Plan Review Details - Permit 08080195
Plan Review Stops For Permit 08080195
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-04-15 Cont ID  
Sent By jwitmer Date 2009-04-15 Time 07:14 Rev Time 1.00
Received By jwitmer Date 2009-04-15 Time 07:14 Sent To  
Notes
2009-04-15 07:15:43REVISION: #2 A-2.0 & A-4.1 DATED 4/07/09 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-02-23 Cont ID  
Sent By jwitmer Date 2009-02-23 Time 08:32 Rev Time 0.77
Received By jwitmer Date 2009-02-23 Time 08:32 Sent To  
Notes
2009-02-23 08:36:36BUILDING PLAN REVIEW
 PERMIT: 08080195
 ADD: 632 HIBISCUS ST
 CONT: SKYLINE BUILDERS
 TEL: (954)605-1196
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 JAN 07/09
  
 SUBMITTAL REVIEW:
 ACTION: REVIEWED
  
 LETTER OF CLARIFICATION:
 1) STEEL STUD BRACING 45 DEGREE ANGLE @ 4'-0" C/C.
  
 2) PARTITION TYPE "E" FRP AT COOLER, WATER HEATER AND
 ICE MACHINE FINISH ON ALL EXPOSED SIDES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-01-09 Cont ID  
Sent By jwitmer Date 2009-01-09 Time 07:49 Rev Time 0.66
Received By jwitmer Date 2009-01-09 Time 07:49 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-01-07 Cont ID  
Sent By jwitmer Date 2009-01-07 Time 10:45 Rev Time 0.33
Received By jwitmer Date 2009-01-07 Time 10:45 Sent To  
Notes
2009-01-07 10:46:32BUILDING PLAN REVIEW
 PERMIT: 08080195
 ADD: 632 HIBISCUS ST
 CONT: SKYLINE BUILDERS
 TEL: (954)605-1196
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 JAN 07/09
  
 3RD REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B)THRESHOLD BUILDING: PLEASE SUBMIT (3) OF ALL
 SURVEYS, PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS
 AND OR SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT
 IS CONSIDERED WITHIN A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D-E) COMPLIED.
  
  
  
  
 JIM WITMER C. B. O.
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-12-17 Cont ID  
Sent By jwitmer Date 2008-12-17 Time 10:43 Rev Time 0.77
Received By jwitmer Date 2008-12-17 Time 10:43 Sent To  
Notes
2008-12-17 10:51:37BUILDING PLAN REVIEW
 PERMIT: 08080195
 ADD: 632 HIBISCUS ST
 CONT: SKYLINE BUILDERS
 TEL: (954)605-1196
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 DEC.17/ 2008
 3RD REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLEASE SUBMIT (3) OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. YOUR PROJECT IS CONSIDERED WITHIN A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR (3)
 THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR
 PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST
 PALM BEACH ADMINISTRATIVE CODE.
  
 1C) ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D-E) COMPLIED.
  
 2) PLANS INDICATE THAT THIS IS A FIVE STORY BUILDING
 (A-1.0) , WHEN THE STRUCTURAL MEMBERS ARE AFFECTED THE
 THRESHOLD RULES ARE ENVOKED REQUIRING:
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) THIRD REQUEST) 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-35.001
  
 THIRD REQUEST:SEMI-COMPLIED, THE SPECIAL INSPECTOR
 AGREEMENT WAS NOT SIGNED BY THE OWNER, CONTRACTOR OR
 ARCHITECT.
 2B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 C) THRESHOLD BLDG, REQUIRED STATEMENT:COMPLIED.
  
  
 JIM WITMER C. B. O.
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-03 Cont ID  
Sent By jwitmer Date 2008-11-03 Time 11:17 Rev Time 0.77
Received By jwitmer Date 2008-11-03 Time 11:17 Sent To  
Notes
2008-11-03 11:17:59BUILDING PLAN REVIEW
 PERMIT: 08080195
 ADD: 632 HIBISCUS ST
 CONT: SKYLINE BUILDERS
 TEL: (954)605-1196
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 NOV. 3/ 2008
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLEASE SUBMIT (3) OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. YOUR PROJECT IS CONSIDERED WITHIN A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR (3)
 THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR
 PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST
 PALM BEACH ADMINISTRATIVE CODE.
  
 1C) ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D-E) COMPLIED.
  
 2) PLANS INDICATE THAT THIS IS A FIVE STORY BUILDING
 (A-1.0) , WHEN THE STRUCTURAL MEMBERS ARE AFFECTED THE
 THRESHOLD RULES ARE ENVOKED REQUIRING:
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 SECOND REQUEST:
 A) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 SECOND REQUEST:
 B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 C) THRESHOLD BLDG, REQUIRED STATEMENT:COMPLIED.
  
 3) ENERGY CALCS, SEE ELECTRICAL REVIEW.
  
 4) BUILDING PROVISO: THE NEW EXTERIOR AIR PURIFICATION
 SYSTEM AND SLAB UNDER SEPERATE PERMIT WILL NEED
 ENGINEERING AS PART OF COMPONENTS AND CLADDING FOR 140
 HPH WIND ZONE.
  
