Plan Review Details - Permit 08080193
Plan Review Stops For Permit 08080193
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-10-21 Cont ID  
Sent By jwitmer Date 2009-10-21 Time 09:45 Rev Time 0.66
Received By jwitmer Date 2009-10-21 Time 09:45 Sent To  
Notes
2009-10-21 09:46:38STEEL & TRUSS SHOP DRAWINGS- OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-10-05 Cont ID  
Sent By jwitmer Date 2009-10-05 Time 10:30 Rev Time 1.00
Received By jwitmer Date 2009-10-05 Time 09:30 Sent To  
Notes
2009-10-05 10:31:17REVISION: S1 & S2 DATED 09-29-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-24 Cont ID  
Sent By jwitmer Date 2008-10-24 Time 16:51 Rev Time 0.55
Received By jwitmer Date 2008-10-24 Time 16:51 Sent To  
Notes
2008-10-24 16:51:49BUILDING PLAN REVIEW
 PERMIT: 08080193
 ADD: 118 S CLEMATIS ST
 CONT: FIVE STAR CONSTRUCTION
 TEL: (561)436-8508
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: REVIEWED -OK
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) COMPLIED.
  
 3) BUILDING PROVISO: BRICK VENEER: 2114.2 EXCEPTION. 6"
 AIR GAP REQUIRED FOR TERMITE INSPECTION.A 6" EXISTING
 STUCCO BAND FROM GRADE BEFORE BRICK VENEER TO START.
 PROVIDED AT LEAST A 6-INCH (152 MM) CLEAR INSPECTION
 SPACE OF THE FOUNDATION SIDEWALL EXTERIOR EXIST BETWEEN
 THE VENEER AND THE TOP OF ANY SOIL, SOD, MULCH OR OTHER
 ORGANIC LANDSCAPING COMPONENT, DECK, APRON, PORCH, WALK
 OR ANY OTHER WORK IMMEDIATELY ADJACENT TO OR ADJOINING
 THE STRUCTURE.
  
 4) COMPLIED.
  
 5) BUILDING PROVISO: PROVIDE BY THE FIRST INSPECTION.
 PLANS DO NOT PROVIDE TYPE OF MATERIALS FOR ADHERED
 VENEER SYSTEMS 1405.9.
  
 7) PROVISO: SEPERATE PERMIT REQUIRED FOR AWNINGS.
  
 8) COMPLIED.
  
 9-12) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-08 Cont ID  
Sent By jwitmer Date 2008-10-08 Time 08:34 Rev Time 0.77
Received By jwitmer Date 2008-10-08 Time 08:34 Sent To  
Notes
2008-10-08 08:40:00BUILDING PLAN REVIEW
 PERMIT: 08080193
 ADD: 118 S CLEMATIS ST
 CONT: FIVE STAR CONSTRUCTION
 TEL: (561)436-8508
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: REVIEWED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) COMPLIED.
  
 3) BUILDING PROVISO: BRICK VENEER: 2114.2 EXCEPTION. 6"
 AIR GAP REQUIRED FOR TERMITE INSPECTION.A 6" EXISTING
 STUCCO BAND FROM GRADE BEFORE BRICK VENEER TO START.
 PROVIDED AT LEAST A 6-INCH (152 MM) CLEAR INSPECTION
 SPACE OF THE FOUNDATION SIDEWALL EXTERIOR EXIST BETWEEN
 THE VENEER AND THE TOP OF ANY SOIL, SOD, MULCH OR OTHER
 ORGANIC LANDSCAPING COMPONENT, DECK, APRON, PORCH, WALK
 OR ANY OTHER WORK IMMEDIATELY ADJACENT TO OR ADJOINING
 THE STRUCTURE.
  
 4) COMPLIED.
  
 5) BUILDING PROVISO: PROVIDE BY THE FIRST INSPECTION.
 PLANS DO NOT PROVIDE TYPE OF MATERIALS FOR ADHERED
 VENEER SYSTEMS 1405.9.
  
