Plan Review Details - Permit 08080277
Plan Review Stops For Permit 08080277
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-01 Cont ID  
Sent By jwitmer Date 2008-10-01 Time 14:34 Rev Time 1.77
Received By jwitmer Date 2008-10-01 Time 14:34 Sent To ENG
Notes
2008-10-01 14:52:56 
 ** BUILDING PLAN REVIEW**
 PERMIT: 08080277
 ADD: 1505 N AUSTRALIAN AVE
 CONT: BRADANNA INC.
 TEL: (239)455-8891
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 FOUNDATION REVIEW
 ACTION: REVIEWED
  
  
 BUILDING PROVISOS:
  
 1) 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO
 MEET THE PROVISIONS OF THE TECHNICAL CODE.
  
 2) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 3) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By jwitmer Date 2008-08-27 Time 10:24 Rev Time 2.22
Received By jwitmer Date 2008-08-27 Time 10:24 Sent To  
Notes
2008-08-27 10:52:54BUILDING PLAN REVIEW
 PERMIT: 08080277
 ADD: 1505 N AUSTRALIAN AVE
 CONT: (PLAN REVIEW)
  
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 NOTE : PLANS APPEAR TO BE CODE COMPLIANT, BUT NO PERMIT
 APPLICATION HAS BEEN MADE WITH CONTRACTOR SIGNED ON NOR
 CAN RADON FEES BE ASSESSED UNTIL A PERMIT APPLICATION
 HAS BEEN MADE.
  
 NOTE: MISSING ELECTRICAL SHEET FOR BONDING REQUIREMENTS
 WILL BE ADDRESSED BY THE ELECTRICAL PLAN REVIEWER..
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-10-20 Cont ID  
Sent By dpalmer Date 2008-10-20 Time 10:26 Rev Time 0.00
Received By dpalmer Date 2008-10-20 Time 10:26 Sent To PC
Notes
2008-10-20 10:26:51** DENIED REVISION**
  
  
  
  
 1) NOTE: PLEASE SUBMIT THE ELECTRICAL TEMPORARY SERVICE
 PLANS UNDER AN ELECTRICAL PERMIT APPLICATION. THIS CAN
 NOT BE A REVISION TO THE BUILDING CONTRACTOR FOUNDATION
 PERMIT.
  
 2) NOTE: PLEASE SEE 250.66 FOR THE CORRECT SIZING OF
 THE GROUNDING ELECTRODE CONDUCTOR.
  
 3) NOTE: PLEASE COMPLETE RISER WITH ALL CONDUCTORS
 INCLUDING ALL CONDUCTORS FROM WHAT APPEARS TO BE A
 GUTTER. THE BOX ABOVE MAY OR MAY NOT BE A GUTTER??
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-30 Cont ID  
Sent By dpalmer Date 2008-09-30 Time 13:27 Rev Time 0.00
Received By dpalmer Date 2008-09-30 Time 13:27 Sent To  
Notes
2008-09-30 13:28:25** FOR INSTALLATION OF GROUNDING ELECTRODE SYSTEM AND
 FOUNDATION/SLAB CONDUITS ONLY.
  
 ** ELECTRICAL SUB PERMIT REQUIRED ONCE THIS PERMIT IS
 ISSUED FOR ELECTRICAL SCOPE OF WORK AS NOTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By dpalmer Date 2008-08-27 Time 16:48 Rev Time 0.00
Received By dpalmer Date 2008-08-27 Time 16:48 Sent To  
Notes
2008-08-27 16:48:22**DENIED**
  
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR PLAN REVIEW AND NOT
 FOR PERMIT APPLICATION.
  
