Plan Review Details - Permit 08080268
Plan Review Stops For Permit 08080268
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-21 Cont ID  
Sent By amorse Date 2008-10-21 Time 13:48 Rev Time 1.00
Received By amorse Date 2008-10-21 Time 13:48 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-21 Cont ID  
Sent By amorse Date 2008-08-21 Time 16:30 Rev Time 0.00
Received By amorse Date 2008-08-21 Time 16:30 Sent To PC
Notes
2008-08-21 17:00:17 
  
 DENIED
  
 1) )THE CLAIMED VALUATION ON THE PERMIT APPLICATION
 IS LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 3)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORGPRODUCT
 APPROVALS ARE REQUIRED FOR NEW WINDOWS AND FRAMING
 STRAPS/CONNECTORS
  
 4)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 5)OWNER BUILDER EXEMPTION CANNOT BE CLAIMED FOR
 PROPERTY THAT IS RENTED OR LEASED. THIS OWNER HAS THREE
 RENTAL UNITS ON THIS PROPERTY AND IT IS DESIGNATED AS
 MULTIFAMILY. PLEASE FILL OUT A CHANGE OF CONTRACTOR
 FORM AND HAVE A LICENSED CONTRACTOR PERFORM THE WORK.
  
 6)ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING,
 ELECTRICAL
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-09 Cont ID  
Sent By btrobaug Date 2008-10-09 Time 09:16 Rev Time 0.00
Received By btrobaug Date 2008-10-09 Time 08:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-08-20 Cont ID  
Sent By btrobaug Date 2008-08-20 Time 12:14 Rev Time 0.00
Received By btrobaug Date 2008-08-20 Time 09:32 Sent To P
Notes
2008-08-20 12:14:08 
  
  
  
 PROVISO
  
 210.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS
 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE.

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-10-14 Cont ID  
Sent By mperson Date 2008-10-14 Time 13:22 Rev Time 0.00
Received By mperson Date 2008-10-14 Time 13:22 Sent To B
Notes
2008-10-14 13:24:19CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-08-20 Cont ID  
Sent By mperson Date 2008-08-20 Time 14:03 Rev Time 0.00
Received By mperson Date 2008-08-20 Time 14:03 Sent To B
Notes
2008-08-20 14:33:59GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 NOTE: PERMIT APPLICATION INDICATES GAS LINE.
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS. PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 3. INDICATE THE TYPE OF GAS, (LP OR NATURAL) BEING
 USED. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 UNDILUTED PROPANE (LP) SPECIFY 11.0 INCH WC OR 10 PSI.
  
 7. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 8. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-07 Cont ID  
Sent By adarroug Date 2008-10-07 Time 12:54 Rev Time 0.00
Received By adarroug Date 2008-10-07 Time 12:54 Sent To E
Notes
2008-10-07 12:55:31TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-08-21 Time   Rev Time 0.00
Received By adarroug Date 2008-08-13 Time 09:53 Sent To  
Notes
2008-08-13 09:53:37TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-08-14 Cont ID  
Sent By tgordon Date 2008-08-14 Time 09:31 Rev Time 0.15
Received By tgordon Date 2008-08-14 Time 09:31 Sent To E
Notes
2008-08-14 09:32:21NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-14 Cont ID  
Sent By mperson Date 2008-10-14 Time 13:21 Rev Time 0.30
Received By mperson Date 2008-10-14 Time 13:21 Sent To G
Notes
2008-10-14 13:25:41NOTE: PLANS INDICATE EXACT FIXTURE CHANGE OUT OF
 KITCHEN SINK W/DISPOSAL AND DISHWASHER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-08-20 Cont ID  
Sent By mperson Date 2008-08-20 Time 14:00 Rev Time 0.00
Received By mperson Date 2008-08-20 Time 14:00 Sent To G
Notes
2008-08-20 14:02:53NOTE: PLANS INDICATE EXACT FIXTURE CHANGE OUT OF
 KITCHEN SINK W/DISPOSAL AND DISHWASHER.

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***