 7) PROVISO: SEPERATE PERMIT REQUIRED FOR AWNINGS.
  
 8) COMPLIED.
  
 9-12) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-26 Cont ID  
Sent By jwitmer Date 2008-08-26 Time 14:34 Rev Time 2.33
Received By jwitmer Date 2008-08-26 Time 14:34 Sent To  
Notes
2008-08-26 16:03:37BUILDING PLAN REVIEW
 PERMIT: 08080193
 ADD: 118 S CLEMATIS ST
 CONT: FIVE STAR CONSTRUCTION
 TEL: (561)436-8508
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) PLANS INDICATE CHANGE OUT OF WINDOWS ON THE 2ND
 FLOOR, BUT FAIL TO PROVIDE WIND INFORMATION:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) ELEVATIONS FOUND ON SHEET 1.1A INDICATE A NEW BRIVK
 VENEER FRONT TO BE ADDED TO THE BUILDING. PLEASE
 PROVIDE COMPLIANCE WITH THE 6 INCH AIR GAP REQUIRED FOR
 THE INSPECTION OFR TERMITES.
 2114.2 CONCRETE BEARING LEDGE.
 BRICK , STONE OR OTHER VENEER SHALL BE SUPPORTED BY A
 CONCRETE BEARING LEDGE AT LEAST EQUAL TO THE TOTAL
 THICKNESS OF THE BRICK , STONE OR OTHER VENEER, WHICH
 IS POURED INTEGRALLY WITH THE CONCRETE FOUNDATION. NO
 SUPPLEMENTAL CONCRETE FOUNDATION POURS WHICH WILL
 CREATE A HIDDEN COLD JOINT SHALL BE USED WITHOUT
 SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS THERE
 IS AN APPROVED PHYSICAL BARRIER. AN APPROVED PHYSICAL
 BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE WALL
 SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO EMBED
 IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS BELOW
 GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE APPLIED
 TO THE CAVITY CREATED BETWEEN THE VENEER AND THE
 FOUNDATION, IN LIEU OF A PHYSICAL BARRIER.
 EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL
 SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH
 ACI 530/ASCE 5/TMS 402, PROVIDED AT LEAST A 6-INCH (152
 MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL
 EXTERIOR EXIST BETWEEN THE VENEER AND THE TOP OF ANY
 SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING
 COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK
 IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE.
  
 4) PLANS FAIL TO INDICATE HOW THE GRAVITY LOADS OF THE
 BRICK FACADE WILL BE RESISTED OVER THE DOOR HEADERS?
 ADDITIONAL INFORMATION REQUIRED. 106.1.2.
  
 5) PLANS DO NOT PROVIDE TYPE OF MATERIALS FOR ADHERRED
 VENNER SYSTEMS 1405.9.
  
 7) THE AWNINGS WILL REQUIRE A SEPERATE PERMIT BUT HOW
 WILL THE LOADS OF THE AWNINGS BE TRANSFERRED BACK
 THROUGH THE BRICK VENEER INTO THE STRUCTURE? 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
 1609 .1.3.ANCHORAGE AGAINST OVERTURNING.
  
 8) 1405.3 FLASHING.
 FLASHING SHALL BE INSTALLED IN SUCH A MANNER SO AS TO
 PREVENT MOISTURE FROM ENTERING THE WALL OR TO REDIRECT
 IT TO THE EXTERIOR. FLASHING SHALL BE INSTALLED AT THE
 PERIMETERS OF EXTERIOR DOOR AND WINDOW ASSEMBLIES,
 PENETRATIONS AND TERMINATIONS OF EXTERIOR WALL
 ASSEMBLIES, EXTERIOR WALL INTERSECTIONS WITH ROOFS,
 CHIMNEYS, PORCHES, DECKS, BALCONIES AND SIMILAR
 PROJECTIONS AND AT BUILT-IN GUTTERS AND SIMILAR
 LOCATIONS WHERE MOISTURE COULD ENTER THE WALL. FLASHING
 WITH PROJECTING FLANGES SHALL BE INSTALLED ON BOTH
 SIDES AND THE ENDS OF COPINGS, UNDER SILLS AND
 CONTINUOUSLY ABOVE PROJECTING TRIM.
  
 9) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) NOA 06-0405.06 PGT HR-710 HORIZONTAL ROLLER WINDOW
 IS 63" TALL WHERE AS THE ELEVATION INDICATES THE
 SLIDERS TO BE AT LEAST 7'-0" TALL AND THE PLANS
 INDICATE IMPACT BYPASS SLIDERS. DOES THE SLIDING GLASS
 UNIT GO ALL THE WAY TO THE FLOOR? PLEASE PROVIDE TTHE
 FLASHING DETAIL OF THE SILL AND TRANSITION TO BRICK.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 11) SHEET 1.1A SECTION 1-1.1A INDICATES A NEW 16X25
 STEEL BEAM (4) AND A NEW 5"X5"X1/4" STEEL COLUMN. PLANS
 DO NOT INDICATE HOW THE BEAM IS ATTACHED TO THE
 STRUCTURE ABOVE, FOR UPLIFT LOADS?
 NOR DOES THE PLANS INDICATE THE HOW THE NORTH END OF
 THE BEAM IS SUPPORTED, AND HOW THE STEEL COLUMN IS
 ATTACHED TO THE STEEL BEAM. PLANS FAIL TO INDICATE IF
 THERE IS A BOTTOM PLATE ON THE STEEL COLUMN,
 SIZE OF PLATE THICKNESS OF PLATE, AMOUNT OF ANCHORING
 HOLES NOR SIZE OF HOLE AND TYPE OF ANCHORS TO BE
 INSTALLED. IS THE EXISTING FLOOR SUFFICIENT ENOUGH TO
 TAKE THE CONCENTRATED LOAD OF THE COLUMN OR WILL A NEW
 FOUNDATION BE REQUIRED? 106.1.2 ADITIONAL INFORMATION
 IS REQUIRED, 106.1.2 ?
  
 12) SHEET 1.0A INDICATES IN THE REAR OF THE BUILDING A
 NEW FLOOR INTERCEPTOR IS TO BE PLACED, PLEASE PROVIDE
 INFORMATION ON THE FLOOR REPLACEMENT, 106.1.2,
 ADDITIONAL INFORMATION REQUIRED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-28 Cont ID  
Sent By dpalmer Date 2008-10-28 Time 10:22 Rev Time 0.00
Received By dpalmer Date 2008-10-28 Time 10:22 Sent To  
Notes
2008-10-28 10:22:46EXISTING UPSTAIRS SHOWN ON PLANS FOR REFERENCE ONLY.
 ALL LIFE SAFETY SHOWN AS EXISITNG SHALL BE VERIFIED
 ON-SITE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-21 Cont ID  
Sent By dpalmer Date 2008-10-21 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2008-10-21 Time 14:43 Sent To  
Notes
2008-10-21 14:44:02 
 ** DENIED 2ND REVIEW**
  
  
  
  
 1) NOTE: PLANS NOW INDICATE RE-USE OF EXISTING
 OCCUPANCY SENSOR HOWEVER HOW IS THIS POSSIBLE WHEN THIS
 AREA IS NEW?
 THESE ARE NEW DEVICES AND NOT ALL FIXTURES ARE EXISTS?
 LABEL NEW DEVICE TO BE INSTALLED.
 LABEL NEW FIXTURES.
 13-415.1.ABC.1.1, .1.2, 13-415.2, ETC
  
 2) NOTE: AS THE SECOND FLOOR IS NOW BECOMING THE PLACE
 OF USE FOR BATHROOMS ETC WE STILL NEED TO SEE THIS AREA
 AS MEETING CODE FOR LIFE SAFETY ETC. NO PLANS WERE
 SUBMITTED SHOWING NEW OR EXISTING CONDITIONS.
 A SITE VISIT TO SEE EXISTING CONDITIONS MAY BE
 REQUIRED.
 RESPONSE LETTER MENTIONS TO SEE REVISED PLANS HOWEVER
 ONLY PART OF THE ONE E-SHEET WAS REVISED.
 NFPA-101 7.8,7.9, NEC 2005, FBC 13-415.1, .2
 FBC 106.1.1 FOR COORDINATION, INFORMATION AND CLARITY
 OF PLANS/SCOPE.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-28 Cont ID  
Sent By dpalmer Date 2008-08-28 Time 14:54 Rev Time 0.00
Received By dpalmer Date 2008-08-28 Time 14:54 Sent To  
Notes
2008-08-28 14:54:11 
  
  
  
  
 ** DENIED PLAN **
  
 08080193
 CABANA REMODEL
  
  
 1) NOTE: PLEASE CLARIFY NOTES ON PLANS. THERE ARE NOTES
 WHICH MENTIONS NEW LIGHTING CONTROLS ETC HOWEVER THERE
 IS A NOTE THAT * NOT ALL NOTES APPLY*.
  
 THE PLANS MENTION REWIRING OF CIRCUITS. IF THIS IS THE
 CASE THE NEW WIRING LIGHTING CONTROLS NEED TO MEET
 PRESCRIPTIVE REQUIREMENTS.13-415.1.ABC.1.1,.1.2 AND
 .1.3
 THE LAYOUT OF THE LIGHTING AS SHOWN DOES NOT APPEAR TO
 BE THE SAME AS ON-SITE AT THIS TIME.
 IN FACT THE EXISTING BATHROOM LOCATION IS SHOWING ALL
 LIGHTING AS EXISTING TO BE REWORKED YET NO NEW LIGHTING
 CONTROLS ETC ARE SHOWN. THE LIGHTING SHOWN IS NOT THE
 SAME AS EXISTING. THIS HAS BEEN VERIFIED BY REVIEWER
 ON-SITE.
  
 2) NOTE: PLEASE KNOW PLANS AS SUBMITTED ARE INCOMPLETE
 AT THIS TIME. PLEASE SUBMIT THE COMPLETE PLANS FOR
 SECOND FLOOR SHOWING COMPLIANCE WITH ALL APPLICABLE
 CODES. PLEASE KNOW SINCE SUBMITTED PLANS AT THIS TIME
 ARE NOT COMPLETE, THERE MAY VERY WELL BE NEW COMMENTS
 ON THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
 PLANS WILL NEED TO VERIFY CODE FOR LIFE SAFETY, FLORIDA
 BUILDING CODE, ELECTRICAL CODE, ETC
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2008-10-30 Cont ID  
Sent By mwennerg Date 2008-10-30 Time 11:05 Rev Time 0.00
Received By mwennerg Date 2008-10-30 Time 11:05 Sent To  
Notes
2008-10-30 11:06:16PLANS APPROVED AND STAMPED ON 10/21/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-21 Cont ID  
Sent By mwennerg Date 2008-10-21 Time 15:37 Rev Time 0.00
Received By mwennerg Date 2008-10-21 Time 15:37 Sent To  
Notes
2008-10-21 15:38:42ADDRESS SHALL BE MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND
 CONTRASTING WITH BACKGROUND.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-09-09 Cont ID  
Sent By mwennerg Date 2008-09-09 Time 14:52 Rev Time 0.00
Received By mwennerg Date 2008-09-09 Time 14:52 Sent To  
Notes
2008-09-09 15:10:36***DENIED***
  
 1) ILLUSTRATE ADDRESS ON SHEET 1.1A, NEW OR EXISTING
 THAT SHALL BE MINIMUM 6" IN HEIGHT, 1" WIDTH AND
 CONTRASTING WITH THE BACKGROUND.
  
