| Plan Review Stops For Permit 08080195 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2009-04-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-04-15 |
Time |
07:14 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2009-04-15 |
Time |
07:14 |
Sent To |
|
|
| Notes |
| 2009-04-15 07:15:43 | REVISION: #2 A-2.0 & A-4.1 DATED 4/07/09 OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2009-02-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-02-23 |
Time |
08:32 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-02-23 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2009-02-23 08:36:36 | BUILDING PLAN REVIEW | | | PERMIT: 08080195 | | | ADD: 632 HIBISCUS ST | | | CONT: SKYLINE BUILDERS | | | TEL: (954)605-1196 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | JAN 07/09 | | | | | | SUBMITTAL REVIEW: | | | ACTION: REVIEWED | | | | | | LETTER OF CLARIFICATION: | | | 1) STEEL STUD BRACING 45 DEGREE ANGLE @ 4'-0" C/C. | | | | | | 2) PARTITION TYPE "E" FRP AT COOLER, WATER HEATER AND | | | ICE MACHINE FINISH ON ALL EXPOSED SIDES. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2009-01-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-01-09 |
Time |
07:49 |
Rev Time |
0.66 |
| Received By |
jwitmer |
Date |
2009-01-09 |
Time |
07:49 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2009-01-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-01-07 |
Time |
10:45 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2009-01-07 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2009-01-07 10:46:32 | BUILDING PLAN REVIEW | | | PERMIT: 08080195 | | | ADD: 632 HIBISCUS ST | | | CONT: SKYLINE BUILDERS | | | TEL: (954)605-1196 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | JAN 07/09 | | | | | | 3RD REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B)THRESHOLD BUILDING: PLEASE SUBMIT (3) OF ALL | | | SURVEYS, PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS | | | AND OR SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT | | | IS CONSIDERED WITHIN A THRESHOLD BUILDING REQUIRING A | | | THRESHOLD INSPECTOR (3) THREE SETS OF ALL SAID | | | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* | | | /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH | | | ADMINISTRATIVE CODE. | | | | | | 1C) ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1D-E) COMPLIED. | | | | | | | | | | | | | | | JIM WITMER C. B. O. | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-12-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-17 |
Time |
10:43 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-12-17 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2008-12-17 10:51:37 | BUILDING PLAN REVIEW | | | PERMIT: 08080195 | | | ADD: 632 HIBISCUS ST | | | CONT: SKYLINE BUILDERS | | | TEL: (954)605-1196 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | DEC.17/ 2008 | | | 3RD REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) PLEASE SUBMIT (3) OF ALL SURVEYS, PLANS, REPORTS, | | | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR | | | REVIEW FOR PERMIT. YOUR PROJECT IS CONSIDERED WITHIN A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR (3) | | | THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR | | | PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST | | | PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C) ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1D-E) COMPLIED. | | | | | | 2) PLANS INDICATE THAT THIS IS A FIVE STORY BUILDING | | | (A-1.0) , WHEN THE STRUCTURAL MEMBERS ARE AFFECTED THE | | | THRESHOLD RULES ARE ENVOKED REQUIRING: | | | | | | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " | | | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH | | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 2A) THIRD REQUEST) 105.13.1 THE ENFORCING AGENCY SHALL | | | REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL | | | INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A | | | WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE | | | ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST | | | BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE | | | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A | | | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL | | | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION | | | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE | | | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED | | | DOCUMENTS. | | | FLORIDA ADMINISTRATIVE CODE 61G15-35.001 | | | | | | THIRD REQUEST:SEMI-COMPLIED, THE SPECIAL INSPECTOR | | | AGREEMENT WAS NOT SIGNED BY THE OWNER, CONTRACTOR OR | | | ARCHITECT. | | | 2B) THRESHOLD INSPECTOR: | | | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES | | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | | CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | C) THRESHOLD BLDG, REQUIRED STATEMENT:COMPLIED. | | | | | | | | | JIM WITMER C. B. O. | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-11-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-03 |
