Plan Review Details - Permit 08080248
Plan Review Stops For Permit 08080248
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-02 Cont ID  
Sent By jwitmer Date 2008-12-02 Time 15:22 Rev Time 0.55
Received By jwitmer Date 2008-12-02 Time 15:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-24 Cont ID  
Sent By jwitmer Date 2008-10-24 Time 16:39 Rev Time 0.55
Received By jwitmer Date 2008-10-24 Time 16:39 Sent To  
Notes
2008-10-24 16:41:42BUILDING PLAN REVIEW
 PERMIT: 08080248
 ADD: 314 CLEMATIS ST
 CONT: GOLDEN SANDS
 TEL: (305)633-3336
  
 OCT 24,2008
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE AND REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION. THE REMOVED SHEETS BIND TOGETHER AND MARK
 OLD SHEETS
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-29 Cont ID  
Sent By jwitmer Date 2008-08-29 Time 15:34 Rev Time 2.22
Received By jwitmer Date 2008-08-29 Time 15:34 Sent To  
Notes
2008-08-29 16:02:29BUILDING PLAN REVIEW
 PERMIT: 08080248
 ADD: 314 CLEMATIS ST
 CONT: GOLDEN SANDS
 TEL: (305)633-3336
  
 AUGUST 29,2008
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS AND THE
 2004 EXISTING BUILDING CODE WITH 2007 SUPPLEMENTS
 PLEASE CORRECT PLANS.
  
 2) 2004 EXISTING BUILDING CODE, 301.5. THE DESIGN
 PROFESSIONAL MUST ELECT ONE OFTHE LEVELS OF ALTERATION
 PURSUANT TO 303, 304 AND 305 OF THIS CODE.
  
 3) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 3A) EXTERIOR METAL DOOR
  
 4) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) INFORMATIONAL ONLY: FABRIC AWNING TO REQUIRE A
 SEPERATE PERMIT DESIGN CRITERIA TO MEET THE FOLLOWING
 3105.4.2. NOTE THE FOLLOWING INFORMATION, A LETTER FROM
 THE OWNER (NOT TENANT) IS TO ACCOMPANY ALL FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO ACKNOWLEDGE
 THEIR RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED
 PRIOR TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF
 75 MPH OR GREATER. THE LETTER MUST BE SIGNED BY THE
 OWNER NOT TENANT.
 3105.4.2.1 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH,.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-12-16 Cont ID  
Sent By dpalmer Date 2008-12-16 Time 16:30 Rev Time 0.00
Received By dpalmer Date 2008-12-16 Time 16:30 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-01 Cont ID  
Sent By dpalmer Date 2008-12-01 Time 10:00 Rev Time 0.00
Received By dpalmer Date 2008-12-01 Time 10:00 Sent To  
Notes
2008-12-01 10:00:50 
 ** TEMPORARY FAILED 3RD REVIEW **
  
  
  
  
 1) NOTE: LIGHTING CONTROLS PER 13-415.1.ABC.1.1,.1.2
 NOT ADDRESSED.
 CALLED ARCHITECT MR. JAMES HEIL. HE MENTIONED NEW PLANS
 WERE SENT VIA FED EX LAST WEDNESDAY TO THE CONTRACTOR.
 NO NEW PLANS ARE IN SETS FOR ELECTRICAL.
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-22 Cont ID  
Sent By dpalmer Date 2008-10-22 Time 15:01 Rev Time 0.00
Received By dpalmer Date 2008-10-22 Time 15:01 Sent To  
Notes
2008-10-22 15:01:50 
 ** DENIED 2ND REVIEW**
  
 ** SOME NOTES FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING.
  
 1) NOTE: AS STATED ON PREVIOUS REVIEW. PLEASE DO NOT
 LEAVE OLD/VOIDED SHEETS IN SETS. PLEASE REMOVE
 COMPLETELY AND SET THE OLD SHEETS ASIDE INTO ONE SET.
 THE NEW SETS OF PLANS WITH REVISED SHEETS SHOULD ONLY
 CONTAIN NEW SHEETS WITH ANY SHEETS WHICH DID NOT NEED
 TO BE REVISED.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO
 LIGHTING CONTROLS PER 13-415.1.ABC.1.1, .1.2. PLANS
 ONLY SHOW A STANDARD SINGLE POLE SWITCH.
  