 5) SECOND REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JIM WITMER C. B. O.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By jwitmer Date 2008-08-27 Time 09:27 Rev Time 3.33
Received By jwitmer Date 2008-08-26 Time 16:58 Sent To  
Notes
2008-11-03 11:10:55BUILDING PLAN REVIEW
 PERMIT: 08080195
 ADD: 632 HIBISCUS ST
 CONT: SKYLINE BUILDERS
 TEL: (954)605-1196
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 NOV. 3/ 2008
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLEASE SUBMIT (3) OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. YOUR PROJECT IS CONSIDERED WITHIN A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR (3)
 THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR
 PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST
 PALM BEACH ADMINISTRATIVE CODE.
  
 1C) ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D-E) COMPLIED.
  
 2) PLANS INDICATE THAT THIS IS A FIVE STORY BUILDING
 (A-1.0) , WHEN THE STRUCTURAL MEMBERS ARE AFFECTED THE
 THRESHOLD RULES ARE ENVOKED REQUIRING:
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 SECOND REQUEST:
 A) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 SECOND REQUEST:
 B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 C) THRESHOLD BLDG, REQUIRED STATEMENT:COMPLIED.
  
 3) ENERGY CALCS, SEE ELECTRICAL REVIEW.
  
 4) BUILDING PROVISO: THE NEW EXTERIOR AIR PURIFICATION
 SYSTEM AND SLAB UNDER SEPERATE PERMIT WILL NEED
 ENGINEERING AS PART OF COMPONENTS AND CLADDING FOR 140
 HPH WIND ZONE.
  
 5) SECOND REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
2008-08-27 09:56:19BUILDING PLAN REVIEW
 PERMIT: 08080195
 ADD: 632 HIBISCUS ST
 CONT: SKYLINE BUILDERS
 TEL: (954)605-1196
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLEASE SUBMIT (3) OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. YOUR PROJECT IS CONSIDERED WITHIN A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR (3)
 THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR
 PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST
 PALM BEACH ADMINISTRATIVE CODE.
  
 1C) ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. SHEET A-4.2
 STRUCTURAL DESIGN DOES NOT INDICATE TO WHICH CODE AND
 SUPPLEMENTS THE DESIGN CRITERIA IS DESIGNED TOO. SHEET
 A-1.0 CODES ALSO NEEDS TO UPDATE THE 2007 SUPDATES TO
 THE 2004 FBC.
  
 1E) SHEET A-1.0 BUILDING INFORMATION INDICATES THIS TO
 BE A LEVEL II ALTERATION BUT NEGLECTS THE CHANGE OF
 OCCUPANCY EXISTING BUILDING CODE CHAPTER 8.
  
 2) PLANS INDICATE THAT THIS IS A FIVE STORY BUILDING
 (A-1.0) , WHEN THE STRUCTURAL MEMBERS ARE AFFECTED THE
 THRESHOLD RULES ARE ENVOKED REQUIRING:
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE
 THE PERMIT MAY BE ISSUED.
  
 THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 3) ENERGY CALCS SUBMITTED ARE 2 SETS ONE AN ORIGINAL
 SIGNED AND SEALED THE OTHER IS A COPY. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 4) BUILDING PROVISO: THE NEW EXTERIOR AIR PURIFICATION
 SYSTEM AND SLAB UNDER SEPERATE PERMIT WILL NEED
 ENGINEERING AS PART OF COMPONENTS AND CLADDING FOR 140
 HPH WIND ZONE.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-04-14 Cont ID  
Sent By dpalmer Date 2009-04-14 Time 18:09 Rev Time 0.00
Received By dpalmer Date 2009-04-14 Time 18:09 Sent To  
Notes
2009-04-14 18:14:05REVISION OK, ONCE OK WITH FIRE, NEED TO KEEP ONE SET.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-01-08 Cont ID  
Sent By dpalmer Date 2009-01-08 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2009-01-08 Time 16:45 Sent To  
Notes
2009-01-08 16:47:28NEW SHEET E-2 IN TWO SETS DOES NOT CONTAIN CITY PLACE
 STAMP. NEW SET FOR THE THIRD SET DOES NOT CONTAIN ANY
 CITY PLACE MANGEMENT STAMP. THIS IS NOT REQUIRED BY
 CODE, STATUTE ETC
 THIS INFORMATION WAS FORWARDED TO ASST BO TO HAVE A
 REPRESENATIVE COME IN AND STAMP PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-23 Cont ID  
Sent By dpalmer Date 2008-12-23 Time 11:21 Rev Time 0.00
Received By dpalmer Date 2008-12-23 Time 11:21 Sent To  
Notes
2008-12-23 11:21:27** DENIED**
  
 1) NOTE: DETERMINATION OF LIGHTING POWER DENSITY
 COMPLIANCE CAN NOT BE MADE THE FIXTURE LEGEND IS STILL
 NOT COMPLETE. FOR EXAMPLE: PLEASE SEE THE TRACK
 LIGHTING WHICH ONLY INDICATES THE TYPE OF TRACK. THE
 FIXTURE MUST BE SHOWN AS THE WATTAGE PER
 13-415.2.ABC.1.1 IS BASED ON THE VA RATING OF EACH
 FIXTURE OR 30 VA PER LINEAR FOOT OF TRACK, **WHICH EVER
 IS GREATER*. IF THE TRACK LIGHTING FIXTURES WERE FOR
 EXAMPLE 75WATT FIXTURES WITH THE NUMBER OF FIXTURES
 SHOWN THE TOTAL WATTAGE WOULD BE 2550. THIS WOULD BE
 FAR GREATER THAN THE 1560 WATTS FIGURED AT 30VA PER FT.
 THE ENERGY CODE IS BASED ON THE WATTAGE WHICH IS
 GREATER, NOT JUST A MINIMUM. EVEN IF THE FIXTURES WERE
 ONLY RATED AT 50WATTS THIS WOULD STILL BE MORE THAN THE
 1560 SHOWN IN CALCULATIONS.
  