 2) ARE ANY DOORS PROVIDED WITH PANIC OR FIRE EXIT
 HARDWARE? NFPA 101, 2003 REQUIRES PANIC OR FIRE EXIT
 HARDWARE ON EXIT DOORS SERVING AN OCCUPANT LOAD OF 100
 OR MORE.
  
 3) ADDRESS TO BE DISPLAYED ON EACH SHEET SUBMITTED FOR
 REVIEW.
  
 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 5) SCOPE OF WORK INDICATES SECOND FLOOR WORK. SUBMIT
 ALL APPROPRIATE SHEETS FOR REVIEW.
  
 6) ILLUSTRATE LOCATION OF REQUIRED 2A-10B,C RATED FIRE
 EXTINGUISHERS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-10-08 Cont ID  
Sent By kstevens Date 2009-10-08 Time 14:19 Rev Time 0.00
Received By kstevens Date 2009-10-08 Time 14:19 Sent To  
Notes
2009-10-08 14:20:14SENT TO JWITMER.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-10-01 Cont ID  
Sent By jwitmer Date 2009-10-01 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2009-10-01 Time 08:16 Sent To  
Notes
2009-10-01 08:17:16SENT TO JW

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-23 Cont ID  
Sent By shill Date 2008-10-23 Time 14:54 Rev Time 0.00
Received By shill Date 2008-10-23 Time 14:54 Sent To  
Notes
2008-10-23 14:58:08TO "COMM" BD#11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-30 Cont ID  
Sent By adarroug Date 2008-09-30 Time 10:46 Rev Time 0.00
Received By adarroug Date 2008-09-30 Time 10:46 Sent To  
Notes
2008-09-30 10:47:26TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-30 Cont ID  
Sent By adarroug Date 2008-09-30 Time 10:44 Rev Time 0.00
Received By adarroug Date 2008-09-30 Time 10:44 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-09 Cont ID  
Sent By mwennerg Date 2008-09-09 Time 15:11 Rev Time 0.00
Received By mwennerg Date 2008-08-08 Time 14:04 Sent To  
Notes
2008-08-08 14:10:51TO "COMM" BD#27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-10-10 Cont ID  
Sent By tgordon Date 2008-10-10 Time 14:47 Rev Time 0.30
Received By tgordon Date 2008-10-10 Time 14:47 Sent To  
Notes
2008-10-10 14:48:21LETTER SUBMITTED 10-7-08 TO H. MOSER TO VOID MECHANICAL
 PERMIT #08080205.
  
 NO MECHANICAL PLANS SUBMITTED, AND NO MECHANICAL WORK
 TO BE DONE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-14 Cont ID  
Sent By tgordon Date 2008-08-14 Time 09:54 Rev Time 0.30
Received By tgordon Date 2008-08-14 Time 09:54 Sent To  
Notes
2008-08-14 09:56:11PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PERMIT #08080205 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW OR VOID MECHANICAL
 PERMIT, PER 2004 FBC CITY OF WPB AMEND. 106.3.5.4 (10).

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-11-06 Cont ID  
Sent By kstevens Date 2008-11-06 Time 11:45 Rev Time 0.00
Received By kstevens Date 2008-11-06 Time 11:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-10-03 Cont ID  
Sent By kstevens Date 2008-10-03 Time 15:30 Rev Time 0.00
Received By kstevens Date 2008-10-03 Time 15:30 Sent To  
Notes
2008-10-03 15:37:45DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. SUBMIT A FLOOR PLAN FOR THE SECOND FLOOR SHOW ALL
 REQUIRED MINIMUM FACILITIES PER TABLES 1004.1.2 & 403.1
 AS WELL AS ALL THE SEATING TO VERIFY THE SEATING COUNT
 INDICATED ON SHT C-2. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT THE SEATING SHALL BE SHOWN TO
 VERIFY MINIMUM FACILITIES REQUIRED BY TABLE 403.1.
  