 3) NOTE: NO LOAD CALCULATIONS WERE SUBMITTED FOR THE
 EXISTING PANEL HP WITH NEW LOADS BEING ADDED AS
 PREVIOUSLY NOTED.
 220.87, 215.3,230.42 ETC.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-29 Cont ID  
Sent By dpalmer Date 2008-08-29 Time 13:55 Rev Time 0.00
Received By dpalmer Date 2008-08-29 Time 13:55 Sent To  
Notes
2008-08-29 13:56:09 
  
  
  
  
 ** DENIED **
  
  
  
 1) NOTE: PLANS NEED TO INDICATE THE MINIMUM CODES AS
 NOTED BELOW FOR DESIGN.
 2004 FBC W/ 2007 REVISONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR LOADS ON
 EXISTING PANEL DP. PLEASE BE SURE ALL CONTINUOUS LOADS
 ARE SHOWN AT 125%.
 220, 215.3, 230.42 ETC
  
 3) NOTE: PLEASE INDICATE THE LIGHTING CONTROLS PER FBC
 13-415.1.ABC.1.1,.1.2.
  
 4) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR NEW FEEDERS
 PER 13-413.1ABC.1
  
 5) NOTE: PLEASE PROVIDE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 6) NOTE: PLEASE SEE THAT PLANS, PANELS, RISER IS NOT
 COMPLETE AS THE RISER CONTAINS NOTES FOR A NEW PANEL
 *B* YET THE SUBMITTED PLANS DO NOT SHOW ANY NEW PANEL
 *B*. NO PANEL SCHEDULE, NO INFORMATION ON RISER ETC.
 PLEASE COMPLETE.
 215.5, 408.4, 240.4, 310.16
 FBC 106.3.5.1.2, 106.1.1 FOR CLARITY AND ADDITIONAL
 INFORMATION.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-12-03 Cont ID  
Sent By mawillia Date 2008-12-03 Time 12:16 Rev Time 0.00
Received By mawillia Date 2008-12-03 Time 11:59 Sent To  
Notes
2008-12-03 12:09:32*****APPROVED*****
  
  
 PLAN SHEETS A00.30 & A04.01 WERE STAMPED, INITIALED,
 AND DATED ON 12/03/2008.
  
  
 *****RESTAMP*****
  
 PLAN SHEETS A00.30, A04.01, AND E2 (OF ONE PLAN SET)
 WERE RSTAMPED, INITIALED, AND DATED ON 03/17/2009.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-29 Cont ID  
Sent By mawillia Date 2008-10-29 Time 14:02 Rev Time 0.00
Received By mawillia Date 2008-10-29 Time 13:37 Sent To  
Notes
2008-10-29 13:46:28*****FIRE STAMPING NEEDED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; THE APPROPIATE PLAN SHEET(S) TO BE
 FIRE-STAMPED WHEN THE OTHER PLAN EXAMINER'S COMMENTS
 HAVE BEEN SATISFIED.
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-05 Cont ID  
Sent By mawillia Date 2008-09-05 Time 16:27 Rev Time 0.00
Received By mawillia Date 2008-09-05 Time 15:36 Sent To  
Notes
2008-09-05 15:49:10*****DENIED*****
  
  
 1. ON SHEET A00.30 GENERAL NOTE #2, REPLACE NFPA 2003
 WITH NFPA 1 - 2003 AS AN REFERENCE.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. THE CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT HINDER OR INTERFERE WITH ACCESS TO OR EGRESS FROM
 THE SUBJECT PROPERTYOR THE VICINITY THEREOF (INCLUDING
 STREETS, ROADS, FIRE LANES, ETC.) .
  