 2) NOTE: PLEASE SUBMIT ALL ELECTRICAL WHICH MAY BE PART
 OF THE SLAB/FOUNDATION. PLEASE SEE 250.50 AS THE
 MINIMUM IS REQUIRED FOR THE GROUNDING ELECTRODE SYSTEM.
 PLEASE SUBMIT THE GROUNDING ELECTRODE RISER FOR
 FOUNDATION WORK.
 PLEASE SUBMIT CONDUIT LAYOUT AND SIZES FOR ANY PROPOSED
 WORK WHICH MAY BE PART OF FOUNDATION.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-10-02 Cont ID  
Sent By dlauderm Date 2008-10-02 Time 15:33 Rev Time 0.00
Received By dlauderm Date 2008-10-01 Time 11:40 Sent To  
Notes
2008-10-02 15:34:54PASSED. ALL ITEMS IN PREVIOUS REVIEWS HAVE BEEN MET.
 DSL

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By rchokshi Date 2008-08-27 Time 14:37 Rev Time 0.00
Received By rchokshi Date 2008-08-27 Time 14:21 Sent To  
Notes
2008-08-27 14:37:38FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW ON DRAWINGS THETURBIDITY BARRIER ON
 NORTH SIDE OF THE SITE,ALONG THE CANAL.ALSO PLEASE
 SHOW SILT FENCE ON EAST SIDE OF SITE.
  
 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
 STORM WATER CALS MUST BE APPROVED FROM 1000 45TH ST
 ENGINEERING.
  
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS AFTER THEY ARE
 APPROVED FROM 1000 45TH ST ENGINEERING.
  
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS AFTER THEY
 ARE APPROVED FROM 100045TH STREET ENGINEERING
 SERVICES BEFORE WE ISSUE A PERMIT.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL WITH DRAWING
 REFERENCE #TO EXPEDITE YOUR PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-30 Cont ID  
Sent By mwennerg Date 2008-09-30 Time 14:29 Rev Time 0.00
Received By mwennerg Date 2008-09-30 Time 14:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-29 Cont ID  
Sent By mwennerg Date 2008-08-29 Time 15:57 Rev Time 0.00
Received By mwennerg Date 2008-08-29 Time 15:56 Sent To  
Notes
2008-08-29 16:00:32FOR PLAN REVIEW ONLY
  
 FOUNDATION
  
 ***DENIED***
  
 1) NO FIRE LINES PERMITTED BENEATH FOUNDATION, SLAB
 ETC.
  
 2) CODE REFERENCE #4 SHOULD READ FLORIDA FIRE
 PREVENTION CODE, 2004. NFPA 101, 2003 IS CORRECTLY
 IDENTIFIED IN NOTE #3.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE PREVENTION
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-15 Cont ID  
Sent By adarroug Date 2008-10-15 Time 09:55 Rev Time 0.00
Received By adarroug Date 2008-10-15 Time 09:55 Sent To E
Notes
2008-10-15 09:55:35TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-08 Cont ID  
Sent By mmiller Date 2008-10-08 Time 14:46 Rev Time 0.00
Received By mmiller Date 2008-10-08 Time 14:46 Sent To P
Notes
2008-10-08 14:46:38ROUTED TO KEN STEVEN'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 09:06 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 09:06 Sent To  
Notes
2008-09-26 09:17:03TO "COMM" BD#25/PLANS ON RACK/LARGE FOLDED
 PLANS--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-29 Cont ID  
Sent By mwennerg Date 2008-08-29 Time 16:03 Rev Time 0.00
Received By mwennerg Date 2008-08-13 Time 11:13 Sent To  
Notes
2008-08-13 11:13:22TO "COMM" BD#16--EXPEDITED--

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-08 Cont ID  
Sent By kstevens Date 2008-10-08 Time 16:50 Rev Time 0.00
Received By kstevens Date 2008-10-08 Time 16:50 Sent To  
Notes
2008-10-08 16:51:19PLUMBING REVISIONS OK -- SHTS P-2, P-4 & P-5

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-08-14 Cont ID  
Sent By kstevens Date 2008-08-14 Time 12:04 Rev Time 0.00
Received By kstevens Date 2008-08-14 Time 12:04 Sent To  
Notes
2008-08-14 12:05:08NO PLUMBING PLANS SUBMITTED--CONTRACTOR TO PROCEED
 AT OWN RISK

Review Stop Z ZONING
Rev No 1 Status P Date 2008-08-15 Cont ID  
Sent By adavila Date 2008-08-15 Time 11:16 Rev Time 0.00
Received By adavila Date 2008-08-15 Time 11:16 Sent To  
Notes
2008-08-15 11:17:02PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  