERNAL SOURCE OF IGNITION. SEE TABLE 6.3.9. TANK IS A | | | MAXIMUM 7 FT TO THE FAR SIDE OF THE GENERATOR. | | | | | | B. SUBMIT THE FOLLOWING INFORMATION FOR THE SEPARATE | | | GAS PERMIT REQUIRED: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. - ALSO SHOW THE AUTOMATIC | | | TRANSFER VALVE AND SHUT OFF VALES. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | 4. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 5. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | 7. INDICATE THE BTU LOAD OF THE EXISTING GENERATOR THAT | | | WILL BE REMOVED. | | | | | | 8. SUBMIT MANUF. SPECIFICATIONS FOR THE AUTOMATIC | | | TRANSFER VALVE THAT SWITCHES THE GENERATOR FROM LP GAS | | | TO NATURAL GAS. | | | | | | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHTS PHM-001 THRU PHM-016. A TITLE BLOCK SHALL BE | | | USED ON EACH SHEET CONTAINING THE PRINTED NAME, ADDRESS | | | AND LICENSE NUMBER OF THE ENGINEER OR IF APPLICABLE, | | | THE NAME AND LICENSE NUMBER OF THE ENGINEER, AND IF | | | PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING | | | BUSINESS, THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS. FAC | | | 61G15-23.002(2) & FS 471.025. | | | | | | 2. ALL SHTS WITH MOFFATT & NICHOL TITLE BLOCKS. THE | | | ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE, | | | (3780 KILROY AIRPORT WAY LONG BEACH CALIFORNIA), DOES | | | NOT REFLECT THE ADDRESS IN THE TITLE BLOCKS, (1509 W. | | | SWANN AVE. TAMPA FLORIDA). FAC 61G15-23.002(2) & FS | | | 471.025. PLEASE UPDATE TITLE BLOCKS OR THE DBPR WEBSITE | | | PRIOR TO RESUBMITTING TO THE CITY WPB FOR REVIEW. (THE | | | ADDRESS ON THE DBPR WEBSITE CAN BE ADDED TO THE TITLE | | | BLOCK OF EACH SHEET TO COMPLY WITH THIS REQUIREMENT). | | | | | | 3. SHT G-003 CODE DESIGN CRITERIA SHALL INCLUDE THE | | | FBC-2004 WITH 2007 REVISIONS. SECTION 106.1.1. | | | | | | 4. THE WATER SUPPLY TO THE DOCKS SHALL BE PROTECTED | | | FROM BACKFLOW PER SECTION 608.13.2. PLEASE INDICATE THE | | | RPZV BACKFLOW LOCATION FOR EACH DOCK OR IF ALL DOCKS | | | ARE CONNECTED TO ONE METER INDICATE ON PLANS THE | | | LOCATION. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-06-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-06-24 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-06-24 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2009-06-24 10:08:09 | SENT TO RON REGUEIRO'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-04-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-04-03 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-04-03 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2009-04-03 11:13:08 | TO "C27" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-29 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-29 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2009-01-29 09:02:49 | TO "COMM" BD#39 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-09-19 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-09-19 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-08-21 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2008-08-21 11:01:49 | TO "COMM" BD#34 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-07-01 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-07-01 |
Time |
21:11 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-07-01 |
Time |
21:11 |
Sent To |
PC |
|
| Notes |
| 2009-07-01 21:12:48 | REVIEWED REVISED SHEETS M-1 THROUGH M-5 INCLUSIVE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-02-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-22 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-22 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2009-02-22 13:21:10 | ******PROVISO****** | | | PROVIDE SUPPORTING DOCUMENTATION FROM APPLIANCE | | | MANUFACTURER SHOWING NEW AC-1 AND AC-2 ARE DESIGNED TO | | | RESIST ANTICIPATED WIND PRESSURES IN ACCORDANCE WITH | | | FBC-M 301.13. SUCH DATA SHALL BE SUBMITTED FOR PLAN | | | REVIEW PRIOR TO FINAL INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-09-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-09-03 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-09-02 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2008-09-03 16:06:55 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. STRUCTURAL PLANS SHOW A DETAIL FOR NEW CONDENSER #8. | | | THE HEIGHT OF THE CONDENSER ABOVE THE ROOF SURFACE IS | | | NOT SHOWN ON THE PAGE S-2 DETAILS. SHOW THE MINIMUM | | | REQUIRED CLEARANCE FROM THE ROOF SURFACE ON THE PLANS | | | IN ACCORDANCE WITH FBCB TABLE 1509.7. | | | | | | 2. PAGE S-2 GENERAL NOTE #6 CALLS FOR DETAIL SHOWING | | | HOW THE APPLIANCE IS TO BE