 4. SPECIFY THE NEW WALL AND CEILING INTERIOR FINISH IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-11 Cont ID  
Sent By adarroug Date 2008-12-11 Time 10:26 Rev Time 0.00
Received By adarroug Date 2008-12-11 Time 10:26 Sent To E
Notes
2008-12-11 10:26:40TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-17 Cont ID  
Sent By adarroug Date 2008-11-17 Time 15:44 Rev Time 0.00
Received By adarroug Date 2008-11-17 Time 15:44 Sent To  
Notes
2008-11-17 15:47:49TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-16 Cont ID  
Sent By adarroug Date 2008-10-16 Time 16:34 Rev Time 0.00
Received By adarroug Date 2008-10-16 Time 16:34 Sent To  
Notes
2008-10-21 09:48:04TO "COMM" BD#5
2008-10-16 16:34:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-05 Cont ID  
Sent By mawillia Date 2008-09-05 Time 15:36 Rev Time 0.00
Received By mawillia Date 2008-08-13 Time 09:29 Sent To  
Notes
2008-08-13 09:50:04TO "COMM" BD#14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-17 Cont ID  
Sent By rregueir Date 2008-10-25 Time 16:06 Rev Time 0.00
Received By rregueir Date 2008-10-25 Time 16:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By rregueir Date 2008-08-27 Time 11:30 Rev Time 0.00
Received By rregueir Date 2008-08-27 Time 11:28 Sent To  
Notes
2008-08-27 11:30:21REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1: REFRIGERANT LINES APPEAR TO BE PENETRATING
 A FIRE RESISTANCE RATED FLOOR/CEILING ASSEMBLY. PROVIDE
 A THROUGH-PENETRATION FIRESTOP SYSTEM W/ DETAIL FOR
 PROTECTING PENETRATIONS OF RATED ASSEMBLIES IN
 ACCORDANCE WITH FBCB SECTION 712.
  
 2. PAGE M1: CONDENSING UNIT DETAIL CALLS FOR THE CU TO
 BE MOUNTED ON PATE CURBS BUT THERE IS ALSO A PRODUCT
 APPROVAL LISTED FOR A PRE-ENGINEERED A/C STAND. WHICH
 IS TO BE USED? PLEASE CLARIFY AND DEMONSTRATE
 COMPLIANCE WITH FBCM 304.10, 306.1 AND 306.5.
 NOTE: IF THE PRE-ENGINEERED STAND IS USED, A PRODUCT
 APPROVAL PACKAGE SHALL BE SUBMITTED WITH THE PERMIT
 APPLICATION. THE PRODUCT APPROVAL SHALL BE APPROVED IN
 WRITING (A SIGNED SHOP DRAWING REVIEW STAMP IS
 SUFFICIENT) BY THE DESIGN PROFESSIONAL IN ACCORDANCE
 WITH FBCB 106.3.3.
  
 3. PAGE M1: CONDENSATE DRAIN TRAP DETAIL DOES NOT
 CORRESPOND WITH MANUFACTURER?S INSTALLATION
 INSTRUCTIONS. CONDENSATE DRAINS SHALL BE TRAPPED AS
 REQUIRED BY THE EQUIPMENT OR APPLIANCE MANUFACTURER IN
 ACCORDANCE WITH FBCM 307.2.4. A COPY OF THE CONDENSATE
 PIPING INSTRUCTIONS IS ATTACHED TO THESE COMMENTS FOR
 REFERENCE. PROVIDE A DETAIL WHICH CORRESPONDS WITH THE
 MANUFACTURER?S INSTRUCTIONS ON THE PLANS OR REMOVE ANY
 CONFLICTING INFORMATION FROM THE PLANS.
  
 4. SHOW THE ACTUAL LOCATION OF CONDENSATE DISPOSAL ON
 THE PLANS. CONDENSATE FROM ALL COOLING COILS AND
 EVAPORATORS SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET
 TO AN APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO
 CAUSE A NUISANCE IN ACCORDANCE WITH FBCM 307.2.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-27 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aaponte Date 2008-10-27 Time 14:04 Sent To  
Notes
2008-10-27 14:04:35PROVISO:SIGNAGE AND AWNING NOT INCLUDED UNDER APPROVED
 PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-08-26 Cont ID  
Sent By aaponte Date 2008-08-26 Time 15:23 Rev Time 0.00
Received By aaponte Date 2008-08-26 Time 15:23 Sent To  
Notes
2008-08-26 15:27:301. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH 80% FRONTAGE REQUIREMENT.
 2. PROPOSED CANVAS AWNING IS NOT CONSISTENT WITH
 BUILDING DESIGN. PLEASE CONTACT ANA MARIA APONTE
 (561-822-1439) TO DISCUSS ALTERNATIVES.
 3. PLEASE PROVIDE INFORMATION REGARDING PROPOSED SIGN,
 AND CONFIRM PROPOSED AND EXISTING SIGN WILL NOT EXCEED
 MAXIMUM DIMESION ALLOWED FOR SIGNS.
 3. PLEASE PROVIDE INFORMATION TO CONFIRM REMOVED EXIT
 IS NOT AN EMERGENCY EXIT.