Plan Review Details - Permit 08080246
Plan Review Stops For Permit 08080246
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-09 Cont ID  
Sent By mjacobs Date 2008-09-09 Time 10:21 Rev Time 0.00
Received By mjacobs Date 2008-09-09 Time 07:37 Sent To  
Notes
2008-09-09 10:21:34 
 BUILDING PLAN REVIEW
 PERMIT: 08080246
 ADD: 477 S. ROSEMARY AVE #209 - 210
 CONT: OCEAN DRIVE BUILDING CORP.
 TEL: (561)833-3900
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES, MARKETING COST,
 OVERHEAD AND PROFIT EXCLUDING LAND. 108.3 FBC*
  
 4) SHEET A2.0 SHOWS TWO DEMOLITION PLANS. ONE PLAN
 SHALL BE THE EXISTING FLOOR PLAN AND THE OTHER SHALL BE
 THE PROPOSED FLOOR PLAN, WHICH SHALL INCLUDE ALL NEW
 CHANGES TO THE EXISTING LAYOUT. CONSTRUCTION DOCUMENT
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THE CODE. 106.1.1.
  
 5) NOW THE SPACE IS ALTERED SHOW THE LOCATION OF THE
 SPRINKLER HEADS FOR CODE COMPLIANCE. FBC 106.3.5.1.1(5)
 FLORIDA STATUTES 553.79(2).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status   Date 2008-09-09 Cont ID  
Sent By dpalmer Date 2008-09-09 Time 08:42 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2008-09-09 08:43:13THIS IS A COMMERIOCAL SPACE. ALL NEW BEING INSTALLED IS
 REQUIRED TO MEET FBC CHAPTER 13 FOR LIGHTING CONTROLS
 AND LIGHTING PERFORMANCE CALCULATIONS.
 VALUE FOR COMPLETE SCOPE OF WORK IS LOW. FBC 108.3

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-18 Cont ID  
Sent By btrobaug Date 2008-09-18 Time 10:24 Rev Time 0.00
Received By btrobaug Date 2008-09-02 Time 16:04 Sent To I
Notes
2008-09-18 10:24:55 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1ABC.1.1 FOR TIME CLOCK REQUIREMENTS AND FOR
 LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE
 ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE
 REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE
 CALCULATION PROCEDURES, GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE. SUBMIT A REFLECTTED CEILING PLAN THAT
 INDICATES THE LUMINAIRES LOCATION, NUMBER AND TYPE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-09-10 Cont ID  
Sent By mwennerg Date 2008-09-10 Time 08:48 Rev Time 0.00
Received By mwennerg Date 2008-09-10 Time 08:48 Sent To  
Notes
2008-09-10 08:52:26***PROVISO***
  
 1) A- SHEETS INDICATE AN ADDRESS OF 477 S. ROSEMARY
 AVE. #209-207 AND MEP'S INDICATE SUITE 209-210. PLEASE
 CORRELATE INFORMATION.
  
 2) PROVIDE FIRE SPRINKLER LAY OUT. ADDITIONALLY,
 SEPARET SHOP DRAWINGS AND PERMIT WILL BE REQUIRED FOR
 FIRE SPRINKLER REMODEL.
  
 PALNS WILL BE STAMPED WHEN RETURNED WITH CORRECTIONS
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-18 Cont ID  
Sent By btrobaug Date 2008-09-18 Time 10:25 Rev Time 0.00
Received By btrobaug Date 2008-08-27 Time 16:36 Sent To PC
Notes
2008-08-27 16:36:27TO "BOB" BD #1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-09-02 Cont ID  
Sent By tgordon Date 2008-09-02 Time 12:12 Rev Time 0.30
Received By tgordon Date 2008-09-02 Time 12:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-09-04 Cont ID  
Sent By mperson Date 2008-09-04 Time 13:22 Rev Time 0.00
Received By mperson Date 2008-09-04 Time 13:22 Sent To B
Notes
2008-09-04 13:33:44****************PROVISO****************
 INFORMATION ONLY: SHEET A3 DETAIL 13, BATHROOM AND
 DRINKNG FOUNTAIN ELEV. PLEASE KNOW THAT THE FOLLOWING
 IS REQUIRED PER THE FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTIONS FOR THE BATHROOM FIXTURES.
  
 **11-4.16 WATER CLOSETS
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
  
 **11-4.19 LAVATORIES AND MIRRORS
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON.
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
  
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM (SEE SHEET
 A2.0 DEMOLITION PLAN), DEAD ENDS SHALL BE PROHIBITED. A
 PLUMBING PERMIT IS REQUIRED AND AN INSPECTION IS
 REQUIRED OF PLUMBING DEMO WORK PRIOR TO COVERING DEMO
 WORK WITH FINNISH WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-09-11 Cont ID  
Sent By eschneid Date 2008-09-11 Time 13:07 Rev Time 0.00
Received By eschneid Date 2008-09-11 Time 13:07 Sent To  
Notes
***NONE***