Time |
11:17 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-11-03 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2008-11-03 11:17:59 | BUILDING PLAN REVIEW | | | PERMIT: 08080195 | | | ADD: 632 HIBISCUS ST | | | CONT: SKYLINE BUILDERS | | | TEL: (954)605-1196 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | NOV. 3/ 2008 | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) PLEASE SUBMIT (3) OF ALL SURVEYS, PLANS, REPORTS, | | | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR | | | REVIEW FOR PERMIT. YOUR PROJECT IS CONSIDERED WITHIN A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR (3) | | | THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR | | | PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST | | | PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C) ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1D-E) COMPLIED. | | | | | | 2) PLANS INDICATE THAT THIS IS A FIVE STORY BUILDING | | | (A-1.0) , WHEN THE STRUCTURAL MEMBERS ARE AFFECTED THE | | | THRESHOLD RULES ARE ENVOKED REQUIRING: | | | | | | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " | | | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH | | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | SECOND REQUEST: | | | A) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A | | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | SECOND REQUEST: | | | B) THRESHOLD INSPECTOR: | | | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES | | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | | CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | C) THRESHOLD BLDG, REQUIRED STATEMENT:COMPLIED. | | | | | | 3) ENERGY CALCS, SEE ELECTRICAL REVIEW. | | | | | | 4) BUILDING PROVISO: THE NEW EXTERIOR AIR PURIFICATION | | | SYSTEM AND SLAB UNDER SEPERATE PERMIT WILL NEED | | | ENGINEERING AS PART OF COMPONENTS AND CLADDING FOR 140 | | | HPH WIND ZONE. | | | | | | 5) SECOND REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JIM WITMER C. B. O. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-08-27 |
Time |
09:27 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2008-08-26 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2008-11-03 11:10:55 | BUILDING PLAN REVIEW | | | PERMIT: 08080195 | | | ADD: 632 HIBISCUS ST | | | CONT: SKYLINE BUILDERS | | | TEL: (954)605-1196 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | NOV. 3/ 2008 | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) PLEASE SUBMIT (3) OF ALL SURVEYS, PLANS, REPORTS, | | | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR | | | REVIEW FOR PERMIT. YOUR PROJECT IS CONSIDERED WITHIN A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR (3) | | | THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR | | | PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST | | | PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C) ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1D-E) COMPLIED. | | | | | | 2) PLANS INDICATE THAT THIS IS A FIVE STORY BUILDING | | | (A-1.0) , WHEN THE STRUCTURAL MEMBERS ARE AFFECTED THE | | | THRESHOLD RULES ARE ENVOKED REQUIRING: | | | | | | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " | | | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH | | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | SECOND REQUEST: | | | A) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A | | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | SECOND REQUEST: | | | B) THRESHOLD INSPECTOR: | | | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES | | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | | CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | C) THRESHOLD BLDG, REQUIRED STATEMENT:COMPLIED. | | | | | | 3) ENERGY CALCS, SEE ELECTRICAL REVIEW. | | | | | | 4) BUILDING PROVISO: THE NEW EXTERIOR AIR PURIFICATION | | | SYSTEM AND SLAB UNDER SEPERATE PERMIT WILL NEED | | | ENGINEERING AS PART OF COMPONENTS AND CLADDING FOR 140 | | | HPH WIND ZONE. | | | | | | 5) SECOND REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | 2008-08-27 09:56:19 | BUILDING PLAN REVIEW | | | PERMIT: 08080195 | | | ADD: 632 HIBISCUS ST | | | CONT: SKYLINE BUILDERS | | | TEL: (954)605-1196 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) PLEASE SUBMIT (3) OF ALL SURVEYS, PLANS, REPORTS, | | | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR | | | REVIEW FOR PERMIT. YOUR PROJECT IS CONSIDERED WITHIN A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR (3) | | | THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR | | | PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST | | | PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C) ) INFORMATIONAL FL S S 713.13 NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS. SHEET A-4.2 | | | STRUCTURAL DESIGN DOES NOT INDICATE TO WHICH CODE AND | | | SUPPLEMENTS THE DESIGN CRITERIA IS DESIGNED TOO. SHEET | | | A-1.0 CODES ALSO NEEDS TO UPDATE THE 2007 SUPDATES TO | | | THE 2004 FBC. | | | | | | 1E) SHEET A-1.0 BUILDING INFORMATION INDICATES THIS TO | | | BE A LEVEL II ALTERATION BUT NEGLECTS THE CHANGE OF | | | OCCUPANCY EXISTING BUILDING CODE CHAPTER 8. | | | | | | 2) PLANS INDICATE THAT THIS IS A FIVE STORY BUILDING | | | (A-1.0) , WHEN THE STRUCTURAL MEMBERS ARE AFFECTED THE | | | THRESHOLD RULES ARE ENVOKED REQUIRING: | | | | | | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " | | | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH | | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | THRESHOLD INSPECTOR: | | | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES | | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | | CODE. | | | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR | | | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION | | | BEFORE | | | THE PERMIT MAY BE ISSUED. | | | | | | THRESHOLD BLDG, REQUIRED STATEMENT: | | | W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING | | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE | | | LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. | | | | | | 3) ENERGY CALCS SUBMITTED ARE 2 SETS ONE AN ORIGINAL | | | SIGNED AND SEALED THE OTHER IS A COPY. PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY | | | THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN | | | PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | | | | 4) BUILDING PROVISO: THE NEW EXTERIOR AIR PURIFICATION | | | SYSTEM AND SLAB UNDER SEPERATE PERMIT WILL NEED | | | ENGINEERING AS PART OF COMPONENTS AND CLADDING FOR 140 | | | HPH WIND ZONE. | | | | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2009-04-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-14 |
Time |
18:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-14 |
Time |
18:09 |
Sent To |
|
|
| Notes |
| 2009-04-14 18:14:05 | REVISION OK, ONCE OK WITH FIRE, NEED TO KEEP ONE SET. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-01-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-08 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-08 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2009-01-08 16:47:28 | NEW SHEET E-2 IN TWO SETS DOES NOT CONTAIN CITY PLACE | | | STAMP. NEW SET FOR THE THIRD SET DOES NOT CONTAIN ANY | | | CITY PLACE MANGEMENT STAMP. THIS IS NOT REQUIRED BY | | | CODE, STATUTE ETC | | | THIS INFORMATION WAS FORWARDED TO ASST BO TO HAVE A | | | REPRESENATIVE COME IN AND STAMP PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-12-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-23 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-23 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2008-12-23 11:21:27 | ** DENIED** | | | | | | 1) NOTE: DETERMINATION OF LIGHTING POWER DENSITY | | | COMPLIANCE CAN NOT BE MADE THE FIXTURE LEGEND IS STILL | | | NOT COMPLETE. FOR EXAMPLE: PLEASE SEE THE TRACK | | | LIGHTING WHICH ONLY INDICATES THE TYPE OF TRACK. THE | | | FIXTURE MUST BE SHOWN AS THE WATTAGE PER | | | 13-415.2.ABC.1.1 IS BASED ON THE VA RATING OF EACH | | | FIXTURE OR 30 VA PER LINEAR FOOT OF TRACK, **WHICH EVER | | | IS GREATER*. IF THE TRACK LIGHTING FIXTURES WERE FOR | | | EXAMPLE 75WATT FIXTURES WITH THE NUMBER OF FIXTURES | | | SHOWN THE TOTAL WATTAGE WOULD BE 2550. THIS WOULD BE | | | FAR GREATER THAN THE 1560 WATTS FIGURED AT 30VA PER FT. | | | THE ENERGY CODE IS BASED ON THE WATTAGE WHICH IS | | | GREATER, NOT JUST A MINIMUM. EVEN IF THE FIXTURES WERE | | | ONLY RATED AT 50WATTS THIS WOULD STILL BE MORE THAN THE | | | 1560 SHOWN IN CALCULATIONS. | | | | | | ** BASED ON EACH OF THESE TWO EXAMPLES OF 75W OR 50W | | | FIXTURES, THE ALLOWANCES AS SHOWN WOULD BE OVER BASED | | | ON CALCULATIONS SHOWN FOR MAXIMUM ALLOWANCES. | | | AS STATED IN THE TWO PREVIOUS REVIEWS ALONG WITH THIS | | | REVIEW IF THERE ARE ANY QUESTIONS PLEASE CALL. LIGHTING | | | ALLOWANCES FOR SPACE BY SPACE NEED TO BE SHOWN FOR | | | SPACE BY SPACE. SOME AREAS MAY BE OVER AS LONG AS SOME | | | OTHER AREAS ARE LESS AND THE TOTAL ALLOWANCE IS NOT | | | EXCEEDED. | | | | | | | | | 2) NOTE: THE SPECIAL INSPECTOR AGREEMENT CONTAINS A | | | RAISED SEAL OVER PHOTO-COPIED SIGNATURES. IN FACT ALL | | | SHEETS ARE PHOTO-COPIES INCLUDING THE SIGNATURES AND | | | STAMPS FROM ALL PARTIES. NOTARY, ENGINEER, INSPECTOR | | | ETC. PLEASE SEE FS 553.79, 471.025, 117, FAC | | | 61G15-23.002. ALL MUST ORIGINAL. | | | ONLY ONE COPY WAS GIVEN TO CONTRACTOR TO OBTAIN ALL NEW | | | ORIGINALS. | | | THE ENGINEER OF RECORD RAISED SEAL FOR MR. OSVALDO | | | AREVALO IS PLACED OVER PHOTO-COPIED LETTERS AND | | | SIGNATURES. | | | ** THESE TWO COPIES WILL BE RETAINED BY THIS OFFICE. | | | DOCUMENTS ALSO SHOWN TO INTERIM ASSISTANT BUILDING | | | OFFICIAL RONALD REGUEIRO. | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-11-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-11-03 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-11-03 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2008-11-03 08:53:38 | | | | | | | | | | | | | ** DENIED 2ND REVIEW ** | | | | | | 1) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2. | | | THE SUBMITTED FORM *C* AS SHOWN MAY NOT BE USED AS IT | | | IS SHOWING SPACE BY SPACE ALLOWANCES. TABLE *C* | | | 13-415.2.C IS FOR BUILDING AREA TYPE. HOWEVER THE | | | SUBMITTED FORM CLEARLY INDICATES TWO SEPARATE SPACES. | | | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN FROM THE | | | FBC AS IT CLEARLY STATES YOU MAY NOT MIX | | | METHODS/TABLE/ALLOWANCES. | | | THE PLANS INDICATE THE SAME ALLOWANCE ALTHOUGH NOT | | | INDICATING A METHOD OF CALCULATION. IN EITHER CASE THE | | | ALLOWANCES AS SHOWN ARE NOT PERMITTED AND THE METHOD IS | | | INCORRECT. | | | THE DINING AREA AS SHOWN ON FORM INDICATES A 2.1 | | | ALLOWANCE HOWEVER NO DINING AREAS AS SHOWN IN TABLE *C* | | | IN THE CODE PERMITS THAT HIGH OF A LIGHTING LEVEL. IN | | | FACT FAMILY DINING IN TABLE C WHICH IS THE HIGHEST IS | | | 1.6. | | | THE FOLLOWING IS A LINE FROM THIS SECTION OF THE CODE. | | | 13-415.2.ABC.1. | | | | | | ** TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE | | | AMONG PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT | | | METHOD OF CALCULATION HAS BEEN USED ARE NOT PERMITTED. | | | | | | ** PLEASE SUBMIT AND SHOW COMPLIANCE WITH THE SECTIONS | | | ABOVE AND IF THERE ARE QUESTIONS PLEASE CALL. ALLOWANCE | | | AS NOTED ON FORM *C* IS OVER. | | | | | | PLEASE BE SURE TO SEE TRACK LIGHTING ALLOWANCES IN | | | SECTIONS ABOVE. | | | | | | | | | 2) NOTE: PLEASE INDICATE MORE INFORMATION FOR THE | | | LIGHTING CONTROL SYSTEM PROPOSED. | | | THE PLANS DO NOT INDICATE IF THERE ARE PILOT LIGHTS AS | | | REQUIRED. SECTION 13-415.1.ABC.1.1,.1.2 REQUIRES THE | | | OVER RIDE FOR NO MORE THAN 4HRS. THESE SAME SECTIONS | | | REQUIRES THE OCCUPANT TO VISUALLY SEE ALL LIGHTING | | | WHICH IS BEING CONTROLLED/OVER RIDDEN. IF THE OCCUPANT | | | CAN NOT SEE *ALL* LIGHTS THEN THE EXCEPTION IS THAT THE | | | LIGHTING CONTROLS REQUIRES PILOT/INDICATOR LIGHTS WHICH | | | ARE REQUIRED TO BE LABELED. IF THE DEVICES AS NOTED | | | CONTAIN THESE INDICATOR/PILOT LIGHTS THEN PLEASE | | | IDENTIFY. | | | | | | 3) NOTE: PREVIOUS NOTE REQUESTED TO SHOW HOW THE TRACK | | | LIGHTING LOADS PER 220.43 ARE FIGURED AND TO PLEASE | | | SHOW. COULD NOT LOCATE ANY CHANGE TO THIS. | | | | | | 4) NOTE: IF BOTH SUITES WHICH ARE SHOWN AS 116 AND 120 | | | ARE GOING TO HAVE TWO MAINS FEEDING WHAT IS NOW GOING | | | TO BE ONE SUITE THAN THIS NEW SINGLE TENANT NEEDS TO | | | HAVE SIGNAGE INDICATING THIS. AS THE APPLIED ADDRESS | | | LOCATION AS SHOWN ON THE TITLE BLOCKS ARE SUITE #116 | | | THAN THE MAINS FOR TENANT BOTH NEED TO BE LABELED SUITE | | | #116 MAIN ONE OF TWO AND 2 OF TWO. RISER SHOWS TWO | | | SEPARATE SUITES. IF THE FIRE DEPARTMENT OR ANY OTHER | | | PERSONNEL NEEDED TO TURN POWER OFF IN ANY EVENT THESE | | | WOULD NOT BE LABELED CORRECTLY. | | | 230.2E, 225.37. (THESE ARE FEEDERS) THE CODE SECTIONS | | | GIVEN ARE FOR SERVICE ENTRANCE AND FEEDERS. THE INTENT | | | OF THE CODE SECTIONS ARE THE SAME AS ALL EQUIPMENT IS | | | REQUIRED TO BE CORRECTLY LABELED. | | | | | | 5) NOTE: PLEASE INDICATE THE HEIGHTS OF DEVICE FOR | | | HORN/STROBES AND ANY PULL STATIONS PER 11-4.28.1,.2 AND | | | .3. | | | THE MINIMUM CANDELA LEVELS ARE SHOWN WHICH ARE