 2. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM AND A
 WATER ISOMETRIC RISER DIAGRAM PER SECTION 106.3.5.1.3.
 SHOW ALL THE PIPE SIZES, CLEANOUTS, TRAPS AND VENTS FOR
 THE SANITARY RISER, AND SHOW ALL PIPE SIZES, VALVES
 AND, (WHERE REQUIRED BY SECTION 604.9), WATER HAMMER
 ARRESTORS. SECTIONS 704, 706, 708, 710, 604, 606 &
 607.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM SHOWS THE
 BUILDING DRAIN CAPPED OFF UPSTREAM OF THE HAND SINK AND
 FLOOR SINK. PLEASE INDICATE WHERE THE TOILET ROOMS AND
 ANY OTHER FIXTURE ON THE 2ND FLOOR CONNECT TO THE
 BUILDING SEWER. SECTIONS 106.1.1 &301.3.
  
 3. SHT 1.0A WITH THE STATE OF FLORIDA DBPR STAMP SHALL
 BE SIGNED, SEALED AND DATED AS REQUIRED IN SECTION
 106.1, FAC 61G15-23.002(1), 61G1-16.001, FS 471.025 &
 481.2055.
 ****RESPONSE NOTED, BUT THE SHEET WITH THE DBPR STAMP
 IS NOT SIGNED AND SEALED IN ONE SET AND HAS BEEN
 DELETED IN THE OTHER SET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By kstevens Date 2008-08-13 Time 06:31 Rev Time 0.00
Received By kstevens Date 2008-08-12 Time 12:57 Sent To  
Notes
2008-08-13 06:54:53DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SUBMIT A FLOOR PLAN FOR THE SECOND FLOOR SHOW ALL
 REQUIRED MINIMUM FACILITIES PER TABLES 1004.1.2 & 403.1
 AS WELL AS ALL THE SEATING TO VERIFY THE SEATING COUNT
 INDICATED ON SHT C-2. SECTION 106.1.2.
  
 2. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM AND A
 WATER ISOMETRIC RISER DIAGRAM PER SECTION 106.3.5.1.3.
 SHOW ALL THE PIPE SIZES, CLEANOUTS, TRAPS AND VENTS FOR
 THE SANITARY RISER, AND SHOW ALL PIPE SIZES, VALVES
 AND, (WHERE REQUIRED BY SECTION 604.9), WATER HAMMER
 ARRESTORS. SECTIONS 704, 706, 708, 710, 604, 606 &
 607.
  
 3. SHT 1.0A WITH THE STATE OF FLORIDA DBPR STAMP SHALL
 BE SIGNED, SEALED AND DATED AS REQUIRED IN SECTION
 106.1, FAC 61G15-23.002(1), 61G1-16.001, FS 471.025 &
 481.2055.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-06 Cont ID  
Sent By mflis Date 2008-10-06 Time 15:40 Rev Time 0.00
Received By mflis Date 2008-10-06 Time 15:40 Sent To  
Notes
2008-10-06 15:41:55ZONING REVIEW: PASSED WITH PROVISO
  
 ** AWNINGS SHALL BE SUBMITTED UNDER SEPARATE PERMIT
  
 MATT FLIS - 822-1439
  
 (ANA MARIA APONTE)

Review Stop Z ZONING
Rev No 1 Status P Date 2008-08-21 Cont ID  
Sent By aaponte Date 2008-08-21 Time 09:41 Rev Time 0.00
Received By aaponte Date 2008-08-21 Time 09:41 Sent To  
Notes
2008-08-21 09:41:45AWNINGS NOT INCLUDED UNDER THIS PERMIT APPROVAL. A
 SEPARATE AWNING PERMIT SHALL BE SUBMITTED.