 ** BASED ON EACH OF THESE TWO EXAMPLES OF 75W OR 50W
 FIXTURES, THE ALLOWANCES AS SHOWN WOULD BE OVER BASED
 ON CALCULATIONS SHOWN FOR MAXIMUM ALLOWANCES.
 AS STATED IN THE TWO PREVIOUS REVIEWS ALONG WITH THIS
 REVIEW IF THERE ARE ANY QUESTIONS PLEASE CALL. LIGHTING
 ALLOWANCES FOR SPACE BY SPACE NEED TO BE SHOWN FOR
 SPACE BY SPACE. SOME AREAS MAY BE OVER AS LONG AS SOME
 OTHER AREAS ARE LESS AND THE TOTAL ALLOWANCE IS NOT
 EXCEEDED.
  
  
 2) NOTE: THE SPECIAL INSPECTOR AGREEMENT CONTAINS A
 RAISED SEAL OVER PHOTO-COPIED SIGNATURES. IN FACT ALL
 SHEETS ARE PHOTO-COPIES INCLUDING THE SIGNATURES AND
 STAMPS FROM ALL PARTIES. NOTARY, ENGINEER, INSPECTOR
 ETC. PLEASE SEE FS 553.79, 471.025, 117, FAC
 61G15-23.002. ALL MUST ORIGINAL.
 ONLY ONE COPY WAS GIVEN TO CONTRACTOR TO OBTAIN ALL NEW
 ORIGINALS.
 THE ENGINEER OF RECORD RAISED SEAL FOR MR. OSVALDO
 AREVALO IS PLACED OVER PHOTO-COPIED LETTERS AND
 SIGNATURES.
 ** THESE TWO COPIES WILL BE RETAINED BY THIS OFFICE.
 DOCUMENTS ALSO SHOWN TO INTERIM ASSISTANT BUILDING
 OFFICIAL RONALD REGUEIRO.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-03 Cont ID  
Sent By dpalmer Date 2008-11-03 Time 08:53 Rev Time 0.00
Received By dpalmer Date 2008-11-03 Time 08:53 Sent To  
Notes
2008-11-03 08:53:38 
  
  
  
 ** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2.
 THE SUBMITTED FORM *C* AS SHOWN MAY NOT BE USED AS IT
 IS SHOWING SPACE BY SPACE ALLOWANCES. TABLE *C*
 13-415.2.C IS FOR BUILDING AREA TYPE. HOWEVER THE
 SUBMITTED FORM CLEARLY INDICATES TWO SEPARATE SPACES.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN FROM THE
 FBC AS IT CLEARLY STATES YOU MAY NOT MIX
 METHODS/TABLE/ALLOWANCES.
 THE PLANS INDICATE THE SAME ALLOWANCE ALTHOUGH NOT
 INDICATING A METHOD OF CALCULATION. IN EITHER CASE THE
 ALLOWANCES AS SHOWN ARE NOT PERMITTED AND THE METHOD IS
 INCORRECT.
 THE DINING AREA AS SHOWN ON FORM INDICATES A 2.1
 ALLOWANCE HOWEVER NO DINING AREAS AS SHOWN IN TABLE *C*
 IN THE CODE PERMITS THAT HIGH OF A LIGHTING LEVEL. IN
 FACT FAMILY DINING IN TABLE C WHICH IS THE HIGHEST IS
 1.6.
 THE FOLLOWING IS A LINE FROM THIS SECTION OF THE CODE.
 13-415.2.ABC.1.
  
 ** TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE
 AMONG PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT
 METHOD OF CALCULATION HAS BEEN USED ARE NOT PERMITTED.
  
 ** PLEASE SUBMIT AND SHOW COMPLIANCE WITH THE SECTIONS
 ABOVE AND IF THERE ARE QUESTIONS PLEASE CALL. ALLOWANCE
 AS NOTED ON FORM *C* IS OVER.
  
 PLEASE BE SURE TO SEE TRACK LIGHTING ALLOWANCES IN
 SECTIONS ABOVE.
  