OK. | | | | | | | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-08-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-08-28 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-08-28 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2008-08-28 14:09:52 | ** DENIED PLAN ** | | | | | | | | | | | | 1) NOTE:PLEASE SEE THE SUBMITTED METHOD *A* | | | CALCULATIONS MAY NOTBE USED. THIS IS NOT A WHOLE | | | BUILDING. PLEASE SEE 13-101.1 | | | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS AND | | | INDICATE THE METHOD TO BE USED. THE PLANS MENTION WHOLE | | | AREA HOWEVER BASED ON OCCUPANCY TYPE PER 13-415.2.C THE | | | LEVELS OF LIGHTING SHOWN ON PLANS EXCEED THAT PERMITTED | | | BY TABLE C. | | | PLEASE SEE 13-415.2.ABC.1.1,.1.2 AND .1.3 | | | PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND. THE | | | LEGEND MUST BE COMPLETE AT THIS TIME TO FIGURE CORRECT | | | WATTAGE ALLOWANCES. PLEASE KNOW THE WATTAGE WHICH MUST | | | BE USED IS THE MAXIMUM VA OF THE FIXTURE, BALLAST OR | | | TRANSFORMER NOT THE BULB. THE WATTAGE FOR TRACK | | | LIGHTING SHALL BE WHICH EVER IS GREATER. | | | | | | 2) NOTE: PLEASE COMPLETE THE PLANS FOR THE LIGHTING | | | CONTROL SYSTEM AS NOTED.PLANS DO NOT SHOW ANY | | | LOCATIONS FOR LIGHTING CONTROLS. | | | THERE IS NOT ENOUGH INFORMATION ON PLANS AT THIS TIME. | | | PLEASE PROVIDE ESTIMATED SCHEDULING. PLEASE PROVIDE ALL | | | LOCATIONS OF CONTROLS, OVER RIDES AND ZONES. PLEASE BE | | | SURE TO STATE ALL MAXIMUM OVER RIDE TIMES AS WELL AS | | | MAXIMUM TIMES ON ANY OTHER DEVICES. PLEASE SEE SECTION | | | BELOW FOR REQUIRED SEPARATE CONTROLS FOR DISPLAY/ACCENT | | | LIGHTING. | | | 13-415.1.ABC.1.1,.1.2, .1.3 AND ANY EXTERIOR LIGHTING | | | SHALL FALL UNDER .1.4. | | | | | | 3) NOTE: PLEASE INDICATE THE TRACK LIGHTING LOADS PER | | | 220.43. | | | | | | 4) NOTE: PLEASE ALSO SEE THE SUBMITTED ENERGY | | | CALCULATIONS ARE PHOTO-COPIES AND ARE NOT ORIGINAL FAC | | | 61G15-23.002, FS 471.025 | | | | | | | | | | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-16 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2009-04-16 11:12:35 | *****REVISION APPROVED***** | | | | | | | | | REVISED PLAN SHEETS A2.0, E1.0, AND E2.0 WERE STAMPED, | | | INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-01-08 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-01-08 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-01-08 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2009-01-08 16:55:54 | PLANS STAMPED BY MIKE WENNERGREN. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2008-12-29 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-29 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-29 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2008-12-29 10:43:51 | ***DENIED*** | | | | | | COMMENT TAKEN DIRECTLY FROM LAST FIRE REVIEW. | | | | | | | | | 1) EXIT LIGHTS FOR EXIT DOORS ARE SHOWN ON LIFE SAFETY | | | DRAWING A-2.2, BUT ARE NOT SHOWN ON THE LIGHTING PLAN | | | SHEET E2.0. PLEASE CORRELATE APPLICABLE SHEETS TO | | | ILLUSTRATE CORRECT INFORMATION. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-11-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-11-12 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-11-12 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2008-11-12 13:18:21 | ***DENIED*** | | | | | | MOST OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED. | | | PLEASE SEE THE FOLLOWING: | | | | | | 2) OK- EXIT LIGHTS FOR EXIT DOORS ARE SHOWN ON LIFE | | | SAFETY DRAWING A-2.2, BUT ARE NOT SHOWN ON THE LIGHTING | | | PLAN SHEET E2.0. PLEASE CORRELATE APPLICABLE SHEETS TO | | | ILLUSTRATE CORRECT INFORMATION. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-09-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-09-05 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-09-05 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2008-09-05 15:26:55 | *****DENIED***** | | | | | | 1. ON SHEET A2.2, SHOW THE PATH OF EGRESS FROM THE OPEN | | | KITCHEN AREA (ROOM 113) . | | | | | | 2. EXIT LIGHTS ARE SHOWN ON BOTH SIDES OF DOOR #6 | | | LOCATED BETWEEN COORIDOR 111 AND 112. THIS WOULD APPEAR | | | TO BE CONFLICT OF EGRESS USAGE. | | | | | | 3. ON SHEET A3.0 AND E2.0 IN THE CEILING LEGEND, | | | REFERENCE IS MADE TO THE ENGINEERED FIRE SPRINKLER | | | DRAWINGS COMPLING WITH NFPA 96. PLEASE BE ADVISED THAT | | | NFPA 96 IS THE STANDARD FOR VENTILATION CONTROL AND | | | FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS. | | | | | | 4. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THIS | | | SCOPE OF WORK. THESE DEVICES MAY BE SHOWN ON SHEET E1.0 | | | (POWER PLAN) . | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2008-11-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-11-05 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-11-05 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-08-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-14 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-13 |
