| Plan Review Stops For Permit 08080248 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-12-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-02 |
Time |
15:22 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-12-02 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-10-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-24 |
Time |
16:39 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-10-24 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2008-10-24 16:41:42 | BUILDING PLAN REVIEW | | | PERMIT: 08080248 | | | ADD: 314 CLEMATIS ST | | | CONT: GOLDEN SANDS | | | TEL: (305)633-3336 | | | | | | OCT 24,2008 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE AND REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. THE REMOVED SHEETS BIND TOGETHER AND MARK | | | OLD SHEETS | | | | | | 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, | | | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: | | | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-08-29 |
Time |
15:34 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-08-29 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2008-08-29 16:02:29 | BUILDING PLAN REVIEW | | | PERMIT: 08080248 | | | ADD: 314 CLEMATIS ST | | | CONT: GOLDEN SANDS | | | TEL: (305)633-3336 | | | | | | AUGUST 29,2008 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, | | | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: | | | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS AND THE | | | 2004 EXISTING BUILDING CODE WITH 2007 SUPPLEMENTS | | | PLEASE CORRECT PLANS. | | | | | | 2) 2004 EXISTING BUILDING CODE, 301.5. THE DESIGN | | | PROFESSIONAL MUST ELECT ONE OFTHE LEVELS OF ALTERATION | | | PURSUANT TO 303, 304 AND 305 OF THIS CODE. | | | | | | 3) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE | | | 2 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS | | | ARE AS FOLLOWS: | | | 3A) EXTERIOR METAL DOOR | | | | | | 4) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 5) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 6) INFORMATIONAL ONLY: FABRIC AWNING TO REQUIRE A | | | SEPERATE PERMIT DESIGN CRITERIA TO MEET THE FOLLOWING | | | 3105.4.2. NOTE THE FOLLOWING INFORMATION, A LETTER FROM | | | THE OWNER (NOT TENANT) IS TO ACCOMPANY ALL FABRIC OR | | | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK | | | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO ACKNOWLEDGE | | | THEIR RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED | | | PRIOR TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF | | | 75 MPH OR GREATER. THE LETTER MUST BE SIGNED BY THE | | | OWNER NOT TENANT. | | | 3105.4.2.1 THE WIND DESIGN LOADS FOR ANY FABRIC OR | | | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK | | | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND | | | VELOCITIES OF 75 MPH,. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-12-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-16 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-16 |
Time |
16:30 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-12-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-01 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-01 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2008-12-01 10:00:50 | | | | ** TEMPORARY FAILED 3RD REVIEW ** | | | | | | | | | | | | | | | 1) NOTE: LIGHTING CONTROLS PER 13-415.1.ABC.1.1,.1.2 | | | NOT ADDRESSED. | | | CALLED ARCHITECT MR. JAMES HEIL. HE MENTIONED NEW PLANS | | | WERE SENT VIA FED EX LAST WEDNESDAY TO THE CONTRACTOR. | | | NO NEW PLANS ARE IN SETS FOR ELECTRICAL. | | | | | | | | | | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-22 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-22 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2008-10-22 15:01:50 | | | | ** DENIED 2ND REVIEW** | | | | | | ** SOME NOTES FROM PREVIOUS REVIEW ARE STILL IN NEED OF | | | ADDRESSING. | | | | | | 1) NOTE: AS STATED ON PREVIOUS REVIEW. PLEASE DO NOT | | | LEAVE OLD/VOIDED SHEETS IN SETS. PLEASE REMOVE | | | COMPLETELY AND SET THE OLD SHEETS ASIDE INTO ONE SET. | | | THE NEW SETS OF PLANS WITH REVISED SHEETS SHOULD ONLY | | | CONTAIN NEW SHEETS WITH ANY SHEETS WHICH DID NOT NEED | | | TO BE REVISED. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO | | | LIGHTING CONTROLS PER 13-415.1.ABC.1.1, .1.2. PLANS | | | ONLY SHOW A STANDARD SINGLE POLE SWITCH. | | | | | | 3) NOTE: NO LOAD CALCULATIONS WERE SUBMITTED FOR THE | | | EXISTING PANEL HP WITH NEW LOADS BEING ADDED AS | | | PREVIOUSLY NOTED. | | | 220.87, 215.3,230.42 ETC. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-08-29 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-08-29 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2008-08-29 13:56:09 | | | | | | | | | | | | | | | | ** DENIED ** | | | | | | | | | | | | 1) NOTE: PLANS NEED TO INDICATE THE MINIMUM CODES AS | | | NOTED BELOW FOR DESIGN. | | | 2004 FBC W/ 2007 REVISONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR LOADS ON | | | EXISTING PANEL DP. PLEASE BE SURE ALL CONTINUOUS LOADS | | | ARE SHOWN AT 125%. | | | 220, 215.3, 230.42 ETC | | | | | | 3) NOTE: PLEASE INDICATE THE LIGHTING CONTROLS PER FBC | | | 13-415.1.ABC.1.1,.1.2. | | | | | | 4) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR NEW FEEDERS | | | PER 13-413.1ABC.1 | | | | | | 5) NOTE: PLEASE PROVIDE THE LIGHTING PERFORMANCE | | | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2. | | | | | | 6) NOTE: PLEASE SEE THAT PLANS, PANELS, RISER IS NOT | | | COMPLETE AS THE RISER CONTAINS NOTES FOR A NEW PANEL | | | *B* YET THE SUBMITTED PLANS DO NOT SHOW ANY NEW PANEL | | | *B*. NO PANEL SCHEDULE, NO INFORMATION ON RISER ETC. | | | PLEASE COMPLETE. | | | 215.5, 408.4, 240.4, 310.16 | | | FBC 106.3.5.1.2, 106.1.1 FOR CLARITY AND ADDITIONAL | | | INFORMATION. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-12-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-12-03 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-12-03 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2008-12-03 12:09:32 | *****APPROVED***** | | | | | | | | | PLAN SHEETS A00.30 & A04.01 WERE STAMPED, INITIALED, | | | AND DATED ON 12/03/2008. | | | | | | | | | *****RESTAMP***** | | | | | | PLAN SHEETS A00.30, A04.01, AND E2 (OF ONE PLAN SET) | | | WERE RSTAMPED, INITIALED, AND DATED ON 03/17/2009. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-10-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-10-29 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-10-29 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2008-10-29 13:46:28 | *****FIRE STAMPING NEEDED***** | | | | | | THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN | | | ADDRESSED; THE APPROPIATE PLAN SHEET(S) TO BE | | | FIRE-STAMPED WHEN THE OTHER PLAN EXAMINER'S COMMENTS | | | HAVE BEEN SATISFIED. | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-09-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-09-05 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-09-05 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2008-09-05 15:49:10 | *****DENIED***** | | | | | | | | | 1. ON SHEET A00.30 GENERAL NOTE #2, REPLACE NFPA 2003 | | | WITH NFPA 1 - 2003 AS AN REFERENCE. | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3. THE CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL | | | NOT HINDER OR INTERFERE WITH ACCESS TO OR EGRESS FROM | | | THE SUBJECT PROPERTYOR THE VICINITY THEREOF (INCLUDING | | | STREETS, ROADS, FIRE LANES, ETC.) . | | | | | | 4. SPECIFY THE NEW WALL AND CEILING INTERIOR FINISH IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-12-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-11 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-11 |
Time |
10:26 |
Sent To |
E |
|
| Notes |