  
 2) NOTE: PLEASE INDICATE MORE INFORMATION FOR THE
 LIGHTING CONTROL SYSTEM PROPOSED.
 THE PLANS DO NOT INDICATE IF THERE ARE PILOT LIGHTS AS
 REQUIRED. SECTION 13-415.1.ABC.1.1,.1.2 REQUIRES THE
 OVER RIDE FOR NO MORE THAN 4HRS. THESE SAME SECTIONS
 REQUIRES THE OCCUPANT TO VISUALLY SEE ALL LIGHTING
 WHICH IS BEING CONTROLLED/OVER RIDDEN. IF THE OCCUPANT
 CAN NOT SEE *ALL* LIGHTS THEN THE EXCEPTION IS THAT THE
 LIGHTING CONTROLS REQUIRES PILOT/INDICATOR LIGHTS WHICH
 ARE REQUIRED TO BE LABELED. IF THE DEVICES AS NOTED
 CONTAIN THESE INDICATOR/PILOT LIGHTS THEN PLEASE
 IDENTIFY.
  
 3) NOTE: PREVIOUS NOTE REQUESTED TO SHOW HOW THE TRACK
 LIGHTING LOADS PER 220.43 ARE FIGURED AND TO PLEASE
 SHOW. COULD NOT LOCATE ANY CHANGE TO THIS.
  
 4) NOTE: IF BOTH SUITES WHICH ARE SHOWN AS 116 AND 120
 ARE GOING TO HAVE TWO MAINS FEEDING WHAT IS NOW GOING
 TO BE ONE SUITE THAN THIS NEW SINGLE TENANT NEEDS TO
 HAVE SIGNAGE INDICATING THIS. AS THE APPLIED ADDRESS
 LOCATION AS SHOWN ON THE TITLE BLOCKS ARE SUITE #116
 THAN THE MAINS FOR TENANT BOTH NEED TO BE LABELED SUITE
 #116 MAIN ONE OF TWO AND 2 OF TWO. RISER SHOWS TWO
 SEPARATE SUITES. IF THE FIRE DEPARTMENT OR ANY OTHER
 PERSONNEL NEEDED TO TURN POWER OFF IN ANY EVENT THESE
 WOULD NOT BE LABELED CORRECTLY.
 230.2E, 225.37. (THESE ARE FEEDERS) THE CODE SECTIONS
 GIVEN ARE FOR SERVICE ENTRANCE AND FEEDERS. THE INTENT
 OF THE CODE SECTIONS ARE THE SAME AS ALL EQUIPMENT IS
 REQUIRED TO BE CORRECTLY LABELED.
  
 5) NOTE: PLEASE INDICATE THE HEIGHTS OF DEVICE FOR
 HORN/STROBES AND ANY PULL STATIONS PER 11-4.28.1,.2 AND
 .3.
 THE MINIMUM CANDELA LEVELS ARE SHOWN WHICH ARE OK.
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-28 Cont ID  
Sent By dpalmer Date 2008-08-28 Time 14:09 Rev Time 0.00
Received By dpalmer Date 2008-08-28 Time 14:09 Sent To  
Notes
2008-08-28 14:09:52** DENIED PLAN **
  
  
  
 1) NOTE:PLEASE SEE THE SUBMITTED METHOD *A*
 CALCULATIONS MAY NOTBE USED. THIS IS NOT A WHOLE
 BUILDING. PLEASE SEE 13-101.1
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS AND
 INDICATE THE METHOD TO BE USED. THE PLANS MENTION WHOLE
 AREA HOWEVER BASED ON OCCUPANCY TYPE PER 13-415.2.C THE
 LEVELS OF LIGHTING SHOWN ON PLANS EXCEED THAT PERMITTED
 BY TABLE C.
 PLEASE SEE 13-415.2.ABC.1.1,.1.2 AND .1.3
 PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND. THE
 LEGEND MUST BE COMPLETE AT THIS TIME TO FIGURE CORRECT
 WATTAGE ALLOWANCES. PLEASE KNOW THE WATTAGE WHICH MUST
 BE USED IS THE MAXIMUM VA OF THE FIXTURE, BALLAST OR
 TRANSFORMER NOT THE BULB. THE WATTAGE FOR TRACK
 LIGHTING SHALL BE WHICH EVER IS GREATER.
  
 2) NOTE: PLEASE COMPLETE THE PLANS FOR THE LIGHTING
 CONTROL SYSTEM AS NOTED.PLANS DO NOT SHOW ANY
 LOCATIONS FOR LIGHTING CONTROLS.
 THERE IS NOT ENOUGH INFORMATION ON PLANS AT THIS TIME.
 PLEASE PROVIDE ESTIMATED SCHEDULING. PLEASE PROVIDE ALL
 LOCATIONS OF CONTROLS, OVER RIDES AND ZONES. PLEASE BE
 SURE TO STATE ALL MAXIMUM OVER RIDE TIMES AS WELL AS
 MAXIMUM TIMES ON ANY OTHER DEVICES. PLEASE SEE SECTION
 BELOW FOR REQUIRED SEPARATE CONTROLS FOR DISPLAY/ACCENT
 LIGHTING.
 13-415.1.ABC.1.1,.1.2, .1.3 AND ANY EXTERIOR LIGHTING
 SHALL FALL UNDER .1.4.
  
 3) NOTE: PLEASE INDICATE THE TRACK LIGHTING LOADS PER
 220.43.
  