Time |
17:05 |
Sent To |
|
|
| Notes |
| 2008-11-05 17:07:07 | SEE PLUMBING PLAN REVIEW FOR GAS COMMENTS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-04-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-04-14 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-04-14 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2009-04-14 16:39:16 | TO "COMM" BD#7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-03-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-03-16 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-03-16 |
Time |
16:39 |
Sent To |
P |
|
| Notes |
| 2009-03-16 16:39:57 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-02-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-11 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-11 |
Time |
10:55 |
Sent To |
B |
|
| Notes |
| 2009-02-11 10:56:11 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-12-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-09 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-09 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2008-12-09 10:09:58 | TO "COMM" BD#56 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-10-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-22 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-22 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2008-10-22 08:31:04 | TO "COMM" BD#52 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-09-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-09-05 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-08-08 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2008-08-08 14:59:13 | TO "COMM" BD#55 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2009-04-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-04-03 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-04-03 |
Time |
17:52 |
Sent To |
|
|
| Notes |
| 2009-04-03 17:52:39 | REVISED M-01 DELTA 4 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2009-02-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-18 |
Time |
18:13 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-18 |
Time |
18:12 |
Sent To |
PC |
|
| Notes |
| 2009-02-18 18:13:01 | REVISED M01 FOR OA DUCT CHANGES |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-01-08 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-01-08 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-01-08 |
Time |
16:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-11-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-11-15 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-11-15 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2008-11-15 13:42:22 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. OK | | | | | | 2. OK: IT IS NOT CLEAR HOW TOTAL SEATS WILL PREDICT | | | MAXIMUM OCCUPANCY, INCLUDING EMPLOYEES AND THOSE | | | WAITING TO BE SEATED, BUT WILL DEFER TO THE JUDGEMENT | | | OF THE DESIGN PROFESSIONAL. | | | | | | 3. **PREVIOUS REVIEW COMMENT** PAGE M1.0: NOTE #1, | | | WHICH REFERENCED 13-409.1.ABC.3.3 FOR SHUTOFF DAMPER | | | CONTROLS, CALLS FOR MOTORIZED DAMPER ON THE OA INTAKE | | | FOR AHU #1 WITH NO PROVISIONS FOR AHU #2 OR AHU #3. | | | EVEN THOUGH THEY SHOW LESS THAN 300 CFM, A BACK DRAFT | | | DAMPER, AT A MINIMUM, IS REQUIRED TO MEET THE | | | REQUIREMENTS OF THIS CODE SECTION. | | | **NOT ADEQUATELY ADDRESSED** PAGE M1.0 SHOWS THE | | | ADDITION OF MANUAL VOLUME DAMPERS IN RESPONSE TO THIS | | | COMMENT. AS STATED IN THE PREVIOUS REVIEW COMMENT, A | | | BACKDRAFT DAMPER IS REQUIRED IN O.A. INTAKES IN LIEU OF | | | THE MOTORIZED DAMPERS PER THE REFERENCED SECTION. THE | | | MANUAL VOLUME DAMPERS SATISFY THE REQUIREMENTS OF | | | 13-409.1.ABC.1.1 BUT DO NOT SATISFY THE REQUIREMENTS OF | | | 13-409.1.ABC.3.3. | | | | | | | | | 4. **PREVIOUS REVIEW COMMENT** PAGE M2.0: DIFFUSER AND | | | FLEXIBLE DUCT DETAILS ARE NOT CODE COMPLIANT. THE | | | MINIMUM WIDTH OF HANGERS AND SUPPORTS FOR FLEXIBLE | | | DUCTS SHALL BE 1.5 INCHES AND THE MAXIMUM SAG BETWEEN | | | SUPPORTS SHALL BE 1/2 INCH PER FOOT IN ACCORDANCE WITH | | | FBCM 603.5.6.6. ADJUST DETAILS TO SHOW COMPLIANCE WITH | | | THIS SECTION. | | | **NOT ADEQUATELY ADDRESSED** DETAIL NOW ALLOWS FOR A | | | MAXIMUM OF 1.5 INCES OF SAG PER FOOT