ATTACHED TO THE STAND TO | | | MEET WIND RESISTANCE REQUIREMENTS. NO SUCH DETAIL OR | | | SHOP DRAWING WAS PROVIDED. PROVIDE MISSING INFORMATION | | | TO DEMONSTRATE COMPLIANCE WITH THE WIND RESISTANCE | | | REQUIREMENTS OF FBCM 301.13 FOR ATTACHMENT TO THE | | | STRUCTURE. | | | | | | 3. IN ADDITION TO THE ABOVE REQUIREMENTS, PROVIDE | | | DOCUMENTATION FROM THE MANUFACTURER OF CONDENSER #8 | | | SHOWING THAT THE APPLIANCE ITSELF IS DESIGNED TO RESIST | | | WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13. | | | | | | 4. PAGE M-3 NOTE ON ROOF PLAN INDICATES THAT THE NEW | | | AC-1 AND NEW AC-2 WILL FIT ON THE EXISTING ROOF CURB. | | | HOWEVER, DETAIL 7 ON PAGE M-4 CALLS FOR A CURB ADAPTER | | | FOR NEW AC UNITS. WHICH IS CORRECT? PLEASE CLARIFY IN | | | ACCORDANCE WITH FBCB 106.1.1. ADJUST ATTACHMENT DETAIL | | | AND NOTES SO PLANS ARE COORDINATED AND SHOW AN | | | ATTACHMENT DETAIL WHICH IS IN COMPLIANCE WITH FBCM | | | 301.13. | | | | | | 5. PROVIDE DOCUMENTATION FROM THE MANUFACTURER OF AC-1 | | | AND AC-2 SHOWING THESE APPLIANCES ARE DESIGNED TO | | | RESIST WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13. | | | | | | 6. PAGE M-4: DETAIL #8 SHOWS GALVANIZED STRAPS OVER F-6 | | | TO SECURE THE FAN FOR WIND LOADS. THIS FAN IS AN | | | UPBLAST FAN, NOT A DOWN DISCHARGE FAN AS SHOWN IN THIS | | | DETAIL. STRAPS OVER AN UPBLAST GREASE EXHAUST FAN WILL | | | ACCUMULATE GREASE AND DIVERT IT TO LOCATIONS OTHER THAN | | | THE GREASE RESERVOIR SUPPLIED WITH THE FAN. THIS HAS | | | THE POTENTIAL TO CREATE AN ADDITIONAL FIRE HAZARD ON | | | THE ROOF. IT IS ALSO UNCLEAR HOW THESE STRAPS WILL | | | INTERACT WITH THE HINGE MECHANISM ON THE GREASE EXHAUST | | | FAN AS REQUIRED IN ACCORDANCE WITH FBCM 506.5.3. | | | NOTE: THERE ARE GREASE EXHAUST FANS AND CURBS WHICH ARE | | | DESIGNED TO RESIST WIND PRESSURES WITHOUT THE USE OF | | | ADDITIONAL, FIELD INSTALLED STRAPPING WHICH WILL AVOID | | | INTERFERENCE WITH GREASE EXHAUST DISCHARGE. THIS MAY BE | | | A PREFERABLE (TO THE DESIGN PROFESSIONAL OR OWNER) | | | MEANS OF ACCOMPLISHING COMPLIANCE WITH THESE CODE | | | PROVISIONS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-04-27 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-04-27 |
Time |
19:42 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-04-27 |
Time |
19:42 |
Sent To |
PC |
|
| Notes |
| 2009-04-27 19:42:58 | ALL GAS AND FUEL TO BE BY SEPERATE PERMIT AND NOT | | | INCLUDED IN THE SCOPE OF THIS PERMIT OR REVIEW. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-03-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-03 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-03 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-08-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-25 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-25 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2008-08-25 16:58:04 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS THE TITLE BLOCK SHALL CONTAIN THE PRINTED | | | NAME, ADDRESS, AND LICENSE NUMBER OF THE ENGINEER. THE | | | ADDRESS DOES NOT REFLECT THE ADDRESS OF RECORD ON THE | | | STATE OF FLORIDA, DBPR WEBSITE. PLEASE UPDATE THE | | | WEBSITE OR THE TITLE BLOCKS TO REFLECT EACH OTHER PRIOR | | | TO RESUBMITTING FOR REVIEW AT THE CITY WPB. FAC | | | 61G15-23.002(2) & FS 471.025. | | | | | | 2. SHT P-3 THREE LINES TO TWO CD-1 AND ONE CD-2 SHALL | | | CONNECT TO THE VENTED HORIZONTAL DRAIN LINE, NOT THE | | | FIXTURE DRAIN LINE FROM ANOTHER FIXTURE. SECTION | | | 912.2.4. | | | | | | 3. SHT P-3 NEW SINK P-12 NOT INDICATED ON THE PLUMBING | | | FIXTURE SHOWN ON SHEET P-7. PLEASE CORRELATE. SECTION | | | 106.1.1. | | | | | | 4. SHT P-5 TWO CD-1 AND ONE CD-2 SHALL CONNECT TO THE | | | VENTED HORIZONTAL DRAIN LINE, NOT THE FIXTURE DRAIN | | | LINE FROM ANOTHER FIXTURE. SECTION 912.2.4. | | | | | | 5. SHT P-5 TWO CD-1 SHOW NO TRAPS. THIS DOES NOT | | | CORRELATE WITH THE FLOOR DRAIN, CLEAN OUTS, ETC. | | | SCHEDULE ON SHT P-7 WHICH INDICATES THAT THE CD-1 4" | | | CASE DRAINS HAVE A P-TRAP. PLEASE CLARIFY & CORRELATE. | | | SECTIONS 106.1.1 & 1002.1. | | | | | | 6. SHT P-7 FOOD PREPARATION SINK DETAIL SHOW A 2" AIR | | | GAP. PER SECTION 802.2.1 THE MINIMUM AIR GAP SHALL BE | | | MINIMUM TWICE THE EFFECTIVE OPENING OF THE INDIRECT | | | WASTE PIPI. THE INDIRECT WASTE PIPE IS SHOWN AS 1-1/2". | | | MINIMUM 3" AIR GAP REQUIRED. | | | | | | 7. SHT P-7 WATER FILTER DETAIL. THE WATER FILTER MUST | | | MEET THE REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF. | | | SPECIFICATIONS SHOWING COMPLIANCE. SECTION 611.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|