 4) NOTE: PLEASE ALSO SEE THE SUBMITTED ENERGY
 CALCULATIONS ARE PHOTO-COPIES AND ARE NOT ORIGINAL FAC
 61G15-23.002, FS 471.025
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mawillia Date 2009-04-16 Time 11:09 Sent To  
Notes
2009-04-16 11:12:35*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS A2.0, E1.0, AND E2.0 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-01-08 Cont ID  
Sent By rregueir Date 2009-01-08 Time 16:56 Rev Time 0.00
Received By rregueir Date 2009-01-08 Time 16:55 Sent To  
Notes
2009-01-08 16:55:54PLANS STAMPED BY MIKE WENNERGREN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-12-29 Cont ID  
Sent By mwennerg Date 2008-12-29 Time 10:42 Rev Time 0.00
Received By mwennerg Date 2008-12-29 Time 10:42 Sent To  
Notes
2008-12-29 10:43:51***DENIED***
  
 COMMENT TAKEN DIRECTLY FROM LAST FIRE REVIEW.
  
  
 1) EXIT LIGHTS FOR EXIT DOORS ARE SHOWN ON LIFE SAFETY
 DRAWING A-2.2, BUT ARE NOT SHOWN ON THE LIGHTING PLAN
 SHEET E2.0. PLEASE CORRELATE APPLICABLE SHEETS TO
 ILLUSTRATE CORRECT INFORMATION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-11-12 Cont ID  
Sent By mwennerg Date 2008-11-12 Time 13:11 Rev Time 0.00
Received By mwennerg Date 2008-11-12 Time 13:11 Sent To  
Notes
2008-11-12 13:18:21***DENIED***
  
 MOST OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING:
  
 2) OK- EXIT LIGHTS FOR EXIT DOORS ARE SHOWN ON LIFE
 SAFETY DRAWING A-2.2, BUT ARE NOT SHOWN ON THE LIGHTING
 PLAN SHEET E2.0. PLEASE CORRELATE APPLICABLE SHEETS TO
 ILLUSTRATE CORRECT INFORMATION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-05 Cont ID  
Sent By mawillia Date 2008-09-05 Time 15:27 Rev Time 0.00
Received By mawillia Date 2008-09-05 Time 14:06 Sent To  
Notes
2008-09-05 15:26:55*****DENIED*****
  
 1. ON SHEET A2.2, SHOW THE PATH OF EGRESS FROM THE OPEN
 KITCHEN AREA (ROOM 113) .
  
 2. EXIT LIGHTS ARE SHOWN ON BOTH SIDES OF DOOR #6
 LOCATED BETWEEN COORIDOR 111 AND 112. THIS WOULD APPEAR
 TO BE CONFLICT OF EGRESS USAGE.
  
 3. ON SHEET A3.0 AND E2.0 IN THE CEILING LEGEND,
 REFERENCE IS MADE TO THE ENGINEERED FIRE SPRINKLER
 DRAWINGS COMPLING WITH NFPA 96. PLEASE BE ADVISED THAT
 NFPA 96 IS THE STANDARD FOR VENTILATION CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS.
  
 4. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THIS
 SCOPE OF WORK. THESE DEVICES MAY BE SHOWN ON SHEET E1.0
 (POWER PLAN) .
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-11-05 Cont ID  
Sent By kstevens Date 2008-11-05 Time 17:07 Rev Time 0.00
Received By kstevens Date 2008-11-05 Time 17:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-08-14 Cont ID  
Sent By kstevens Date 2008-08-14 Time 17:05 Rev Time 0.00
Received By kstevens Date 2008-08-13 Time 17:05 Sent To  
Notes
2008-11-05 17:07:07SEE PLUMBING PLAN REVIEW FOR GAS COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-04-14 Cont ID  
Sent By mjacobs Date 2009-04-14 Time 16:38 Rev Time 0.00
Received By mjacobs Date 2009-04-14 Time 16:38 Sent To  
Notes
2009-04-14 16:39:16TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-03-16 Cont ID  
Sent By shill Date 2009-03-16 Time 16:39 Rev Time 0.00
Received By shill Date 2009-03-16 Time 16:39 Sent To P
Notes
2009-03-16 16:39:57TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-11 Cont ID  
Sent By adarroug Date 2009-02-11 Time 10:55 Rev Time 0.00
Received By adarroug Date 2009-02-11 Time 10:55 Sent To B
Notes
2009-02-11 10:56:11TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-09 Cont ID  
Sent By adarroug Date 2008-12-09 Time 10:07 Rev Time 0.00
Received By adarroug Date 2008-12-09 Time 10:07 Sent To  
Notes
2008-12-09 10:09:58TO "COMM" BD#56

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-22 Cont ID  
Sent By adarroug Date 2008-10-22 Time 08:30 Rev Time 0.00
Received By adarroug Date 2008-10-22 Time 08:30 Sent To  
Notes
2008-10-22 08:31:04TO "COMM" BD#52

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-05 Cont ID  
Sent By mawillia Date 2008-09-05 Time 14:52 Rev Time 0.00
Received By mawillia Date 2008-08-08 Time 14:55 Sent To  
Notes
2008-08-08 14:59:13TO "COMM" BD#55

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-04-03 Cont ID  
Sent By rregueir Date 2009-04-03 Time 17:52 Rev Time 0.00
Received By rregueir Date 2009-04-03 Time 17:52 Sent To  
Notes
2009-04-03 17:52:39REVISED M-01 DELTA 4