OF LENGTH RATHER | | | THAN THE 0.5 INCHES PER FOOT OF LENGTH AS STATED IN | | | PREVIOUS REVIEW COMMENT AND AS REQUIRED BY FBCM | | | 603.5.6.6(4). | | | | | | NOTE: METHOD C CALCS OK FOR MECHANICAL. SEE ELECTRICAL | | | REVIEW COMMENTS. | | | | | | NOTE: NO INFORMATION WAS PROVIDED ON THESE PLANS | | | REGARDING KITCHEN HOOD/EXHAUST AND WALK-IN COOLER | | | SYSTEMS. SEPARATE PERMITS AND PLANS ARE REQUIRED FOR | | | THESE SYSTEMS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-26 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-26 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-25 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2008-08-26 10:59:14 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M1.0: VENTILATION CALCULATIONS STATE THEY ARE | | | BASED ON ASHRAE 62.1-2007. HOWEVER, THE REFERENCED | | | STANDARD IS CURRENTLY ASHRAE 62.1-2004 EDITION IN | | | ACCORDANCE WITH FBCM CHAPTER 15. PLEASE REFERENCE THE | | | CORRECT STANDARD ON THE PLANS AT THE VENTILATION | | | CALCULATIONS TABLE. | | | | | | 2. PAGE M1.0: THE DINING AREA DEFAULT OCCUPANT DENSITY | | | BASED ON TABLE 6-1 FOR DINING ROOMS IS 70/1000 SQ. FT. | | | WITH THE GIVEN SQUARE FOOTAGE OF 1800, THIS GIVES A | | | DEFAULT OCCUPANT LOAD OF 126 PERSONS. BASED ON EQUATION | | | 6-1, THE TOTAL OUTSIDE AIR REQUIRED FOR THE DINING | | | AREAS IS 1269 CFM. PLEASE ADJUST OUTDOOR AIR QUANTITIES | | | ACCORDINGLY. | | | | | | 3. PAGE M1.0: NOTE #1, WHICH REFERENCED | | | 13-409.1.ABC.3.3 FOR SHUTOFF DAMPER CONTROLS, CALLS FOR | | | MOTORIZED DAMPER ON THE OA INTAKE FOR AHU #1 WITH NO | | | PROVISIONS FOR AHU #2 OR AHU #3. EVEN THOUGH THEY SHOW | | | LESS THAN 300 CFM, A BACK DRAFT DAMPER, AT A MINIMUM, | | | IS REQUIRED TO MEET THE REQUIREMENTS OF THIS CODE | | | SECTION. | | | NOTE: BASED ON COMMENT #2, THE OUTSIDE AIR VOLUME FOR | | | EACH UNIT IS LIKELY TO BE OVER 300 CFM AND THEREFORE A | | | MOTORIZED DAMPER WILL BE REQUIRED. | | | | | | 4. PAGE M2.0: DIFFUSER AND FLEXIBLE DUCT DETAILS ARE | | | NOT CODE COMPLIANT. THE MINIMUM WIDTH OF HANGERS AND | | | SUPPORTS FOR FLEXIBLE DUCTS SHALL BE 1.5 INCHES AND THE | | | MAXIMUM SAG BETWEEN SUPPORTS SHALL BE 1/2 INCH PER FOOT | | | IN ACCORDANCE WITH FBCM 603.5.6.6. ADJUST DETAILS TO | | | SHOW COMPLIANCE WITH THIS SECTION. | | | | | | NOTE: THE METHOD A ENERGY CALCULATIONS WHICH WERE | | | SUBMITTED WITH THIS APPLICATION WERE NOT REVIEWED FOR | | | COMPLIANCE WITH THE MECHANICAL PROVISIONS OF FBCB | | | CHAPTER 13. METHOD A CALCULATIONS ARE NEITHER | | | APPROPRIATE NOR REQUIRED FOR THIS PROJECT AS THIS IS | | | NOT A WHOLE BUILDING AND DOES NOT QUALIFY AS A | | | RENOVATION AS DEFINED IN FBCB SECTION 13-202. THE | | | MINIMUM REQUIRED FOR COMPLIANCE WITH FBCB CHAPTER 13 | | | FOR THIS PROJECT CAN BE FOUND IN SECTION 13-101.6 AND | | | ARE AS FOLLOWS: | | | | | | THERMAL EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING | | | BUILDING SYSTEMS WHERE NEW PRODUCTS ARE INSTALLED OR | | | REPLACED IN EXISTING BUILDINGS, AND FOR WHICH A PERMIT | | | MUST BE OBTAINED. SUCH SYSTEMS SHALL MEET THE MINIMUM | | | EFFICIENCIES ALLOWED FOR THAT SYSTEM ON FORM 400C FOR | | | COMMERCIAL BUILDINGS AND ON FORM 600C FOR RESIDENTIAL | | | BUILDINGS. | | | 1. HEATING, VENTILATING OR AIR CONDITIONING SYSTEMS; | | | 2. SERVICE WATER OR POOL HEATING SYSTEMS; | | | 3. ELECTRICAL SYSTEMS AND MOTORS; | | | 4. LIGHTING SYSTEMS. | | | | | | THESE REQUIREMENTS HAVE BEEN DEMONSTRATED ON THE PLANS | | | FOR THE NEWLY INSTALLED MECHANICAL SYSTEMS. PLEASE SEE | | | OTHER TRADE REVIEWS FOR COMMENTS REGRADING OTHER | | | AFFECTED SYSTEMS. | | | | | | NOTE: NO INFORMATION WAS PROVIDED ON THESE PLANS | | | REGARDING KITCHEN HOOD/EXHAUST AND WALK-IN COOLER | | | SYSTEMS. SEPARATE PERMITS AND PLANS ARE REQUIRED FOR | | | THESE SYSTEMS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2009-03-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-27 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-27 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2009-03-27 14:31:29 | REVISION OK -- SHT P1.0 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2009-03-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-18 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-18 |
Time |
18:27 |
Sent To |
|
|
| Notes |