| 2008-12-11 10:26:40 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-11-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-17 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-17 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2008-11-17 15:47:49 | TO "COMM" BD#18 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-10-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-16 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-16 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2008-10-21 09:48:04 | TO "COMM" BD#5 | | 2008-10-16 16:34:44 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-09-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-09-05 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-08-13 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2008-08-13 09:50:04 | TO "COMM" BD#14 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-11-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-10-25 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-10-25 |
Time |
16:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-27 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-27 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-27 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2008-08-27 11:30:21 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M1: REFRIGERANT LINES APPEAR TO BE PENETRATING | | | A FIRE RESISTANCE RATED FLOOR/CEILING ASSEMBLY. PROVIDE | | | A THROUGH-PENETRATION FIRESTOP SYSTEM W/ DETAIL FOR | | | PROTECTING PENETRATIONS OF RATED ASSEMBLIES IN | | | ACCORDANCE WITH FBCB SECTION 712. | | | | | | 2. PAGE M1: CONDENSING UNIT DETAIL CALLS FOR THE CU TO | | | BE MOUNTED ON PATE CURBS BUT THERE IS ALSO A PRODUCT | | | APPROVAL LISTED FOR A PRE-ENGINEERED A/C STAND. WHICH | | | IS TO BE USED? PLEASE CLARIFY AND DEMONSTRATE | | | COMPLIANCE WITH FBCM 304.10, 306.1 AND 306.5. | | | NOTE: IF THE PRE-ENGINEERED STAND IS USED, A PRODUCT | | | APPROVAL PACKAGE SHALL BE SUBMITTED WITH THE PERMIT | | | APPLICATION. THE PRODUCT APPROVAL SHALL BE APPROVED IN | | | WRITING (A SIGNED SHOP DRAWING REVIEW STAMP IS | | | SUFFICIENT) BY THE DESIGN PROFESSIONAL IN ACCORDANCE | | | WITH FBCB 106.3.3. | | | | | | 3. PAGE M1: CONDENSATE DRAIN TRAP DETAIL DOES NOT | | | CORRESPOND WITH MANUFACTURER?S INSTALLATION | | | INSTRUCTIONS. CONDENSATE DRAINS SHALL BE TRAPPED AS | | | REQUIRED BY THE EQUIPMENT OR APPLIANCE MANUFACTURER IN | | | ACCORDANCE WITH FBCM 307.2.4. A COPY OF THE CONDENSATE | | | PIPING INSTRUCTIONS IS ATTACHED TO THESE COMMENTS FOR | | | REFERENCE. PROVIDE A DETAIL WHICH CORRESPONDS WITH THE | | | MANUFACTURER?S INSTRUCTIONS ON THE PLANS OR REMOVE ANY | | | CONFLICTING INFORMATION FROM THE PLANS. | | | | | | 4. SHOW THE ACTUAL LOCATION OF CONDENSATE DISPOSAL ON | | | THE PLANS. CONDENSATE FROM ALL COOLING COILS AND | | | EVAPORATORS SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET | | | TO AN APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL NOT | | | DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO | | | CAUSE A NUISANCE IN ACCORDANCE WITH FBCM 307.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-10-27 |
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2008-10-27 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2008-10-27 14:04:35 | PROVISO:SIGNAGE AND AWNING NOT INCLUDED UNDER APPROVED | | | PERMIT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-08-26 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2008-08-26 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2008-08-26 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2008-08-26 15:27:30 | 1. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE | | | WITH 80% FRONTAGE REQUIREMENT. | | | 2. PROPOSED CANVAS AWNING IS NOT CONSISTENT WITH | | | BUILDING DESIGN. PLEASE CONTACT ANA MARIA APONTE | | | (561-822-1439) TO DISCUSS ALTERNATIVES. | | | 3. PLEASE PROVIDE INFORMATION REGARDING PROPOSED SIGN, | | | AND CONFIRM PROPOSED AND EXISTING SIGN WILL NOT EXCEED | | | MAXIMUM DIMESION ALLOWED FOR SIGNS. | | | 3. PLEASE PROVIDE INFORMATION TO CONFIRM REMOVED EXIT | | | IS NOT AN EMERGENCY EXIT. |
|
|