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-02-18 Cont ID  
Sent By rregueir Date 2009-02-18 Time 18:13 Rev Time 0.00
Received By rregueir Date 2009-02-18 Time 18:12 Sent To PC
Notes
2009-02-18 18:13:01REVISED M01 FOR OA DUCT CHANGES

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-01-08 Cont ID  
Sent By rregueir Date 2009-01-08 Time 16:52 Rev Time 0.00
Received By rregueir Date 2009-01-08 Time 16:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-11-15 Cont ID  
Sent By rregueir Date 2008-11-15 Time 13:56 Rev Time 0.00
Received By rregueir Date 2008-11-15 Time 13:40 Sent To  
Notes
2008-11-15 13:42:22REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK: IT IS NOT CLEAR HOW TOTAL SEATS WILL PREDICT
 MAXIMUM OCCUPANCY, INCLUDING EMPLOYEES AND THOSE
 WAITING TO BE SEATED, BUT WILL DEFER TO THE JUDGEMENT
 OF THE DESIGN PROFESSIONAL.
  
 3. **PREVIOUS REVIEW COMMENT** PAGE M1.0: NOTE #1,
 WHICH REFERENCED 13-409.1.ABC.3.3 FOR SHUTOFF DAMPER
 CONTROLS, CALLS FOR MOTORIZED DAMPER ON THE OA INTAKE
 FOR AHU #1 WITH NO PROVISIONS FOR AHU #2 OR AHU #3.
 EVEN THOUGH THEY SHOW LESS THAN 300 CFM, A BACK DRAFT
 DAMPER, AT A MINIMUM, IS REQUIRED TO MEET THE
 REQUIREMENTS OF THIS CODE SECTION.
 **NOT ADEQUATELY ADDRESSED** PAGE M1.0 SHOWS THE
 ADDITION OF MANUAL VOLUME DAMPERS IN RESPONSE TO THIS
 COMMENT. AS STATED IN THE PREVIOUS REVIEW COMMENT, A
 BACKDRAFT DAMPER IS REQUIRED IN O.A. INTAKES IN LIEU OF
 THE MOTORIZED DAMPERS PER THE REFERENCED SECTION. THE
 MANUAL VOLUME DAMPERS SATISFY THE REQUIREMENTS OF
 13-409.1.ABC.1.1 BUT DO NOT SATISFY THE REQUIREMENTS OF
 13-409.1.ABC.3.3.
  
  
 4. **PREVIOUS REVIEW COMMENT** PAGE M2.0: DIFFUSER AND
 FLEXIBLE DUCT DETAILS ARE NOT CODE COMPLIANT. THE
 MINIMUM WIDTH OF HANGERS AND SUPPORTS FOR FLEXIBLE
 DUCTS SHALL BE 1.5 INCHES AND THE MAXIMUM SAG BETWEEN
 SUPPORTS SHALL BE 1/2 INCH PER FOOT IN ACCORDANCE WITH
 FBCM 603.5.6.6. ADJUST DETAILS TO SHOW COMPLIANCE WITH
 THIS SECTION.
 **NOT ADEQUATELY ADDRESSED** DETAIL NOW ALLOWS FOR A
 MAXIMUM OF 1.5 INCES OF SAG PER FOOT OF LENGTH RATHER
 THAN THE 0.5 INCHES PER FOOT OF LENGTH AS STATED IN
 PREVIOUS REVIEW COMMENT AND AS REQUIRED BY FBCM
 603.5.6.6(4).
  
 NOTE: METHOD C CALCS OK FOR MECHANICAL. SEE ELECTRICAL
 REVIEW COMMENTS.
  
 NOTE: NO INFORMATION WAS PROVIDED ON THESE PLANS
 REGARDING KITCHEN HOOD/EXHAUST AND WALK-IN COOLER
 SYSTEMS. SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 THESE SYSTEMS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-26 Cont ID  
Sent By rregueir Date 2008-08-26 Time 10:59 Rev Time 0.00
Received By rregueir Date 2008-08-25 Time 16:40 Sent To  
Notes
2008-08-26 10:59:14REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1.0: VENTILATION CALCULATIONS STATE THEY ARE
 BASED ON ASHRAE 62.1-2007. HOWEVER, THE REFERENCED
 STANDARD IS CURRENTLY ASHRAE 62.1-2004 EDITION IN
 ACCORDANCE WITH FBCM CHAPTER 15. PLEASE REFERENCE THE
 CORRECT STANDARD ON THE PLANS AT THE VENTILATION
 CALCULATIONS TABLE.
  
 2. PAGE M1.0: THE DINING AREA DEFAULT OCCUPANT DENSITY
 BASED ON TABLE 6-1 FOR DINING ROOMS IS 70/1000 SQ. FT.
 WITH THE GIVEN SQUARE FOOTAGE OF 1800, THIS GIVES A
 DEFAULT OCCUPANT LOAD OF 126 PERSONS. BASED ON EQUATION
 6-1, THE TOTAL OUTSIDE AIR REQUIRED FOR THE DINING
 AREAS IS 1269 CFM. PLEASE ADJUST OUTDOOR AIR QUANTITIES
 ACCORDINGLY.
  