| 2009-03-18 18:31:26 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHT P1.0 ALL REVISIONS TO A SIGNED, SEALED & DATED | | | SET OF PLANS SHALL BE SIGNED, SEALED & DATED BY THE | | | ENGINEER OF RECORD. SECTION 106.1, FAC 61G15023.002 & | | | FS 471.025. | | | | | | 2. SHT P1.0 IS INDICATING THE HAND SINK CONNECTING TO | | | THE LAV STACK FOR THE TOILET ROOM. THIS IS NOT APPROVED | | | PER SECTION 909.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2009-03-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-18 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-18 |
Time |
18:27 |
Sent To |
|
|
| Notes |
| 2009-03-18 18:27:44 | REVISION OK -- SHT P2.0 REVISION #2. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-12-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-18 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-18 |
Time |
16:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2008-11-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-11-05 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-11-05 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2008-11-05 17:08:29 | PASSED/PROVISO -- EXPANSION TANK TO BE DETA-12 MODEL |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-08-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-14 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-13 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2008-08-14 11:33:35 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | MUNICIPAL CODE CITY WPB | | | | | | 1. ALL SHEETS REQUIRE THE "CITY PLACE" APPROVAL STAMP | | | PRIOR TO REVIEW BY CITY WPB. | | | | | | 2. ALL SHTS WITH THE ARCHITECT'S TITLE BLOCK. THE | | | ADDRESS ON THE TITLE BLOCK, 370 CAMINO GARDENS BLVD, | | | DOES NOT REFLECT THE ADDRESS OF RECORD ON THE STATE OF | | | FLORIDA, DBPR WEBSITE. PLEASE UPDATE EITHER THE TITLE | | | BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING TO | | | CITY WPB. FAC 61G1-16.004(1) & FS 481.2055. | | | | | | 3. SHT A-1.0 CODES TO INDICATE ALL UPDATES UP TO 2007. | | | SECTION 106.1.1. | | | | | | 4. ALL ARCHITECTURAL SHEETS. A SIGNATURE IS REQUIRED ON | | | THE DATED SEAL OF EACH SHEET. IT APPEARS THAT INITIALS | | | HAVE BEEN USED. IF THIS IS INDEED THE LEGAL SIGNATURE, | | | THEN A SIGNED, SEALED, NOTORIZED LETTER IS REQUIRED FOR | | | OUR FILES INDICATING THE LEGAL SIGNATURE OF THE | | | ARCHITECT, CRAIG MOSSEY. FAC 61G1-16.003, | | | 61G1-16.004(5) & FS 481.2055. PLEASE SUBMIT | | | VERIFICATION LETTER. ^^^^^^^^(DELETE COMMENT NEXT | | | REVIEW)^^^^^^^ | | | | | | 5. SHTS A-2.4 DETAIL #2 AND A-5.0 FINISH SCHEDULE. | | | ROOMS 106 & 106 WALLS WITH IN 2 FEET OF THE WATER | | | CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT | | | SURFACE. EPOXY PAINT DOES NOT COMPLY WITH THE "HARD" | | | REQUIREMENT. SECTION 1210.2. PLEASE INDICATE METHOD OF | | | COMPLIANCE. | | | | | | 6. SHT P1.0 SANITARY PLAN/ISOMETRIC. THE DISHWASHER | | | SHALL DISCHARGE INTO THE SANITARY SYSTEM PER ARTICLE | | | III SECTION 90-124(7)(B). PLEASE CHANGE FLOOR PLAN AND | | | ISOMETRIC. | | | | | | 7. SHT P1.0 SANITARY PLAN/ISOMETRIC. THE DISCHARGE FROM | | | THE AIR PURIFICATION UNIT SHALL BE THRU AN INDIRECT | | | WASTE RECEPTOR. SECTION 802.1.5. A FLOOR SINK OR HUB | | | DRAIN IS REQUIRED FOR INDIRECT WASTE RECEPTOR. SECTIONS | | | 802.3 & 802.3.2. | | | | | | 8. SHT P2.0 WATER PLAN/ISOMETRIC. A WATER HAMMER | | | ARRESTOR IS REQUIRED ON THE WATER SUPPLY FOR THE | | | DISHWASHER. SECTION 604.9. PLEASE SHOW ON THE | | | ISOMETRIC. | | | | | | 9. A SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE | | | FOLLOWING INFORMATION REQUIRED FOR THE GAS PERMIT: | | | | | | A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | B. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | 10. SHT P3.0 FLOOR SINK DETAIL. THE AIR GAP SHALL BE | | | PER SECTION 802.2.1, MINIMUM TWICE THE EFFECTIVE | | | OPENING OF THE INDIRECT WASTE PIPE. PLEASE INDICATE ON | | | DETAIL. | | | | | | 11. SHT P3.0 ELECTRIC WATER HEATER DETAIL. THERMAL | | | EXPANSION CONTROL IS REQUIRED. SECTION 607.3.2. PLEASE | | | INDICATE METHOD. | | | | | | 12. SHT P3.0 GREASE INTERCEPTOR DETAIL NOTES INDICATES | | | THE INLET PIPING SHALL EXTEND 24" BELOW THE WATER | | | LEVEL, BUT THE DETAIL DOES NOT SHOW THIS. PER SECTION | | | 1003.5.3 THE INLET PIPING SHALL CONNECT TO A TEE WHICH | | | SHALL EXTEND 24" BELOW THE WATER LEVEL. PLEASE HAVE | | | DETAIL REFLECT REQUIREMENT. (CITY WPB APPROVED | | | DETAIL). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2008-08-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2008-08-18 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-08-18 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2008-08-18 13:23:35 | PROVISO: CITYPLACE STAMP REQUIRED ON ALL PLAN SETS. | | | | | | NO EXTERIOR WORK. | | | | | | PLEASE NOTE THAT NO BAR FACILITIES MAY BE INSTALLED. |
|
|