Plan Review Details - Permit 08080394
Plan Review Stops For Permit 08080394
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 14:41 Rev Time 0.00
Received By tgordon Date 2008-08-18 Time 16:17 Sent To  
Notes
2008-08-18 16:17:13WAITING FOR "BOB" W/MASTER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 14:28 Rev Time 0.45
Received By tgordon Date 2008-08-26 Time 14:28 Sent To  
Notes
2008-08-26 14:32:29*** PROVISO ***
 1)IN REGARDS TO THE A/C UNIT. PER 2004 FBC/R M1305.1
 APPLIANCE ACCESS FOR INSPECTION SERVICE, REPAIR AND
 REPLACEMENT.
 APPLIANCES SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE,
 REPAIR AND REPLACEMENT WITHOUT REMOVING PERMANENT
 CONSTRUCTION. THIRTY INCHES OF WORKING SPACE SHALL BE
 PROVIDED IN FRONT OF THE CONTROL SIDE TO SERVICE AN
 APPLIANCE.
 2) PROVIDE FOR RETURN AIR TO BEDROOMS, PER 2004 FBC/R
 M1602.4.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729