 3. PAGE M1.0: NOTE #1, WHICH REFERENCED
 13-409.1.ABC.3.3 FOR SHUTOFF DAMPER CONTROLS, CALLS FOR
 MOTORIZED DAMPER ON THE OA INTAKE FOR AHU #1 WITH NO
 PROVISIONS FOR AHU #2 OR AHU #3. EVEN THOUGH THEY SHOW
 LESS THAN 300 CFM, A BACK DRAFT DAMPER, AT A MINIMUM,
 IS REQUIRED TO MEET THE REQUIREMENTS OF THIS CODE
 SECTION.
 NOTE: BASED ON COMMENT #2, THE OUTSIDE AIR VOLUME FOR
 EACH UNIT IS LIKELY TO BE OVER 300 CFM AND THEREFORE A
 MOTORIZED DAMPER WILL BE REQUIRED.
  
 4. PAGE M2.0: DIFFUSER AND FLEXIBLE DUCT DETAILS ARE
 NOT CODE COMPLIANT. THE MINIMUM WIDTH OF HANGERS AND
 SUPPORTS FOR FLEXIBLE DUCTS SHALL BE 1.5 INCHES AND THE
 MAXIMUM SAG BETWEEN SUPPORTS SHALL BE 1/2 INCH PER FOOT
 IN ACCORDANCE WITH FBCM 603.5.6.6. ADJUST DETAILS TO
 SHOW COMPLIANCE WITH THIS SECTION.
  
 NOTE: THE METHOD A ENERGY CALCULATIONS WHICH WERE
 SUBMITTED WITH THIS APPLICATION WERE NOT REVIEWED FOR
 COMPLIANCE WITH THE MECHANICAL PROVISIONS OF FBCB
 CHAPTER 13. METHOD A CALCULATIONS ARE NEITHER
 APPROPRIATE NOR REQUIRED FOR THIS PROJECT AS THIS IS
 NOT A WHOLE BUILDING AND DOES NOT QUALIFY AS A
 RENOVATION AS DEFINED IN FBCB SECTION 13-202. THE
 MINIMUM REQUIRED FOR COMPLIANCE WITH FBCB CHAPTER 13
 FOR THIS PROJECT CAN BE FOUND IN SECTION 13-101.6 AND
 ARE AS FOLLOWS:
  
 THERMAL EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING
 BUILDING SYSTEMS WHERE NEW PRODUCTS ARE INSTALLED OR
 REPLACED IN EXISTING BUILDINGS, AND FOR WHICH A PERMIT
 MUST BE OBTAINED. SUCH SYSTEMS SHALL MEET THE MINIMUM
 EFFICIENCIES ALLOWED FOR THAT SYSTEM ON FORM 400C FOR
 COMMERCIAL BUILDINGS AND ON FORM 600C FOR RESIDENTIAL
 BUILDINGS.
 1. HEATING, VENTILATING OR AIR CONDITIONING SYSTEMS;
 2. SERVICE WATER OR POOL HEATING SYSTEMS;
 3. ELECTRICAL SYSTEMS AND MOTORS;
 4. LIGHTING SYSTEMS.
  
 THESE REQUIREMENTS HAVE BEEN DEMONSTRATED ON THE PLANS
 FOR THE NEWLY INSTALLED MECHANICAL SYSTEMS. PLEASE SEE
 OTHER TRADE REVIEWS FOR COMMENTS REGRADING OTHER
 AFFECTED SYSTEMS.
  
 NOTE: NO INFORMATION WAS PROVIDED ON THESE PLANS
 REGARDING KITCHEN HOOD/EXHAUST AND WALK-IN COOLER
 SYSTEMS. SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 THESE SYSTEMS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 6 Status P Date 2009-03-27 Cont ID  
Sent By kstevens Date 2009-03-27 Time 14:30 Rev Time 0.00
Received By kstevens Date 2009-03-27 Time 14:30 Sent To  
Notes
2009-03-27 14:31:29REVISION OK -- SHT P1.0

Review Stop P PLUMBING
Rev No 5 Status F Date 2009-03-18 Cont ID  
Sent By kstevens Date 2009-03-18 Time 18:27 Rev Time 0.00
Received By kstevens Date 2009-03-18 Time 18:27 Sent To  
Notes
2009-03-18 18:31:26DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P1.0 ALL REVISIONS TO A SIGNED, SEALED & DATED
 SET OF PLANS SHALL BE SIGNED, SEALED & DATED BY THE
 ENGINEER OF RECORD. SECTION 106.1, FAC 61G15023.002 &
 FS 471.025.
  
 2. SHT P1.0 IS INDICATING THE HAND SINK CONNECTING TO
 THE LAV STACK FOR THE TOILET ROOM. THIS IS NOT APPROVED
 PER SECTION 909.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status N Date 2009-03-18 Cont ID  
Sent By kstevens Date 2009-03-18 Time 18:27 Rev Time 0.00
Received By kstevens Date 2009-03-18 Time 18:27 Sent To  
Notes
2009-03-18 18:27:44REVISION OK -- SHT P2.0 REVISION #2.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-12-18 Cont ID  
Sent By kstevens Date 2008-12-18 Time 16:49 Rev Time 0.00
Received By kstevens Date 2008-12-18 Time 16:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-11-05 Cont ID  
Sent By kstevens Date 2008-11-05 Time 17:07 Rev Time 0.00
Received By kstevens Date 2008-11-05 Time 17:07 Sent To  
Notes
2008-11-05 17:08:29PASSED/PROVISO -- EXPANSION TANK TO BE DETA-12 MODEL

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-14 Cont ID  
Sent By kstevens Date 2008-08-14 Time 10:51 Rev Time 0.00
Received By kstevens Date 2008-08-13 Time 17:10 Sent To  
Notes
2008-08-14 11:33:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE CITY WPB
  
 1. ALL SHEETS REQUIRE THE "CITY PLACE" APPROVAL STAMP
 PRIOR TO REVIEW BY CITY WPB.
  
 2. ALL SHTS WITH THE ARCHITECT'S TITLE BLOCK. THE
 ADDRESS ON THE TITLE BLOCK, 370 CAMINO GARDENS BLVD,
 DOES NOT REFLECT THE ADDRESS OF RECORD ON THE STATE OF
 FLORIDA, DBPR WEBSITE. PLEASE UPDATE EITHER THE TITLE
 BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING TO
 CITY WPB. FAC 61G1-16.004(1) & FS 481.2055.
  
 3. SHT A-1.0 CODES TO INDICATE ALL UPDATES UP TO 2007.
 SECTION 106.1.1.
  
 4. ALL ARCHITECTURAL SHEETS. A SIGNATURE IS REQUIRED ON
 THE DATED SEAL OF EACH SHEET. IT APPEARS THAT INITIALS
 HAVE BEEN USED. IF THIS IS INDEED THE LEGAL SIGNATURE,
 THEN A SIGNED, SEALED, NOTORIZED LETTER IS REQUIRED FOR
 OUR FILES INDICATING THE LEGAL SIGNATURE OF THE
 ARCHITECT, CRAIG MOSSEY. FAC 61G1-16.003,
 61G1-16.004(5) & FS 481.2055. PLEASE SUBMIT
 VERIFICATION LETTER. ^^^^^^^^(DELETE COMMENT NEXT
 REVIEW)^^^^^^^
  
 5. SHTS A-2.4 DETAIL #2 AND A-5.0 FINISH SCHEDULE.
 ROOMS 106 & 106 WALLS WITH IN 2 FEET OF THE WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE. EPOXY PAINT DOES NOT COMPLY WITH THE "HARD"
 REQUIREMENT. SECTION 1210.2. PLEASE INDICATE METHOD OF
 COMPLIANCE.
  
 6. SHT P1.0 SANITARY PLAN/ISOMETRIC. THE DISHWASHER
 SHALL DISCHARGE INTO THE SANITARY SYSTEM PER ARTICLE
 III SECTION 90-124(7)(B). PLEASE CHANGE FLOOR PLAN AND
 ISOMETRIC.
  
 7. SHT P1.0 SANITARY PLAN/ISOMETRIC. THE DISCHARGE FROM
 THE AIR PURIFICATION UNIT SHALL BE THRU AN INDIRECT
 WASTE RECEPTOR. SECTION 802.1.5. A FLOOR SINK OR HUB
 DRAIN IS REQUIRED FOR INDIRECT WASTE RECEPTOR. SECTIONS
 802.3 & 802.3.2.
  
 8. SHT P2.0 WATER PLAN/ISOMETRIC. A WATER HAMMER
 ARRESTOR IS REQUIRED ON THE WATER SUPPLY FOR THE
 DISHWASHER. SECTION 604.9. PLEASE SHOW ON THE
 ISOMETRIC.
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE
 FOLLOWING INFORMATION REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 B. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 10. SHT P3.0 FLOOR SINK DETAIL. THE AIR GAP SHALL BE
 PER SECTION 802.2.1, MINIMUM TWICE THE EFFECTIVE
 OPENING OF THE INDIRECT WASTE PIPE. PLEASE INDICATE ON
 DETAIL.
  
 11. SHT P3.0 ELECTRIC WATER HEATER DETAIL. THERMAL
 EXPANSION CONTROL IS REQUIRED. SECTION 607.3.2. PLEASE
 INDICATE METHOD.
  
 12. SHT P3.0 GREASE INTERCEPTOR DETAIL NOTES INDICATES
 THE INLET PIPING SHALL EXTEND 24" BELOW THE WATER
 LEVEL, BUT THE DETAIL DOES NOT SHOW THIS. PER SECTION
 1003.5.3 THE INLET PIPING SHALL CONNECT TO A TEE WHICH
 SHALL EXTEND 24" BELOW THE WATER LEVEL. PLEASE HAVE
 DETAIL REFLECT REQUIREMENT. (CITY WPB APPROVED
 DETAIL).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2008-08-18 Cont ID  
Sent By eschneid Date 2008-08-18 Time 13:23 Rev Time 0.00
Received By eschneid Date 2008-08-18 Time 13:22 Sent To  
Notes
2008-08-18 13:23:35PROVISO: CITYPLACE STAMP REQUIRED ON ALL PLAN SETS.
  
 NO EXTERIOR WORK.
  
 PLEASE NOTE THAT NO BAR FACILITIES MAY BE INSTALLED.


Account Summary | Usage Policy | Privacy Policy