| 2008-08-20 11:17:41 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-2 DETAIL 1, ELEVATIONS: PLEASE DELETE THE |
| | FOLLOWING "19" MAX CLEAR AREA UNDERNEATH SINK IS |
| | AVAILABLE UPON REMOVAL OF BASE CAB DOORS" FROM THIS |
| | DETAIL. PLEASE KNOW THAT THERE ARE NO EXCEPTIONS BEING |
| | INDICATED IN THE CODE AS INDICATED ON PLAN SHEET. |
| | PLEASE KNOW THAT THIS IS NOT COMPLIANT TO THE FBC-2004 |
| | CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION |
| | 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR |
| | SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE |
| | SINK. |
| | |
| | 2. SHEET P-1 WATER ISOMETRIC: CLEARLY INDICATE THE |
| | FOLLOWING COMPLIANT WITH THE FBC-2004 PLUMBING CODE |
| | SECTIONS. |
| | |
| | A} POTABLE WATER SUPPLY TO THE ICE MAKER AND COFFEE |
| | MAKER. PER SECTION 601.1 SCOPE. |
| | |
| | B} SHUT OFF VALVES FOR THE ICE MAKER AND COFFEE MAKER. |
| | PER SECTION 602.2 (3) LOCATION OF SHUT OFF VALVES. |
| | |
| | C} THE REQUIRED WATER HAMMER ARRESTORS FOR THE POTABLE |
| | WATER SUPPLY TO THE REFRIGERATOR ICE MAKER AND COFFEE |
| | MAKER. PER SECTION 604.9 WATER HAMMER. A WATER-HAMMER |
| | ARRESTOR SHALL BE INSTALLED WHERE QUICK CLOSING VALVES |
| | ARE UTILIZED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |